© 1995-2009 Energy Saving Products Ltd.

(3)

HE PS

Return Air Base

Air Flow

Return Air Base

Hi-Velocity Fancoil

RPM-E

4. 

When installing the HE PS to a Hi-Velocity 50 or 

70 fan coil, a transition should be made (

Fig. 4)

 

or simply 

block air flow with a piece of sheet metal 

(Fig. 5)

.

Fig. 4 Transition

HE PS

RPM-E-70

HE/HV/HE-Z-70 

Fan Coil

Block air flow with 

18 ga. sheet metal

Top View

RPM-E-70

Create transition from 

18 ga. sheet metal

HE PS

Transition

Transition

Top View

Fig. 5 Block Air Flow

5.

 

Tape all seams between the air handler and the 

outlet side of the HE PS so there can be no air bypassing 

the system.

6. 

Attach the air handler to the outlet side of the 

HE PS and fasten with #10 x 3/8 self-drilling sheet 

metal screws.

NOTE: Only 1/2 inch of clearance has been provided 

between the outer and inner case.

7. 

Slide the components into the outer case 

and tighten locking knobs finger tight. Make sure the 

inner module will freely slide in and out of the outside 

enclosure.

8. 

Plug in the power cord to any 120vac outlet 

and check both sight ports to make sure both lamps 

are     illuminated. Ultraviolet lamps must remain on at 

all times regardless of thermostat or AirCycler settings.

9. 

Check the service panel 

(Fig. 11)

. The LED 

lights should be flashing in sequence for a 15 second 

period of time and then return to green. The filter lamp 

should be flashing green and the UV lamp light should 

be a steady green.

10. 

Set the thermostat or the AirCycler to operate 

the  fan  unit  for  at  least  25  minutes  every  hour.  If  air   

quality problems persist after one week, increase the 

fan unit operating time by (5) minute intervals.

Fig. 3 Vertical Installation

HE/HV/HE-Z-70 

Fan Coil

Содержание HE PS

Страница 1: ...nstallation and Operation Manual www hi velocity com The AirPurification System Module HPS Hi Velocity Air Purification System Installation Manual 050515 MERV 13 Small Duct Heating Cooling and Indoor Air Quality Systems ...

Страница 2: ... Replacement MERV 13 Filter 20180100015 Replacement 1750 MERV 13 Filter 20180100012 Optional MERV 14 Filter n a for 1750 20180100006 Item Part Number Electronic Lamp Ballast 20180100003 Item Part Number 12 Volt Transformer 20180100004 Item Part Number HE PS Titanium Honeycomb Catalyst 20180100005 HE PS 1750 Titanium Honeycomb Catalyst 20180100013 HE PS Replacement Parts Item Part Number HE PS One ...

Страница 3: ... interior module can gravity fall from an elevated position and cause injury to people or equipment below 2 Specifications HE PS HE PS 1750 Capacity 1 5 3 Tons 4 5 Tons Dimensions 163 4 W x 25 H x 10 D 21 W x 25 H x 10 D Flange 1 2 around unit Weight 23 lbs 26 lbs Filter Size 157 8 W x 243 4 H x 33 4 D 201 8 W x 243 4 H x 33 4 D Power 120v 54 watts 1 1amps Fuse AGC 2 amps Service Panel 12 vac Cata...

Страница 4: ...y 1 2 inch of clearance has been provided between the outer and inner case 7 Slide the components into the outer case and tighten locking knobs finger tight Make sure the inner module will freely slide in and out of the outside enclosure 8 Plug in the power cord to any 120vac outlet and check both sight ports to make sure both lamps are illuminated Ultraviolet lamps must remain on at all times reg...

Страница 5: ...e against indoor air pollutants Photocatalytic Oxidation PCO technology combined with high efficiency electrostatic MERV 13 particulate filtration and germicidal ultraviolet light quickly reduces and eliminates toxic gasphase chemicals lung damaging dust and airborne germs from the living environment Many new homes have smart programmable thermostats that allow for automatic operation of the air h...

Страница 6: ...atalytic module and filter secure door and re insert plug check sight ports to ensure lamp illumination Changing the Filter 1 Unplug the power cord from the HE PS unit Unscrew the two locking knobs and remove the door Fig 6 2 Remove old filter and replace with new filter Make sure airflow arrow on filter is pointing to the inside of module Fig 7 Locking Knobs Fig 8 Fig 9 Unplug UV Lights Loosen Re...

Страница 7: ...Electrical Diagram 6 HE PS ELECTRICAL DIAGRAM POWER CORD RECEPTACLE WHITE GROUND LINE RED 2 AMP FUSE AGC2 RED NEUTRAL WHITE WHITE BLACK 1 AMP TRANSFORMER 120 V SERVICE PANEL LAMP BALLAST 120 220 V BALLAST 120 220 V BLACK WHITE BLACK WHITE BLUE BLUE LAMP ...

Страница 8: ...faulty installation or damage to personal property resulting from incorrect or faulty installation This warranty does not cover the cost for removal or reinstallation of the HE PS when service or warranty work is required All warranty repair work must be performed either at the factory or by a factory certified service center Shipping cost to the factory or service center is the responsibility of ...

Отзывы: