IC100CX SERVICE MANUAL                                                                                                                      

 
 

 

 Manual IC100CX GB                                                                                     

 

 

 

Page 5 di 20  

Upper display shows “rSt” label if the alarm can be reset, “NO” label if it is not 
possible. 
Use 

o

 or 

n

 keys to scroll the alarm list. 

5)

 

Push “SET” key when “rSt” is lighted to reset the alarm; after a while the read-out 
move to next alarm. 

6)

 

To exit the function menu push and release the “menu” key or wait the time-out.  
The “menu” icon disappears. 

Compressors And Pumps Working hours 

Enter the function “menu”.  
Use 

o

 or 

n

 keys to find on the lower display:  

 

C1Hr (Compressor n°1 working hours),  

 

C2Hr (Compressor n°2 working hours),   

 

PFHr (Evaporator Water pump or supply fan working hours), 

 

PCHr (Condenser water pump working hours). 

The clock icon     is lighted. 

Reset Working Hours 

1.

 

Enter the function “menu”.  

2.

 

Use 

or

 n

 keys to find on the lower display the C1Hr, C2Hr, PFHr or PCHr.  

3.

 

Push “SET” key for 3 seconds: the upper display shows  “0” indicating the reset. 

4.

 

To exit the function menu push and release the “menu” key or wait the time-out.  
The “menu” icon disappears. 

How to Display the Delay Time Between Two Defrost 

1.

 

Enter the function “menu”. 

2.

 

Use o or n keys to find on the upper display the “dEF”  label; the lower display 
shows delay time between two defrost (minutes and seconds). 

3.

 

The icon   is flashing.  

4.

 

To exit the function “menu” push and release the “menu” key or wait the time-out.  
The “menu” icon disappears. 

How to See the Alarm Log 

1.

 

Enter the function “menu”. 

2.

 

Use o or n keys to find “ALOG” label. 

3.

 

Push “SET” key: the lower display shows the alarm code, the upper display shows 
n°” followed by the progressive number. 

4.

 

With o or n scroll the alarm list.  

5.

 

To exit from ALOG function push “menu” key or wait the time-out delay is 
expired. 

Memory capacity is 50 alarm structured in a FIFO list (first in first out). Each new alarm 
will take the place of the oldest alarm contained in the list ( the read-out is ordered from 
the oldest to the newest). 

How to Reset the Alarm Log 

1)

 

Enter the function “menu”. 

2)

 

Use o or n keys to find “ALOG” label. 

3)

 

Push “SET” key. 

4)

 

Use o or n keys to find “ArSt” (Alarm reset) label on the lower display; the upper 
display shows “PAS”. 

5)

 

Push “SET” key and then enter the password value using o or n keys; confirm the 
value pushing “SET” key. 

6)

 

The ArSt label starts flashing for 5s, to confirm the alarm logging data is reset. 

K

EYBOARD 

F

UNCTIONS

 

How to See the Set Point Value 

Push and release the “SET” key. 
Lower display shows:   “SetC” set point chiller;  

“SetH” set point heat pump. 

The upper display shows the value.  
Note: 
SetH is available only if configured for Heat Pump. 

How to Change the Set Point Value 

1)

 

Push and hold “SET” key (for about seconds). 

2)

 

The setpoint value is flashing. 

3)

 

Use and n

 

to increase or decrease the new value. 

4)

 

Push and release “SET” key or wait the time-out to exit the programming. 

How to See the real Set Point 

When Energy Saving, Dynamic Set Point or Function For Units Without Water Storage 
Tank are enabled is possible to see the real set point. 
When the machine is running: 

 

push “SET” key once: lower display shows “SetC” (setpoint chiller) or  “SetH” 
(setpoint heat pump) and upper display shows the value. 

