background image

11

196349 rev 1

EN

9.4.14  36 Advanced Pin code

To change the code to your personal choice, use the 
up and down 

arrow keys

 to change the first digit, press 

select

 to confirm. Continue with the second, third and 

fourth digit. When completed press 

select

 to confirm the 

new four-digit PIN code. 

Warning! 

Make sure that you remember the new code.

9.4.15  37 Dist Unit

This provides you with the opportunity to change unit 
type between centimeters and inches.

9.4.16  43 Advanced Code

It is possible to enable/disable the request for a PIN 
code. This will remove the PIN code request in program 
mode and the code 

0000

 will give you access to ad-

vanced settings. Press 

select

 to confirm your choice. 

9.4.17  44 Reset Prog. settings

You can reset to the pre-programmed factory settings for 
all programs. Confirm by pressing 

yes

.

9.4.18  45 Reset Filter Timer

After a filter change on the cassette/s, restart the filter 
timer with this setting. Confirm by pressing 

yes

 to reset 

the filter time counting.
To adjust the value in the filter timer, see 9.4.11.

9.4.19  46 Statistics

The following information is available:

Run time 

Shows accumulated working hours and minutes.

Start-ups 

Shows the total number of starts of the dryer. 

Σ

 (Total Power Consumption) 

 

Presents the total energy consumption.

Φ

 (Average power consumption)

 

Presents the average consumption for all runs.

9.4.20  47 Perform Self test

In this test all the important input and outputs to and 
from the computer can be tested. This test will give the 
opportunity for a quick and accurate function verification 
of the different parts of the system.
This test procedure is only available in English. By press-
ing the 

yes

 button, you enter the first step of the self-test. 

To exit the self-test, press the 

start/stop

 button.

Automatic testing includes the following:

Test 1: Push Button Test

 

All buttons on the control unit are tested. The corre-
sponding symbols are displayed by pressing the buttons. 
Press 

enter

 for approx. three seconds in order to con-

tinue to the next step of the test program.

Test 2: Display Test

 

Verify that all pixels light up on the display. Press

 enter

and check that all pixels go out. Press 

enter

* to continue.

* or upper left software button

Test 3: Buzzer Test

 

Check that the buzzer sounds. Press 

enter

 or 

next

 to 

continue.

Test 4: Cassette IR Test 

The IR cassette lamps (output I) light up. Check that all 
the IR lamps are lit. For safety reasons this test is limited 
to 10 seconds. Press 

enter

 or 

next

 to continue.

Test 5: Ventilator Test/Cassette/Control unit 

The ventilator in the cassette and control unit now starts. 
A sound from the ventilator confirms that it is working. 
If the dryer is equipped with two or more cassettes, 
you will have to repeat test no. 4 and 5 for the other 
cassette/-s. Press 

enter

 or 

next

 to continue.

Test 6: Laser Test (OPTION) 

Direct the laser towards the object. Check that a red dot-
ted circle or point is visible on the object. Press 

enter

 or 

next

 to continue.

Test 7: Temperature Sensor Test (OPTION) 

Direct the temperature sensor towards an object that is 
at room temperature. The temperature on the display 
should not deviate from room temperature by more than 
±3 °C or ±5 °F. Press 

enter

 or 

next

 to continue.

Note!

 Temperature measurement is made as an average 

of a surface according to chapter 8.1.

Test 8: Distance Sensor Test (OPTION)

 

Direct the distance sensor towards the object at a 
distance of 0.3-1 m. Check that the distance shown on 
the display matches the manually measured distance. A 
deviation of ±3 cm is acceptable. Press 

enter

 or 

next

 to 

continue.

Test 9: Cassette Temp. Switch and Circuit Board Temp.

 

The circuit board has a temperature measuring device 
that is seen on the display. The temperature is shown in 
ºC or ºF depending on the settings you have made. The 
circuit board lifetime will be shortened if temperatures 
are above 70ºC/158ºF during operation. If this happens 
during drying a new window will appear after the com-
pleted drying cycle saying “warning High temp Pc”.

There is also an indication of the temperature in each 
cassette which is in reality only a temperature switch 
which will trigger when the temperature is above 150ºC. 
The value -13ºC is given when the temp switch is not 
triggered and - - - when it is triggered. If the temperature 
gets too high during operation a warning will appear 
showing the actual cassette and the value 500 the drying 
operation will also be terminated.

