IC100CX SERVICE MANUAL
Manual IC100CX GB
Page 18 di 20
DF07
Maximum defrost duration
0
250 Min
DF08
Compressor Off time before starting a defrost cycle
0
250 Sec
DF09
Compressor Off time after a defrost cycle
0
250 Sec
DF10
Interval time between defrost cycles
1
99 MIN
DF11
Temperature setpoint to start a combined defrost cycle after the DF10 counting time
-50.0
-58
110
230
°C
°F
Decimal
integer
DF12
Temperature Setpoint to stop a combined defrost
-50.0
-58
110
230
°C
°F
Decimal
integer
DF13
Forced activation of the 2
nd
compressor in defrost
0= Not enabled
1= Enabled
0
1
DF14
Forced fan activation during defrost and draining times
0= Not enabled
1= Enabled only for defrost
2= Enabled for defrost and draining time (dF09)
0
2
DF15
Temperature/Pressure Setpoint to start a forced condensing fan control in defrost cycle
-50.0
-58
0.0
0
110
230
50
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
DF16
Low alarm control during defrost
0= Not enabled
1= Enabled
0
1
DF17
Low alarm delay time after changing the status of the 4-ways valve
0
250 Sec
DF18
4-ways reversing valve
0= ON in cooling
1= ON in heating
0
1
DF19
Temperature/pressure Setpoint to start a forced defrost cycle
-50.0
-58
0.0
0
110
230
50
725
°C
°F
bar
psi
Decimal
integer
Decimal
integer
DF20
Forced defrost cycle differential
0.0
0
0.0
0
25.0
45
50.0
725
°C
°F
Decimal
Integer
Decimal
Integer
DF21
Fan status during defrost
0
1
Pr2
Password
0
999
Alarm Parameter
Parameter
Description
Min
Max
Meas.
Resolution
AL01
Low pressure alarm delay time
0
250 Sec
AL02
Maximum low pressure alarm events in 1 hour
0
16
AL03
Low pressure alarm with off compressor
0= Not enabled when compressor Off
1= Enabled when compressor Off
0
1
AL04
“Water flow/Supply fan thermal protection” alarm delay after “water pump / supply air fan” starting.
0
250 Sec
AL05
Maximum duration of the flow switch alarm before it becomes manual and blocks the water pump
0
250 Sec
AL06
“Water flow/Supply fan thermal protection” input activation duration
0
250 Sec
AL07
“Water flow/Supply fan thermal protection” input de-activation duration
0
250 Sec
AL08
Thermal protection alarm delay after starting the compressor
0
250 Sec
AL09
Number of maximum thermal protection alarm events.
0
16
AL10
Maximum number of high temperature / condenser pressure alarm interventions per hour
0
16
AL11
Condensing temperature/pressure high alarm setpoint for input probe
-50.0
-58
0.0
0
110
230
50
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL12
Temperature/pressure high alarm differential for input probe
0
0
0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL13
Low pressure alarm delay for input probe
0
250 Sec
AL14
Low pressure alarm Setpoint for input probe
-50.0
-58
0.0
0
110
230
50
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL15
Low pressure differential for input probe
0
0
0
0
25.0
45
50.0
725
°C
°F
Bar
Psi
Decimal
integer
Decimal
integer
AL16
Maximum number of the low alarm events in 1 hour for input probe
0
16
AL17
Alarm relay and buzzer activation when the unit is Off or stand-by
0= Alarm relay and buzzer enabled
1= Alarm relay and buzzer disabled
0
1
AL18
Alarm relay output/open collector polarity
0= Output without voltage in normal conditions, with voltage when there is an alarm
1= Output with voltage in normal conditions, without voltage when there is an alarm
0
1