 

push “SET” key again:  

- when “Energy Saving” is enabled the lower display shows “SEtS” (Energy 
saving setpoint) and upper display shows the value. 
 - when “Dynamic Set” is enabled, the lower display shows “SEtd” (dynamic 
set point) and upper display shows the value. 
- when the function for units without water storage tank is enabled the lower 
display shows “Setr” (real set point) and upper display shows its value. 
 - when two function above are both enabled, the lower display shows “Setr” 
(real set point) and upper display shows its value. 

R

EMOTE 

ON/OFF

 

 

If a digital input is configured as remote on/off, it is possible to switch on or switch off the 
unit.  
The remote ON/OFF: 

 

It has priority over the keyboard 

 

The unit can be switched on and off by keyboard only if the digital input set 
the unit switched on 

 

When the digital input is disabled the instrument returns to its condition prior 

to activation 

 

It is possible to navigate the functions menu 

The upper display visualizes “OFF” and the decimal LED will be flashing. 

H

OW TO 

D

ISABLE A 

C

OMPRESSOR

 

A compressor can be disabled for maintenance; the unit continues to work normally but 
only with one compressor. 
How to disable a compressor: 
1.

 

Access to the programming parameters mode. 

2.

 

Set the parameter CO12 = 1 or CO13=1 (compressor 1 or 2 = OFF). 

To enable the compressor set C011=0 or CO12= 0. 

D

YNAMIC 

S

ET 

P

OINT

 

This function is useful to save energy or to use the unit during particular external air 
temperature condition.  
The setpoint is changed according to the external temperature or 4..20mA trasducer. 
The Dynamic Set point function is enabled: 
 - if Sd01 = 1 and CF06 = 3 (Pb3 probe is configured as 4..20mA signal for dynamic set 
point), or; 
 - if Sd01 = 1 and CF07 = 3 (Pb4 probe is configured as outside air temperature). 

E

NERGY 

S

AVING 

 

It’s possible to change the setpoint for the Energy saving periods. 
The activation can be: 

 

weekly/daily; in this case is required a controller with RTC on board 

 

by digital input configured as “Energy saving” 

 
The setpoint during an Energy Saving period is:  
Chiller: setpoint =SET+ES10            differential=ES11 
Heat pumpsetpoint =SET+ES12     differential=ES13 

Daily Programming 

It is necessary to set parameters ES03 

 ES09 to activate the Energy saving (one 

parameter for each day of the week). 
The value “1” enable the function for that day. 
Eg: ES03 = 1 means that every Monday the Energy Saving is activated for all day.  

Programmable timer (RTC is required) 

It’s possible to activate the Energy Saving for a period of the day by setting the start time 
end the end time. 
ES01 Energy Saving start hour 
ES02 Energy Saving stop hour 
Eg: ES01 = 8.0 and ES02 = 10.0: Energy Saving is active from 8 to 10.0 for all the days 
of the week. 
Eg: ES01 = 23.0 and ES02 = 8.0: Energy Saving is active from 23.0 to 8.0 of the next 
morning for all the days of the week.  
Energy Saving is disabled if the parameters ES01 / ES02 are both “0”. 

Energy Saving by Digital Input 

The function is enabled when a digital input, configured as Energy Saving, is activated 
by remote contact.   

D

EFROST 

F

UNCTION

 

The defrost cycle is enabled only if the following conditions are satisfied:  
1.

 

the unit is working in heat pump mode (heat pump enabled by parameter CF28) 

2.

 

the unit is air/air or air/water (CF01=0 or CF01=1) 

Содержание iCHiLL 100CX

Страница 1: ...IC100CX SERVICE MANUAL Manual IC100CX GB Page 1 di 20 iCHiLL 100CX Service Manual ...

Страница 2: ...ch is activated When the pump is OFF the led is on flashing to indicate the correct status of the digital input On if at least one water pump is on On if evaporator fans are activated On if a compressor is on On flashing during the delay time for compressor activation On if open collector output is active On if the controller is on in Heat or Cool mode On in case of Low pressure alarm or High pres...

