FM 3180 Installation Guide
UPS
For any UPS (Uninterruptible Power Supply) providing power to an HPE FM 3180 fabric module, HPE
recommends the following:
•
The UPS must have enough capacity to power the fabric module plus any other equipment that is
connected to the UPS.
•
The UPS must be a double-conversion on-line sine-wave UPS.
Cabling
Ensure there is ample clearance at the power panel and I/O panel to allow unrestricted cabling. Also
ensure the AC power cords can easily reach from the AC power outlet to the connection on the power
supply panel of the fabric module.
Unpack the Fabric Modules
Unpack all fabric module components and inspect for shipping damage.
Verify Equipment Delivered
Compare the contents of the shipment against the packing slip that was included in the shipment, check
for any shipping damage, and verify that the components received match those ordered.
Equipment
Description
Four hot swappable fans
Installed in chassis. A red tab (warm side) indicates
airflow from front to rear (I/O to power panel). A blue
tab (cool side) indicates airflow from rear to front
(power to I/O panel).
Two power supplies
Installed in chassis. A red cable latch (warm side)
indicates airflow from front to rear (I/O to power
panel). A blue cable latch (cool side) indicates airflow
from rear to front (power to I/O panel).
One Control Panel
Installed in chassis.
Two power cables
1.5 meter cables which comply with appropriate
country standards.
For redundancy: Connect the power cables to
separate site power circuits.
DB9 serial cable
For Console connection.
Cables
Verify that you have all cables ordered for your
installation. For valid cables and part numbers, refer
to the HPE Composable Fabric Support Matrix.
Rack mount kit
Rack mount for the fabric module.