Johannesburg
(011) 879-6620
Durban
(031) 569-9900
Cape Town
(021) 594-7100
Port Elizabeth
(041) 408-2400
TIMT Line Insulation Monitor Tester
5
FEATURES
• Testing of IT Supply Systems derived from high impedance transformers.
• Test between earth reference and phase with output connections for a multimeter.
• Test Insulation monitoring alarm by adjusting the potentiometer to verify the audio and visual indication.
INSTRUCTION MANUAL
A) Multimeter voltage test:
Socket Outlet Voltage Test 1: Test between “Earth Reference“ and Line 1 (Blue) Reading ± 115 Volts.
Socket Outlet Voltage Test 2: Test between “Earth Reference“ and Line 2 (Red) Reading ± 115 Volts.
B) Remove “Multimeter” and set switch to blue or red phase, turn the potentiometer clockwise until the line
insulation monitor indicates both audio and visual.
C) Verify operation of Line Insulation Monitor testing all socket-outlets
.
These values can be captured on a ‘‘COC’’ test report.
Note: The Voltage values could fluctuate due to changes in load.
0-10k
Ω
Potentiometer to test audio & visual
Blue OFF Red
Phase selection switch
Voltage
output points
for multimeter
V+
V+
Earth
Line 1
Blue
Line 2
Red
Earth Reference
Line 2
Red
Line 1
Blue
Plug configuration
±115V
±230V
±115V
Содержание ACADEMY T419