HM1525 Weigh Scale Module
Page 11
REQUIRED CONTROLLER TAGS
CH1/CH2 SCALE SET AND AUTOCAL REFERANCE
CH1_SCALE_MOD1
Full scale setting for CH1, CH2
Value is determined by capacity of load cell and by resolution required.
Example: 10KG = 10,000
GET WEIGH VALUE CH1
CH1_WEIGHT_MOD1
CH2_WEIGHT_MOD1
Reports measured weigh value in RUN mode.
Reports raw A/D count value in CAL mode.
SET AVERAGE SAMPLE COUNT
SMAPLE_SET_MOD1
Set number of samples to take for average type filter.
SET mV/V CH1, CH2
CH1_MV_V MOD1
CH2_MV_V MOD1
CH1/CH2 MV_V Settings
Enter 2000 for 2.0 mV/V
Actual value is from load cell specification.
FILTER TIME _MOD1
FILTER_TIME_MOD1
Each count = 1 msec
50 h2: 20 msec = 20
60 h2: 16 msec = 16