background image

Johannesburg  

(011) 879-6620

Durban

(031) 569-9900

Cape Town

(021) 594-7100

Port Elizabeth

(041) 408-2400

TIMT Line Insulation Monitor Tester

5

FEATURES

•  Testing of IT Supply Systems derived from high impedance transformers.
•  Test between earth reference and phase with output connections for a multimeter.
•  Test Insulation monitoring alarm by adjusting the potentiometer to verify the audio and visual indication.

INSTRUCTION MANUAL

A)   Multimeter voltage test:  

Socket Outlet Voltage Test 1: Test between “Earth Reference“ and Line 1 (Blue) Reading ± 115 Volts. 
Socket Outlet Voltage Test 2: Test between “Earth Reference“ and Line 2 (Red) Reading ± 115 Volts.

B)  Remove “Multimeter” and set switch to blue or red phase, turn the potentiometer clockwise until the line 

insulation monitor indicates both audio and visual.

C)  Verify operation of Line Insulation Monitor testing all socket-outlets

.

  

These values can be captured on a ‘‘COC’’ test report.

Note:  The Voltage values could fluctuate due to changes in load.

0-10k

Ω

Potentiometer to  test audio & visual

Blue OFF Red

Phase selection switch

Voltage 

output points

for multimeter

V+

V+

Earth

Line 1 

Blue

Line 2

Red

Earth Reference

Line 2 
Red

Line 1
Blue

Plug configuration

±115V

±230V

±115V

Содержание ACADEMY T419

Страница 1: ......

Страница 2: ...RS232 Interface or USB Frequency Voltage Phase Rotation 350 Memory Locations Description TCTRP Analogue Kit TCTDT Digital Kit TCTCDK Digital Kit DMM TBM811 Clamp Meter TBM3030 TBM3030 Insulation Test...

Страница 3: ...24 Instruments 1 WHAT IS AN ELECTRICAL INSTALLATION 1 2 WHO IS RESPONSIBLE 1 3 HOW CAN A LAYMAN KNOW IF THE INSTALLATION IS SAFE 1 4 WHERE TO OBTAIN A CERTIFICATE OF COMPLIANCE 1 5 WHAT MUST BE DONE B...

Страница 4: ...by the Chief Inspector of the Department of Labour in terms of the regulations as an electrical contractor QUESTION 5 WHAT MUST THE REGISTERED PERSON DO BEFORE ISSUING A CERTIFICATE OF COMPLIANCE TES...

Страница 5: ...3 d Subtract previous reading b from this reading c to get the required reading e This reading shall not exceed 0 2 see note on table 8 1 on page 276 of code of practice SANS 10142 f All points must...

Страница 6: ...9900 Cape Town 021 594 7100 Port Elizabeth 041 408 2400 Earth 3 Test Lead Insulation Tester Fig A Continuity of all Bonding Conductors Fig B Resistance of Earth Continuity Conductors Earth Insulation...

Страница 7: ...ed can be written down as illustrated in addendum A below QUESTION 9a WHAT INSTRUMENT CAN BE USED TO TEST THE CONTINUITY OF THE RING CIRCUIT ANSWER Any meter with continuity buzzer function similar to...

Страница 8: ...eference and Line 1 Blue Reading 115 Volts Socket Outlet Voltage Test 2 Test between Earth Reference and Line 2 Red Reading 115 Volts B Remove Multimeter and set switch to blue or red phase turn the p...

Страница 9: ...92 Therefore the loop resistance of the circuit must be below 1 92 to allow a fault current of 120 amps to flow h Set the tester on the 2000A range on the PSC scale and measure the prospective short...

Страница 10: ...iring resistance earth resistance and resistance of transformer winding Line earth loop resistance is the sum of wiring resistance earth resistance and resistance of transformer winding L1 Transformer...

Страница 11: ...m of wiring resistance earth resistance and resistance of transformer winding Line earth loop resistance is the sum of wiring resistance earth resistance and resistance of transformer winding Transfor...

Страница 12: ...mber of Phases One Two Three Phase rotation Clockwise Anticlockwise Frequency 50Hz Other d c Prospective short circuit current at point of control PSCC kA How determined Calculated Measured From suppl...