Страница 3: ...r digits yellow color configurable by parameter CF43 PB1 PB2 PB3 PB4 Set point parameter value working set point real set point modified from dinamic set point Energy saving or function for units without water storage tank Hysteresis RTC Machine status the display visualizes chiller set point when the unit is on and in chiller mode heating set point when the unit is on and in heat pump mode and OF...

Страница 4: ... o when a parameter label is displayed or wait 15s time out without pushing any keys NOTE The new parameter value is also confirmed if after changing it no SET key is pressed for the time out to exit ATTENTION CF parameters Configuration parameters can be modified only if the controller is in OFF digital input or STD BY HOW TO CHANGE THE PASSWORD To change the password you must know the previous v...

Страница 5: ...nd upper display shows the value push SET key again when Energy Saving is enabled the lower display shows SEtS Energy saving setpoint and upper display shows the value when Dynamic Set is enabled the lower display shows SEtd dynamic set point and upper display shows the value when the function for units without water storage tank is enabled the lower display shows Setr real set point and upper dis...

Страница 6: ...ferential differential chiller Par ST14 CO01 compressor working time x Par ST16 10 Compressor working time is in sec x 10 The function for units without water storage tank is compatible with Energy Saving function or with the Dynamic set point Visualization of the set point on the display Chiller with energy saving or dynamic set point enabled push SET button once SetC set point value from paramet...

Страница 7: ...higher than Ar25 set point the Ar26 differential the compressors are switched on Anti freeze support heater 2 Heather ON if outside air temperature Ar21 for more than Ar23 Ar24 time regulation probe Heating set point ST04 2 or real Heating set point ST04 2 if Energy saving or Dynamic set point or function for units without water storage tank are enabled Ar23 delay time starts when outside temperat...

Страница 8: ...rm A10 Compressor 2 thermal protection alarm A11 Condenser fan thermal protection alarm A12 Defrost error alarm A13 Compressor 1 maintenance warning A14 Compressor 2 maintenance warning A15 Water pump or supply air fan air air maintenance warning A16 High temperature evaporator inlet water A17 Thermal protection alarm for evaporator water pump supply fan A18 Thermal protection alarm for condenser ...

Страница 9: ...tank Parameter Description Min Max Meas Resolution ST10 Chiller unit without water storage tank 0 function disabled 1 function activated 0 1 ST11 Minimum temperature Set point for outlet water in chiller mode unit without water storage tank 50 0 58 110 230 C F Dec int ST12 Maximum temperature Set point for outlet water in HP function unit without water storage tank 50 0 58 110 230 C F Dec int ST13...

Страница 10: ... control 2 4 20mA for condensing pressure 3 4 20ma for Dynamic Set point 4 NTC temperature for anti freeze alarm water water 5 NTC high temperature probe of system inlet water 6 0 5V for condensing pressure 0 6 CF07 Pb4 configuration 0 Probe not enabled 1 NTC condensing control 2 Multifunction digital input 3 External air temperature 4 NTC temperature for anti freeze alarm water water 5 NTC temper...

Страница 11: ...thermal protection alarm 14 Condenser flow switch alarm 15 not used 0 15 CF11 Pb4 configuration in digital input mode 0 1st compressor thermal protection 1 Condenser fan thermal protection 2 Evaporator flow switch alarm 3 Remote On off 4 Cooling Heating 5 2nd compressor thermal protection 6 2nd compressor or step request Motocondensing unit 7 End defrost 8 Energy Saving 9 Anti Freeze alarm 10 1st ...

Страница 12: ...integer CF26 Pb3 Offset 12 0 21 12 0 174 12 0 21 12 0 174 C F Bar Psi Decimal Integer Decimal integer CF27 Pb4 Offset 12 0 21 12 0 21 C F Decimal integer CF28 Chiller or Heat Pump configuration 0 chiller and heat pump selected by keyboard 1 chiller and heat pump selected by digital input 2 chiller and heat pump selected by probe 3 only chiller unit 4 only heat pump unit 0 4 CF29 Automatic Changeov...

