HEAT TRANSFER FLUID SPECIFICATION AND SYSTEM NOTES

7. NOTES

7.0. General Dyn-O-Flo HD Notes

Dyn-O-Flo HD is a 100% concentrate inhibited propylene glycol and is recommended 
for use in applications where low acute oral toxicity is important or where incidental 
contact with drinking water is possible.  Extra strength corrosion inhibitors in the HD fluid 
are formulated for high temperature use, resulting in reduced maintenance and longer 
inhibitor life in most applications.  Freeze tolerances are based on a set of acceptable 
limits.

7.0.0. Use Directions

 

Do not use full strength.

• 

 

Recommended concentration is 40 – 60%. 

• 

 

Dilute with good quality soft water.  If the tap water has more than 25 ppm of 

• 

chloride or sulfate ions, or more than 50 ppm of calcium or magnesium, use 
mountain spring water.

 

Do not use zinc or galvanized components in contact with the fluid. 

• 

 

System preparation:  Flush thoroughly with water (use 1 – 2% TSP) and 

• 

circulate without adding heat, before introducing the operating fluid. 

 

Fluid Introduction: Please see the Helio-Pak systems Manuals for filling, 

• 

venting and priming. 

 

Maintenance: The fluid should be checked periodically for pH, which should 

• 

not drop below 8, and reserve alkalinity, which should stay greater than zero 
at all times.  

 

Flush thoroughly before replacing with new mix. 

• 

 

The Dyn-O-Flo HD has an operating temperature range of -50 – 325 ˚F.

• 

7.0.1. Specifications

 

• 

Specific Gravity:

 

  1.053 

– 

1.063

 

• 

Propylene Glycol:

 

  94%

 

• 

Inhibitor Concentration by Weight:

 6%, inhibitors and water

 

• 

Dye:

 

 

   Bright 

yellow

 

• 

Suspended Solids:

 

  substantially 

free

 

• 

Reserve Alkalinity:

 

  15 

mL

7.0.2. Values at 50% Concentration

The listed values are typical of a 50% by volume aqueous solution at 120˚ F and should 
not be regarded as specifications.

 

• 

pH:

 

 

  9.5 

– 

10.5

 

• 

Specific Heat: 

 0.842 

BTU / lb ˚F

 

• 

Freezing Point:

  

-30 

˚F

 

• 

Burst Protection:

 

 

< -60 ˚F 

 

• 

Viscosity

:    

2.36 Cps

7.0.3. First Aid

While essentially non-irritating, absorbing or toxic, Dyn-O-Flo HD heat transfer fluid should 
be kept away from children and be treated with care.  In case of physical contact, follow 
these directions:

 

• 

Eyes

   

Flush with plenty of water

 

• 

Skin

   

Wash off with flowing water

 

• 

Ingestion:

   

Induce vomiting and consult a physician

 

• 

Inhalation

:  Remove to fresh air, consult physician.

Notice to Physician: No specific antidote.  Supportive care based on judgment of 
physician.

7.0.4. Handling

 

• 

Exposure Guidelines:

  Propylene glycol: AIHA WEEL is 50 ppm total, 10 mg 

/ m

3

 aerosol only.

 

• 

Ventilation

:  

Good general ventilation should be sufficient for most 

conditions.

 

• 

Respiratory Protection:

 No respiratory protection should be needed.

 

• 

Skin Protection

 

For brief contact, no precautions other 

than cleaning of body and covering.  Use impervious gloves when prolonged 

   

 

   

 

or frequently repeated contact occurs.

 

• 

Eye Protection

 

Use safety glasses.

 

• 

Spills

   

 

Cover with absorbent material, soak up 

and seep into bag.

 

• 

Disposal

:    

Discharge into sanitary sewers only with the explicit 

pre-approval of the local waste water facility.  Any disposal 

  

 

   

 

practice must be in compliance with 

federal, state, provincial and local laws and regulations.  Check with the 
 

 

 

 

  appropriate 

agencies.

7.0.5. Maintenance

The glycol / water mix should be tested periodically for freeze protection and pH.  Empty 
the system and flush thoroughly before replacing with a fresh mix when the pH drops 
below 8, or reserve alkalinity approaches zero.

7.0.6. System Fluid Information

Always use copper tubing for collector supply and return connections. 

 

Black iron pipe can also be used, with proper dielectrics.  Never use 
galvanized pipe or plastic based products, such as PEX.

Use only Dyn-O-Flo HD heat transfer fluid with good quality water mixture: 
min 40% HD mixture, max 60% HD mixture.  Do not use distilled water.  
Good quality water: chlorides and sulfates must be less than 25 ppm; 
calcium and magnesium must be less than 50 ppm (as calcium carbonate, 
with hardness less than 100 ppm).  If unsure, use bottled mountain spring 
water.

Rinse system with 1 – 2% mixture of trisodium phosphate and water. 

 

Remove the expansion tank for testing only, and pressure test system with 
water before filling.

Maintain minimum operating pressure of 30psig when system is cold to 
avoid pump cavitation.  If using an air vent during filling, ensure it is closed 
during system operation.

7.0.7. Safety Precautions

Follow all local codes and regulations.  Work should only be performed on 
the HPAK and system when it is disconnected from the power supply.

When creating and repairing roof penetrations, ensure final seal 
disallows any unwanted animal or creature intrusion, and the integrity 
of the structure is not compromised.  Penetrations through fire-rated 
assemblies must not reduce fire resistance capacity below code.  Ensure 
building materials adjacent to solar components are not exposed to 
elevated temperatures.

7.0.8. Components

Always install a tempering valve, or rated anti-scald valve, after the 
solar storage tank.  Route the pressure relief port on the HPAK to avoid 
accidental scalding in case of release.

Place the HPAK and tank in a non-freezing environment.

Solder suitable for 400°F and 150 psig must be used: 96/4 Tin / Silver is 
recommended.

7.0.9. Description Of Product and Operation

The HPAK is a fully automatic solar energy heat transfer appliance.  The 
controller senses the collector and storage temperatures and powers both 
circulation pumps when the collector has achieved enough temperature 
over the solar storage tank.  See the Delta-T and Delta-T Pro manuals for 
full descriptions of operation and functions.

7.0.10. Commissioning

After the system is filled, it is normal for the initial pressure to drop as air 
comes out of solution.  Repressurize the system to ensure at least 30psig 
when cold.

Содержание GOBI 406 001

Страница 1: ...EXCELLENCE BY DESIGN INSTALLATION GUIDE HPAK SYSTEMS S O L A R H O T W A T E R ...

Страница 2: ...TABLE OF CONTENTS 1 PREPARATIONS 3 9 GOBI INSTALLATION 10 11 2 12 13 14 16 20 21 17 19 3 HPAK INSTALLATION 4 PIPING 5 COMMISSIONING 6 O M ...

Страница 3: ...r Flush mount hardware kit Appropriate roof penetration hardware and sealant Copper tubing type M or L for collector heat transfer appliance connections adapters elbows and fittings 96 4 Tin Silver solder Non rubber based insulation Armaflex 1 2 wall R2 6l minimum UV resistant covering or coating for outdoor exposed insulation Helio Pak heat transfer appliance HPAK Isolation valves tempering valve...

Страница 4: ...9 93 37 47 g Dry Weight lb 97 110 128 G Full Weight lb 103 2 116 9 135 8 V Volume Gal 0 75 0 83 0 95 Max Pressure PSI 150 10 Bar Test Pressure PSI 300 20 Bar Stag Temp F 397 6 203 C A F D P W M T L H 1 2 Flow and Pressure Loss1 RECOMMENDED DESIGN FLOW RATES WITH GLYCOL2 GOBI 406 GOBI 408 GOBI 410 0 85 Gal min 1 0 Gal min 1 25 Gal min PRESSURE DROP PLOT 1 Losses calculated at recommended Gobi desig...

Страница 5: ...i Orientation and Plumbing OR OR Figure 1 3 2 Two DOS Discs Per Vertical Array Figure 1 3 1 DOS Disc Assembly p n 50013 Figure 1 3 3 Two DOS Discs Per Horizontal Collector S 15 15 15 Helio Pak Helio Flo Drain Back Helio Pak Helio Flo Drain Back Combi DHW DHW Pool 45 35 2x ...