Страница 13: ...rth c Spikes must be inserted in a straight line minimum spacing is 2m d If the ground is dry or sandy moisten with water Test spikes only e Where it is not possible to insert the auxiliary earth bars...

Страница 14: ...that purpose or for the capacity supply or both In a balanced three phase system the three phase value can be estimated by multiplying the single phase value by 1 73 Note 2 Ensure that the instrument...

Страница 15: ...r Impedance in Ohm A Z TRF Z TRF Z TRF 0 0144 V2 PX103 Z 100 x 4002 P x 103 4 5 100 x 400 x 400 500 x 103 0 045 x 160 000 500 000 0 045 x C The PSCC of complete system A B Z TRF Z conductor Z Total Is...

Страница 16: ...ent Toptronic T1805 On a concrete floor not asphalt where auxilary earth bars cannot be driven lay the earth bars and make them moist with water before proceeding with measurement Earth Resistance Mea...

Страница 17: ...epted QUESTION 14a WHAT INSTRUMENT CAN BE USED TO TEST THE VOLTAGE MAIN DB WITH NO LOAD ANSWER Any meter with voltage function similar to a Toptronic TBM811 b Toptronic TBM251 c Toptronic TBM3030 QUES...

Страница 18: ...r similar to a Toptronic TEL1TLB b Toptronic T419 QUESTION 17b HOW IS THIS TEST DONE AND WHAT VALUE OF MEASUREMENT IS ACCEPTABLE ANSWER a Ensure ALL leads are disconnected all appliances unplugged sto...

Страница 19: ...ion of a potential danger See 8 7 6 and 8 7 10 To The supplier From The registered person During an inspection in terms of SANS 10142 The wiring of premises performed at stand No situated at I Registr...

Страница 20: ...2003 as illustrated in Addendum B Pg 9 g The results can only be correct if a fault is detected it must be rectified immediately QUESTION 20a WHAT INSTRUMENT CAN BE USED TO TEST ALL THE SWITCHING DEVI...

Страница 21: ...safe Note 1 Indicate a or b or a and b on the test report Note 2 Indicate N A in the case of a or b where applicable 14 Where an alternative supply is installed it complies with the requirements in re...

Страница 22: ...ut Warning Transient 6 5KV lightning surge Protection 1 2 50 s fuse Technical Specification Meter Supplied With Certificate of Conformence Meter Supplied With Certificate of Conformence TBM811 General...

Страница 23: ...C Voltage 4 40 400 600V Resistance 400 4K 40K 400K 4M 40M Frequency 1KHz to 100KHz Capacitance 500n 5 50 500 3000 F Accuracy AC DC Current 2 5 5 Digit DC Voltage 1 0 4 Digit AC Voltage 4 40 400V 1 0 4...

Страница 24: ...Source 8 x 1 5V AA Batteries Weight 655g Model Specification Technical Specification Insulation Test Voltage 250 500 1000V Insulation Resistance 250V 2k 2G 500V 4k 4G 1000V 8k 8G AC Voltage 0 to 700V...

Страница 25: ...on earth probes without any cable breaking Measurement of leakage current on earth installations Setting of alarm thresholds on measurements Storage of measurement results Detection of current noise o...

Страница 26: ...test 7mA for Phase rotation field indication Meter Supplied With Certificate of Conformence TEL1TLB SOCKET ELCB TESTER POLARITY Live on earth indication LCD Display Polarity indication Identifies 6 w...

Страница 27: ...erminate own plug Dimensions mm 330 L x 260 W x 150 H Power Source 8 x C Batteries Weight 2 0kg Model Specification Current Settings 999mAac 50Hz Current Selection Knob Phase start selection 0 180 Ope...

Страница 28: ...9 9900 Fax 031 569 9909 Cape Town Unit 11A Maitland Park Voortrekker Road Maitland Cape Town P O Box 453 Goodwood 7459 Tel 021 594 7100 Fax 021 594 7130 Johannesburg 34 Milky Way Avenue Linbro Busines...

Отзывы: