Technical data
94/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
Category
Parameter
Value
Rated operational voltage
24 V DC
-15 % +20 %
Input voltage residual ripple
≤
5 %
Protection against polarity reversal
Yes
max. current I
max
3 A
Note
: If contactors with a total power consumption
> 3 A are connected, a power feeder module
EU5C-SWD-PF1/2 has to be used.
Short-circuit strength
No, external fuse FAZ Z3
Heat dissipation
Typ. 1 W
Potential isolation
No
Supply voltage U
AUX
Rated operating voltage of 24-V-DC
slaves
Typical U
AUX
-0,2 V
Supply voltage
24 V DC
-15 % +20 %
Input voltage residual ripple
≤
5 %
Protection against polarity reversal
Yes
Rated operational current I
111 mA (with two participants)
Heat dissipation at 24 V DC
2.66 W (with two participants)
Potential isolation between U
POW
and 15-V-SmartWire-DT supply
voltage
No
Bridging voltage dips
10 ms
Repeat rate
1 s
Supply voltage U
POW
Status display
POW
LED
Rated operational voltage U
e
15 V ± 3 %
max. current I
max
0.7 A
Note
: If contactors with a total power consumption
> 0.7 A are connected, a power feeder module
EU5C-SWD-PF2 has to be used.
SmartWire-DT supply
voltage
Short-circuit strength
Yes
Connection type
Push-in terminals
solid
0.2 – 1.5 mm
2
(AWG 24 – 16)
Connection supply
voltages
Flexible with ferrule
0.25 – 1.5 mm
2
Participant type
SmartWire-DT master
SmartWire-DT Master ASIC
SWD-80P-RS485
Number of SmartWire-DT slaves
99
Baud rate
125 / 250 kBd
SmartWire-DT network
Address setting
Automatic