Страница 13: ...pump 0 10 CF42 Switching time of reversing valve when the compressor is switched off 0 250 CF43 Default viewing of lower display of the controller 0 PB1 visualization 1 PB2 visualization 2 PB3 visualization 3 PB4 visualization 4 Real working set point set point modified from Energy Saving Dynamic set point function for units without water storage tank 5 Unit status 6 Clock 7 No visualization 8 Wok...

Страница 14: ...5 C F Decimal integer ES12 Energy saving setpoint offset in heat pump 30 0 54 30 0 54 C F Decimal integer ES13 Energy saving differential in heat pump 0 1 0 25 0 45 C F Decimal integer Pr2 Password value 0 999 Compressor parameters Parameter Description Min Max Meas Resolution CO01 Minimum ON time 0 250 Sec 10Sec CO02 Minimum OFF time 0 250 Sec 10Sec CO03 ON delay time between two compressors or C...

Страница 15: ...0 CO33 Minimum speed of modulating pump in operation with enabled compressor Heat Pump 30 100 CO34 Speed of modulating pump in operation with enabled compressor 30 100 CO35 Set point modulating pump in chiller mode evaporator outlet temperature 50 0 58 110 230 C F Dec int CO36 Temperature control band for the modulating pump in chiller function 0 0 0 25 0 45 C F Dec int CO37 Delay for switching of...

Страница 16: ... function 30 100 Hot Start Function Parameter Description Min Max Meas Resolution FA25 Hot Start Setpoint 50 0 58 110 230 C F Decimal integer FA26 Hot Start differential 0 1 0 25 0 45 C F Decimal integer Pr2 Password 0 999 Anti freeze Heater parameters Parameter Description Min Max Meas Resolution Ar01 Minimum value of Anti Freeze Setpoint 50 0 58 Ar03 C F Decimal integer Ar02 Maximum value of Ant...

Страница 17: ... 0 1 0 25 0 45 C F Dec int Anti freezer alarm in HP function Ar27 Anti freeze alarm set point in heat pump mode Ar01 Ar02 C F Dec int Ar28 Anti freeze alarm differential in heat pump mode 0 0 25 0 45 C F Dec int Evaporator water pump functioning condenser of ambient probe Ar29 Evaporator condenser water pump set point with external temperature regulation 50 0 58 110 230 C F Dec int Ar30 Evaporator...

Страница 18: ...1 hour 0 16 AL03 Low pressure alarm with off compressor 0 Not enabled when compressor Off 1 Enabled when compressor Off 0 1 AL04 Water flow Supply fan thermal protection alarm delay after water pump supply air fan starting 0 250 Sec AL05 Maximum duration of the flow switch alarm before it becomes manual and blocks the water pump 0 250 Sec AL06 Water flow Supply fan thermal protection input activat...

Страница 19: ...f system inlet high temperature alarm interventions per hour 0 16 AL28 Condenser water flow alarm delay time 0 250 Sec AL29 Maximum duration of the flow switch alarm before it becomes manual and blocks the water pump 0 250 Sec AL30 Minimum activation time for water flow alarm 0 250 Sec AL31 Minimum time with inactive water flow input after alarm event 0 250 Sec AL32 Condenser flow switch alarm con...

Страница 20: ...ion relays Pb1 Pb2 Pb4 NTC probe or digital input Pb3 pressure trasducer Tk output for external fan speed controller MF o c out multifunction open collector output for external relay 1 4 Model with 5 internal relays and ratiometric pressure trasducer Pb3 MF ID1 MF ID2 MF ID5 multifunction digital inputs ID3 high pressure digital input ID4 low pressure digital input MF RL2 MF RL3 MF RL4 MF RL5 mult...

Отзывы: