78
• System EEPROM appears to be corrupted
Corrective action: Reset power off/on, contact customer ser-
vice
Hardware Warnings
• CH1 F.S. INVALID/ CH2 F.S. INVALID:
Danger, the PTE-2 may not display the full scale psi when
applied (A legacy PTE-1 module with invalid output at full
scale) Contact Customer Service
• CH1 Low Span / CH2 Low Span
Danger, the PTE-2 may not display the full scale psi when
applied (A legacy PTE-1 module with invalid output at full
scale) Contact Customer Service
• Loop supply overloaded: see troubleshooting section
• Loop supply reset failed: see troubleshooting section
• FRAM write failed: Contact customer service
• FRAM read failed: Contact customer service
• Datalog corrupt: Contact customer service
•
Datalog error corrected: if warning reoccurs contact cus-
tomer service
•
Can’t read clock: There is an issue with the internal real
time clock,
• Current date bad: the real time used may not be accurate.
•
Failed to open file/ Failed to close file: SD card failure, card
may be bad or full
System Warnings
• SYS not-calibrated: The PTE-2 is not calibrated, contact
customer service
•
Out of internal memory: datalog memory is filled, transfer to
SD Card and clear internal datalog to make room.
•
Out of datalog: maximum number of datalogs reached,
transfer to SD Card and clear internal datalog to make
room.
•
Out of records: present datalog can take no more records,
start a new datalog.
Operation Warnings
•
CH1 zero out of bounds/ CH2 zero out of bounds: input
pressure is too high to be zeroed
•
CH1 not a pressure mod / CH2 not a pressure mod:
attempting to zero or tare a module which is not a pressure
module
•
CH1 conversion invalid/ CH2 conversion invalid: module
range is not valid for Units selection
•
No SD card present: Attempting to perform an SD card
operation with non-installed SD card
•
SD card locked: attempting to transfer to an SD card but
the write protect tab is engaged.
•
No module to damp: attempting to damp with no module
present
•
Can’t enter MENU (log): The MENU cannot be entered
while datalogging, press the Esc key to halt a datalog when
ready.
System Warnings
• Low battery: main battery is low, replace with four fresh AA
alkaline batteries
•
RTC battery low: Real time clock battery is near end of life.
The battery needs to be replaced. This is not a field service
item. Contact customer service.
• Bad msg sent to display: reset PTE-2, contact customer service
SECTION 16 b.
TROUBLE SHOOTING CONT.