4. Set the switch to on to enable the M1 card encryption
function.
5. Set the sector ID.
The sector ID ranges from 1 to 100.
6. Click Save to save the settings.
Set RS-485 Parameters
You can set the access control device's RS-485 parameters
including the baud rate, data bit, the stop bit, parity type, flow
control type, communication mode, work mode, and connection
mode.
Steps
Note
The RS-485 Settings should be supported by the device.
1. Enter the Access Control module.
2. On the navigation bar on the left, enter Advanced Function →
More Parameters .
3. Select an access control device in the device list and click
RS-485 to enter the RS-485 Settings page.
4. Select the serial port number from the drop-down list to set
the RS-485 parameters.
5. Set the baud rate, data bit, the stop bit, parity type,
communication mode, working mode, and connection mode in
the drop-down list.
6. Click Save.
• The configured parameters will be applied to the device
automatically.
• After changing the working mode or connection mode, the
device will reboot automatically.
Set Wiegand Parameters
You can set the access control device's Wiegand channel and the
communication mode. After setting the Wiegand parameters, the
device can connect to Wiegand card reader via Wiegand
communication.
Steps
Note
This function should be supported by the device.
1. Enter the Access Control module.
2. On the navigation bar on the left, enter Advanced Function →
More Parameters .
3. Select an access control device in the device list and click
Wiegand to enter the Wiegand Settings page.
4. Set the switch to on to enable the Wiegand function for the
device.
5. Select the Wiegand channel No. and the communication mode
from the drop-down list.
86