F20
4 Start-Up
HI 800 143 E Rev. 1.01
Page 37 of 56
System parameter
Data
type
R/W Description
Module.Error Code
WORD
R
Module error code
Coding
Description
0x0000
I/O processing, if required with errors,
see other error codes
0x0001
No I/O processing (CPU not in RUN)
0x0002
No I/O processing during the booting test
0x0004
Manufacturer interface operating
0x0010
No I/O processing: incorrect configuration
0x0020
No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module.SRS
[UDINT]
R
Slot number (System Rack Slot)
Module.Type
[UINT]
R
Type of module, target value: 0x00A5 [165
dec
]
1)
LS/LB (LS = short-circuit, LB = open-circuit)
Table 27: SILworX - System Parameters for the Digital Inputs,
Module
Tab
4.3.2.2
DIO 8/8: DO Channels
Tab
The
DIO 8/8: DO Channels
tab contains the following system parameters.
System parameter
Data
type
R/W Description
Channel no.
---
R
Channel number, defined by default
-> Error Code
[BYTE]
BYTE
R
Error codes for the digital output channels
Coding
Description
0x01
Fault in the digital output module
0x02
Channel shutdown due to overload
0x04
Error while reading back the digital outputs
0x08
Error while reading back the status of the
digital outputs
0x20
Impossible to activate the output (wrong
configuration)
Value [BOOL] ->
BOOL
W
Output value for DO channels:
1 = output energized
0 = output de-energized
Channel Used
[BOOL] ->
BOOL
W
Configuration of the digital channels as input or output:
1 = The digital channel is used as output
0 = The digital channel is used as input
Table 28: SILworX - System Parameters for the Digital Inputs,
DIO 8/8: DO Channels
Tab