Страница 6: ...22 5 Figure 1B 1 HPAK Dimensions HPAK 0XX 00X Heat Exch 000 Std 001 Pro 016 000 Btu hr 024 000 Btu hr 032 000 Btu hr 048 000 Btu hr Control 1 5 Technical Specifications Maximum Operating Conditions 150 psig 275 F Heat Transfer Fluid 40 50 Dyn O Flo HD and Water Solar Loop Connections Compression fittings for 3 4 Type M or L Copper 7 8 OD ASTM B88 Domestic Water Connections 3 4 Male NPT Fittings Pr...

Страница 7: ...ket for combo valves 3 14 Combo Valve Hot 23090 Hot combination valve check ball temperature 1 15 Combo Valve Cold 23091 Cold combination valve check ball temperature 1 16 Combo Valve Fill 23092 Filling combination valve 1 17 EX 2 EX 5 23030 23031 2 gallon bladder type expansion tank 5 gallon bladder type expansion tank 1 20 Tank Bracket 21204 Tank mounting bracket 1 22 Mtg Screws 21194 1 4 20 x 1...

Страница 8: ...ration of Pressure Relief Valve and Expansion Tank The HPAK comes with a preinstalled pressure only relief valve nonadjustable and pre set at 150 psig A 1 4 barbed hose fitting is supplied for routing relief fluid to a drain or retaining vessel In addition the system comes with a pre sized bladder type expansion tank The acceptance volume of the expansion tank should be large enough to store up to...

Страница 9: ...tlet and wire the storage and collector sensor appropriately The control comes prewired with two sensor lines Use 22 AWG or larger cable if the sensor lines need to be extended Connect the sensors to wire using non metal wirenuts or other corrosion resistant connection method Ensure the control high limit is set at or below the tank manufacturer s recommended limit If attaching additional sensors ...

Страница 10: ...TY 1 CLIP 000 000 40082 Gobi Rail Clamp 3 8 16 x 1 SS Bolt Flange Nut set of 4 1 Gobi 2 RAIL 002 000 40090 2x102 0 Gobi Mounting Rail 2xCLIP 000 000 set See Note 1 3 RACK 000 000 RACK 000 001 RACK 000 002 40080 40081 40083 Commercial Mount 4 Front Leg 47 Rear Leg Flat Roof Rack Mount 4 Front Leg 47 Rear Leg Flat Roof Rack Mount 8 Front Leg 47 Rear Leg Gobi 1 4 RAIL 000 001 40089 Splice Kit for Joi...

Страница 11: ...ts the distance between front and rear mounting points Rear Leg Height Front Leg Height Tan Gobi Tilt Angle 3 Brace rails for first collector 4 Place first collector and install all 4 Helio Clips Tighten bolts on Helio Clips to engage locking serrated flange nut Roof Sealant RACK MOUNTING INSTALLATION 11 S O L A R H O T W A T E R 5 Insert O rings tighten Unions Take care not to crimp O ring Do not...

Страница 12: ...r Mounting Kit Shingle Mount Hanger Bolt Kit Shingle Mount Flange Kit Tile Mount Kit Gobi 1 4 RAIL 000 001 40089 Splice Kit for Joining Rails 1 Kit E F H G N D 3 8 16 x 1 SS Bolt1 1 2 13 SS Flange Nut 3 8 16 SS Flange Nut 1 2 13 x 1 25 SS Bolt 3 8 SS Flat Washer1 1 2 13 x 6 SS Hanger Bolt Flush Mount Flange 3 8 x 4 SS Lag Screw Tile Bracket Gobi Collector Clip Rail L Bracket 1 2 SS Flat Washer 3 8...

Страница 13: ...late to drill two 3 8 holes for lag screws add roof sealant to holes and flange Lag in 2 screws Place 3 OATEY 1 1 4 flashing over flange Replace 4 shingle over flashing follow best roofing practices to ensure seal Remove 1 tiles Locate a rafter and use tile bracket as template to drill three 3 8 holes for lag screws add roof sealant to holes Lag in 2 screws Replace 3 tiles over bracket follow best...

