background image

E-mail: [email protected]Website: www.hellermanntyton.co.za

TEL28 Industrial ELCB

  Micro-processor controlled

  Fully programmable

  Direct readout of Time/Current

  Voltage measurement during test

  Suitable for Industrial, Mining and Domestic environments

  Each phase tested separately on a 3 phase system

Technical Specification

Rated tripping
current at 317 Volts

0 to 1000mA

Resolution

1mA

Operating voltage

100 to 450V AC

Maximum trip time

100 secs

Resolution

1m sec

Accuracy
Rated trip current

1% (1mA)

Voltage measurement

1% (1V)

Rated trip time

1ms

Operating temperature

0ºC to 40ºC

Humidity (%)

80

Phase angle setting

0 & 180º 
selectable

Meter 

Supplied With 

Certificate of 
Conformence

MACROG3

  Continuity with 200mA

• 

Insulation resistance

• 

Line/Loop Impedance (L-L, L-N, L-PE)

• 

Earth reistance and ground resistivity

• 

RCD tripping time and current

• 

Non-trip earth loop impedance

• 

1 Terminal phase sequence

24

TEL11 ELCB/Phase Rotation Tester

 Indicates phase presence

 Indicates phase rotation

 TEST for disconnection sensitivity

 TEST for disconnection time

 Select one of 3 phase to test ELCB

 Measure voltage phase to Earth

 Over temperature protection

 Phase polarity trip indicator

Accessories

Test Leads x 2 (terminate 
own plug

Dimensions (mm)

330(L) x 260(W) x 150(H)

Power Source

8 x C Batteries

Weight

2.0kg

Model Specification

Current Settings

999mAac/50Hz

Current Selection

Knob

Phase-start-selection

0° & 180°

Operation Voltage (L-e)

60Vac to 317Vac
(525V System)

Timer Resolution

1mS
(Max Time = 99.99s)

Current Resolution

1mA

Voltmeter Resolution

1V

Accuracy
Earth Leakage Constant Current Iac

5 to 999 (mA) @50Hz

Ramping Current

5 to 999 (mA)

Sensitivity Disconnection Check 

5 to 999 (mA)

Time Delay Disconnection Check(s)

0.001 - 99.999

Maximum Current Consumption

10mA

ELCB Voltage Measurement L-E (Vac)

10 to 330V

ELCB Tester Voltage Present (VELCB)

LED

ELCB Fuse (Slow Blow)

1.5A

Protection
OverVoltage CLASS III

450V

Over Load between all terminals

550V

Battery OK goes off when battery
voltage

<9Vdc

Technical Specification

Meter 

Supplied With 

Certificate of 
Conformence

WIBRE1000 1000V CATIV

 IEC61243-3

 LED lights

  DIN / VDE 0682-401

 AC/DC Voltage 110,230,380,690,1000V

 Polarity

 Oil resistant

 No batteries

NEW

Optional 
Accessories

Software & USB cable 

(TOPVIEW)

Standard 
Accessories

4 Cables, alligator clips, test 
leads and earth rods. Carry case
English instruction manual
Calibration certificate ISO9000

Dimensions (mm)

225(L) x 165(W) x 75(H)

Power Source

6 x 1,5 AA Batteries

Weight

1200g

Model Specification

Meter 

Supplied With 

Calibration

Certificate

INSTRUMENTS | 

For more specifications, refer to the Test Instruments Catalogue

Содержание ACADEMY T419

Страница 1: ......

Страница 2: ...RS232 Interface or USB Frequency Voltage Phase Rotation 350 Memory Locations Description TCTRP Analogue Kit TCTDT Digital Kit TCTCDK Digital Kit DMM TBM811 Clamp Meter TBM3030 TBM3030 Insulation Test...

Страница 3: ...24 Instruments 1 WHAT IS AN ELECTRICAL INSTALLATION 1 2 WHO IS RESPONSIBLE 1 3 HOW CAN A LAYMAN KNOW IF THE INSTALLATION IS SAFE 1 4 WHERE TO OBTAIN A CERTIFICATE OF COMPLIANCE 1 5 WHAT MUST BE DONE B...

Страница 4: ...by the Chief Inspector of the Department of Labour in terms of the regulations as an electrical contractor QUESTION 5 WHAT MUST THE REGISTERED PERSON DO BEFORE ISSUING A CERTIFICATE OF COMPLIANCE TES...

Страница 5: ...3 d Subtract previous reading b from this reading c to get the required reading e This reading shall not exceed 0 2 see note on table 8 1 on page 276 of code of practice SANS 10142 f All points must...

Страница 6: ...9900 Cape Town 021 594 7100 Port Elizabeth 041 408 2400 Earth 3 Test Lead Insulation Tester Fig A Continuity of all Bonding Conductors Fig B Resistance of Earth Continuity Conductors Earth Insulation...

Страница 7: ...ed can be written down as illustrated in addendum A below QUESTION 9a WHAT INSTRUMENT CAN BE USED TO TEST THE CONTINUITY OF THE RING CIRCUIT ANSWER Any meter with continuity buzzer function similar to...

Страница 8: ...eference and Line 1 Blue Reading 115 Volts Socket Outlet Voltage Test 2 Test between Earth Reference and Line 2 Red Reading 115 Volts B Remove Multimeter and set switch to blue or red phase turn the p...

Страница 9: ...92 Therefore the loop resistance of the circuit must be below 1 92 to allow a fault current of 120 amps to flow h Set the tester on the 2000A range on the PSC scale and measure the prospective short...

Страница 10: ...iring resistance earth resistance and resistance of transformer winding Line earth loop resistance is the sum of wiring resistance earth resistance and resistance of transformer winding L1 Transformer...

Страница 11: ...m of wiring resistance earth resistance and resistance of transformer winding Line earth loop resistance is the sum of wiring resistance earth resistance and resistance of transformer winding Transfor...

Страница 12: ...mber of Phases One Two Three Phase rotation Clockwise Anticlockwise Frequency 50Hz Other d c Prospective short circuit current at point of control PSCC kA How determined Calculated Measured From suppl...

Страница 13: ...rth c Spikes must be inserted in a straight line minimum spacing is 2m d If the ground is dry or sandy moisten with water Test spikes only e Where it is not possible to insert the auxiliary earth bars...

Страница 14: ...that purpose or for the capacity supply or both In a balanced three phase system the three phase value can be estimated by multiplying the single phase value by 1 73 Note 2 Ensure that the instrument...

Страница 15: ...r Impedance in Ohm A Z TRF Z TRF Z TRF 0 0144 V2 PX103 Z 100 x 4002 P x 103 4 5 100 x 400 x 400 500 x 103 0 045 x 160 000 500 000 0 045 x C The PSCC of complete system A B Z TRF Z conductor Z Total Is...

Страница 16: ...ent Toptronic T1805 On a concrete floor not asphalt where auxilary earth bars cannot be driven lay the earth bars and make them moist with water before proceeding with measurement Earth Resistance Mea...

Страница 17: ...epted QUESTION 14a WHAT INSTRUMENT CAN BE USED TO TEST THE VOLTAGE MAIN DB WITH NO LOAD ANSWER Any meter with voltage function similar to a Toptronic TBM811 b Toptronic TBM251 c Toptronic TBM3030 QUES...

Страница 18: ...r similar to a Toptronic TEL1TLB b Toptronic T419 QUESTION 17b HOW IS THIS TEST DONE AND WHAT VALUE OF MEASUREMENT IS ACCEPTABLE ANSWER a Ensure ALL leads are disconnected all appliances unplugged sto...

Страница 19: ...ion of a potential danger See 8 7 6 and 8 7 10 To The supplier From The registered person During an inspection in terms of SANS 10142 The wiring of premises performed at stand No situated at I Registr...

Страница 20: ...2003 as illustrated in Addendum B Pg 9 g The results can only be correct if a fault is detected it must be rectified immediately QUESTION 20a WHAT INSTRUMENT CAN BE USED TO TEST ALL THE SWITCHING DEVI...

Страница 21: ...safe Note 1 Indicate a or b or a and b on the test report Note 2 Indicate N A in the case of a or b where applicable 14 Where an alternative supply is installed it complies with the requirements in re...

Страница 22: ...ut Warning Transient 6 5KV lightning surge Protection 1 2 50 s fuse Technical Specification Meter Supplied With Certificate of Conformence Meter Supplied With Certificate of Conformence TBM811 General...

Страница 23: ...C Voltage 4 40 400 600V Resistance 400 4K 40K 400K 4M 40M Frequency 1KHz to 100KHz Capacitance 500n 5 50 500 3000 F Accuracy AC DC Current 2 5 5 Digit DC Voltage 1 0 4 Digit AC Voltage 4 40 400V 1 0 4...

Страница 24: ...Source 8 x 1 5V AA Batteries Weight 655g Model Specification Technical Specification Insulation Test Voltage 250 500 1000V Insulation Resistance 250V 2k 2G 500V 4k 4G 1000V 8k 8G AC Voltage 0 to 700V...

Страница 25: ...on earth probes without any cable breaking Measurement of leakage current on earth installations Setting of alarm thresholds on measurements Storage of measurement results Detection of current noise o...

Страница 26: ...test 7mA for Phase rotation field indication Meter Supplied With Certificate of Conformence TEL1TLB SOCKET ELCB TESTER POLARITY Live on earth indication LCD Display Polarity indication Identifies 6 w...

Страница 27: ...erminate own plug Dimensions mm 330 L x 260 W x 150 H Power Source 8 x C Batteries Weight 2 0kg Model Specification Current Settings 999mAac 50Hz Current Selection Knob Phase start selection 0 180 Ope...

Страница 28: ...9 9900 Fax 031 569 9909 Cape Town Unit 11A Maitland Park Voortrekker Road Maitland Cape Town P O Box 453 Goodwood 7459 Tel 021 594 7100 Fax 021 594 7130 Johannesburg 34 Milky Way Avenue Linbro Busines...