HM1525 Weigh Scale Module
Page 27
A complete listing of a sample ladder logic program is included at the back of this manual.
Examples shown here are for reference.
All values are 0 (default) on initial start-up. This means that all alarms are
disabled. You must make the following adjustments for proper operation:
Balance sensor input(s)
Set Calibration numbers
Step 1. Balance Sensor Input.
1. Set to Cal Mode
2. Press Clear Tare for each channel
3. Check balance value, should be 131,000 counts
Step 2. Set Calibration Numbers
1. Set Scale to capacity of load cell
2. Set mV/V to load cell specification
3. Example:
100 ton load cell, 2.025 mV/V
For scale set, enter 100
For mV/V set, enter 2025
4. Push Set CH1, Set CH2 Scale
Push Save to eeprom
5. Set to Run Mode
HT-400 Sensor Ohm Readings:
Green-Black
350 ohms
Red-White
350 ohms
All other color combinations 266 ohms
All colors to Ground
open
Shield to Ground
open
Setup
Procedure