Страница 14: ...DIPTUBE SHORT DIPTUBE SHORT DIPTUBE Helio Tank 119 Helio Tank 80 DRAIN Figure 3 0 1 HPAK Connections Figure 3 0 2 HPAK Hydraulic Figure 3 1 1 HPAK and Helio Tank 119 Connections Figure 3 1 2 HPAK and Helio Tank 80 Connections 3 1 Tank Orientation If using a Helio Tank for installation orient the proper solar connections in line with the HPAK connections to eliminate piping On all tanks ensure prop...

Страница 15: ... specific area is not available attach to a metal drain disconnected lower element or use the cold in for lower tank sensor use the hot out for a top tank sensor The collector sensor must go on the outlet header of the array For Pro models the energy production is default set to calculate via the collector outlet sensor and the pre installed flow meter temperature and flow sensor For greater accur...

Страница 16: ...the outer mounting holes on the flattened part of the X Align the top and bottom lugs on the X with the top and bottom mating holes on the HPAK pre mounted bracket and hang Pull the HPAK down to lock in the lugs with the HPAK bracket holes 3 5 Expansion Tank Mounting Helio Paks come with a pre sized expansion tank of bladder type If the shipped expansion tank volume is less than 1 5th of the total...

Страница 17: ...ics below Use dielectric unions when connecting piping to the storage tank nipples When using the Helio Tank appropriately sized flex hoses can be purchased from Heliodyne to avoid rigid copper plumbing In the case of standard storage tanks Heliodyne Gas Tank or multiple tanks this is unavoidable When using the Helio Tank the DHW Cold is shared with the HPAK Cold NEVER share the hot DHW and HPAK t...

Страница 18: ...e 4 2 5 Flow Thru Connection 4 2 Different Tank Schematics If your tank is not here contact Heliodyne with questions Refer to the valve descriptions on the previous page In accordance with SRCC standard OG 300 all piping and valves must be labeled Attach the waterproofed labels provided with this manual to the appropriate components using zip ties NOTE For single tank electric systems disconnect l...

Страница 19: ...tion with environment protection or Solar Pipe from Heliodyne Gobi collectors can be put in portrait arrays of up to eight Install bleed vents for filling at local high points Install a flexible arm or line on either side of the inlet and outlet to allow for header expansion 4 3 0 Portrait Single Collector or Array 4 3 1 Single Horizontal Collector 4 3 2 Multiple Horizontal Collectors 4 3 3 Multip...

Страница 20: ...rements Air vents or bleed vents at the high points in the system help rid the system of air during filling only If using any type of automatic air vent close vent after filling is complete as vents are not suitable for glycol systems or systems without continuously replaced fluids For use with a pump connect pump supply hose to position 3 at right and return hose to position 2 Turn 1 so slot is h...

Страница 21: ...ube valve for pressurization it should be charged with approximately 25 psig 6 0 3 Check the glycol color concentration and pH Heliodyne has glycol testing kits that perform the required analysis Review the data sheet for Dyn O Flo HD in this manual for proper levels Glycol should be a bright green color anything else needs to be replaced Use only Dyn O Flo HD or equivalent 6 0 4 Check the control...

Страница 22: ...otection Use safety glasses Spills Cover with absorbent material soak up and seep into bag Disposal Discharge into sanitary sewers only with the explicit pre approval of the local waste water facility Any disposal practice must be in compliance with federal state provincial and local laws and regulations Check with the appropriate agencies 7 0 5 Maintenance The glycol water mix should be tested pe...

Страница 23: ...liodyne Customer Service by email at sales heliodyne com by letter to 4910 Seaport Ave Richmond CA 94804 Provide proof of purchase and date Should service be requested and no defect found in the Product then a reasonable charge will be made for the service In no event shall HELIODYNE be liable for the following Conditions resulting from a defect in a component or part that does not make up the HEL...

Страница 24: ...Heliodyne Inc 4910 Seaport Avenue Richmond CA 94804 T 510 237 9614 F 510 237 7018 www heliodyne com Sales Inquiries sales heliodyne com Information and Support info heliodyne com ...

Отзывы: