IC100CX SERVICE MANUAL
Manual IC100CX GB
Page 13 di 20
CF39
RL2 configuration
0 = Alarm relay
1 = compressor 1 capacity step
2 = compressor 2
3 = ON/OFF ventilation
4 = reversing valve
5 = anti-freezer heaters / integration heater n.1
6 = solenoid valve on water circuit
7 = solenoid valve on water circuit only for heat pump
8= anti-freezer heaters / integration heater n. 2
9 = evaporator water pump / supply fan (air / air unit)
10= condenser water pump
0
10
CF40
RL3 configuration
0 = Alarm relay
1 = compressor 1 capacity step
2 = compressor 2
3 = ON/OFF ventilation
4 = reversing valve
5 = anti-freezer heaters / integration heater n.1
6 = solenoid valve on water circuit
7 = solenoid valve on water circuit only for heat pump
8= anti-freezer heaters / integration heater n. 2
9 = evaporator water pump / supply fan (air / air unit)
10= condenser water pump
0
10
CF41
Open collector output configuration
0 = Alarm relay
1 = compressor 1 capacity step
2 = compressor 2
3 = ON/OFF ventilation
4 = reversing valve
5 = anti-freezer heaters / integration heater n.1
6 = solenoid valve on water circuit
7 = solenoid valve on water circuit only for heat pump
8= anti-freezer heaters / integration heater n. 2
9 = evaporator water pump / supply fan (air / air unit)
10= condenser water pump
0
10
CF42
Switching time of reversing valve when the compressor is switched off
0
250
CF43
Default viewing of lower display of the controller
0 = PB1 visualization
1 = PB2 visualization
2 = PB3 visualization
3 = PB4 visualization
4 = Real working set point (set point modified from Energy Saving, Dynamic set point, function for units
without water storage tank)
5 = Unit status
6 = Clock
7 = No visualization
8 = Woking differential
9 = Unit set point (parameter value)
0
8
CF44
Default viewing of upper display of the remote keyboard
0 = PB1 visualization
1 = PB2 visualization
2 = no visualization (display off)
3 = PB4 visualization
4 = Real working set point (set point modified from Energy Saving, Dynamic set point, function for units
without water storage tank)
5 = Unit status
6 = No visualization (display off)
7 = No visualization (display off)
8 = Woking differential
9 = Unit set point (parameter value)
0
8
CF45
Default viewing of lower display of the remote keyboard
0 = PB1 visualization
1 = PB2 visualization
2 = PB3 visualization
3 = PB4 visualization
4 = Real working set point (set point modified from Energy Saving, Dynamic set point, function for units
without water storage tank)
5 = Unit status
6 = Clock
7 = No visualization
8 = Woking differential
9 = Unit set point (parameter value)
0
8
CF46
Controller: visualization in Std-by mode
0 = default visualization (CF36 and CF43 parameters)
1 = the display visualizes “OFF”
2 = the display visualizes “StbY”
0
2