3 Product Description
F20
Page 24 of 56
HI 800 143 E Rev. 1.01
TCP ports
Use
502
Modbus (can be modified by the user)
xxx
TCP SR assigned by the user
44818
Ethernet/IP Explicit Messaging Services
Table 11: Network Ports (TCP Ports) in Use
3.4.2.3
Connections for Fieldbus Communication
The two 9-pole D-sub connectors are located on the front plate of the enclosure.
Designation
Fieldbus submodule
Protocols
FB 1
(with Module)
PROFIBUS master
PROFIBUS slave
RS485 module
RS232 module
RS422 module
INTERBUS master
PROFIBUS DP master
PROFIBUS DP slave
RS485 for Modbus (master or slave) and
ComUserTask
RS232 for ComUserTask
RS422 for ComUserTask
INTERBUS master
1)
FB 2
RS485
RS485 for Modbus (master or slave) and
ComUserTask
1)
INTERBUS is not supported in SILworX.
Table 12: Connections for Fieldbus Communication
The fieldbus submodule for communication using FB1 is optional and must be mounted by
the manufacturer.
3.4.3
Pin Assignments
The following tables describe the Pin assignments of the fieldbus connectors.
3.4.3.1
Pin Assignment of the D-sub Connector FB1
with fieldbus submodule for PROFIBUS DP master or slave
Connection
Signal
Function
1
- - -
- - -
2
- - -
- - -
3
RxD/TxD-A
Receive/send data A
4 RTS Control
signal
5 DGND
Data
ground
6
VP
5 V, plus pole supply voltage
7
- - -
- - -
8
RxD/TxD-B
Receive/send data B
9
- - -
- - -
Table 13: Pin Assignment of D-sub Connector FB1 for PROFIBUS