Parameterization
71/98
SmartWire-DT Gateway | EU5C-SWD-ETHERCAT
DOC140901UM01EN | Revision 1 | English | 2015-03 | Released | Public
© Hilscher 2015
The
Data
column of the
Startup
tab displays the changed hexadecimal
value of the parameters byte (the corresponding decimal value is
displayed in brackets).
Figure 36: Editing device parameters of SWD device (3)
In the main menu of the TwinCAT System Manager, choose
Actions
>
Activate Configuration…
to download the changed configuration data.
9.3.3.4
Example of calculating the parameters byte
This example shows how to calculate the default value
0x50
of the
parameter byte of the
EU5E-SWD-4AX
SWD
device.
Bit 0 (Sensor selector input 1)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 1 (Sensor selector input 2)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 2 (Sensor selector input 3)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 3 (Sensor selector input 4)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 4 (Reading refresh rate)
=
TRUE
(1)
=
16
(Dez)
=
0x10
(Hex)
+
Bit 5 (Reading refresh rate)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
+
Bit 6 (Mean value/averaging)
=
TRUE
(1)
=
64
(Dez)
=
0x40
(Hex)
+
Bit 7 (Reserved)
=
FALSE
(0)
=
0
(Dez)
=
0x00
(Hex)
=
Parameter Byte
80
(Dez)
=
0x50
(Hex)