Test Completed 

Automatic testing is now complete. Press 

enter

 or 

next

 

to finish.

9.4.21  49 Power Rating 1

Possibilities to independently the other outputs give the 
power rating for output 1.

Option:

 0-99.9 kW where 0.0 is inactive.

9.4.22  50 Power Rating 2

Possibilities to independently the other outputs give the 
power rating for output 2.

Option:

 0-99.9 kW where 0.0 is inactive.

Содержание IRT System Series

Страница 1: ...196349 rev 1 Hedson Technologies AB 2018 IRT Dryer Siemens Leading Edge Protection EN Operation Manual original language...

Страница 2: ...wner 5 5 Assembly instruction 5 6 Basic instruction for operation 5 7 Program mode 8 8 Extended usage information 9 9 Settings mode 9 10 Maintenance and Service 12 11 Spare parts 14 12 Safety inspecti...

Страница 3: ...ounted on the lifting platform 1 Safety instructions 1 1 Operator s duty of care The IRT Siemens Leading Edge Protection Dryer is designed and built after a hazard assessment was con sidered and follo...

Страница 4: ...king under the raised working platform and during its lifting and lowering movements is not permitted 3 Product description The IRT Siemens Leading Edge Protection Dryer is a maneuverable infrared dry...

Страница 5: ...ir only A filter regulator must only be installed in the air supply line air filter and water separator 6 Basic instruction for operation Move the dryer to the site where you want to use it This can o...

Страница 6: ...amps Control panel 1 The lights turn green when the correct distance obtained between IR lamps and object This distance must be checked before the IR lights turned on During operation with IR lamps th...

Страница 7: ...ered This is normally not a part of the everyday usage To enter the settings mode press both arrow keys when you turn the main switch to position 1 Read chapter 9 for more information 6 8 Program inte...

Страница 8: ...is finished If this happens check the cooling system of the con trol unit fan filter or ambient temperature 3 Paint Temperature Alarm Also called Process alarm see 8 2 Option if pyrometer is used 4 Fi...

Страница 9: ...ram is terminated In case of process alarm check if the temperature measuring device pyrometer is aligned correctly on the surface to be dried and that it is not registering unwanted material temperat...

Страница 10: ...o select no yes Press select to confirm 9 4 6 7 Basic PIN Code You can change the PIN code to prevent unauthor ized access to the basic setting as described in table in chapter 9 4 To do this use the...

Страница 11: ...t 4 Cassette IR Test The IR cassette lamps output I light up Check that all the IR lamps are lit For safety reasons this test is limited to 10 seconds Press enter or next to continue Test 5 Ventilator...

Страница 12: ...uitably trained personnel Do not use running water or flammable liquids for clean ing Abide by the following points to ensure a long service life and continuous operation of the dryer Only original sp...

Страница 13: ...round the lamp until the fit ting is completed 1 Loosen the mounting screws on both end cov ers 2 Loosen both lamp end protections 3 Pull the protection out of the slide The screws for the lamp holder...

Страница 14: ...st environmental pro tection facility for recycling 11 Spare parts The following spare parts are the most common ones for the SingleHeater IR units Part Part nr 1 Fan 202024 2 Filter 103055 3 IR lamp...

Страница 15: ...s to the zero position when released Fall arrester function Emergency release status Air bellows status Supporting structure status Function test Lifting lowering Function test Lifting lowering with l...

Страница 16: ...lowing standard s or other normative document s EN 61000 6 4 Electromagnetic Compatibility Generic Emission Standard EN 61000 6 3 Electromagnetic Compatibility Generic Immunity Standard EN 60204 1 Saf...

Страница 17: ...appendix 1 761 054_PNTS 77 Electrical diagram for IRT Siemens Leading Edge Protection Dryer equipment is found in the appendix 2 15 Weights and Dimensions The overall weight is 665 kg Dimensions as b...

Страница 18: ...sette tripped Check fans filters hoses and ambient tempera ture Reset by pressing the temp switch button Lifting malfunction Maintenance unit manometer without mains pressure Ensure the mains pressure...

Страница 19: ...70 196349 rev 1...

Страница 20: ...53 42 00 Telefax 46 0 40 43 29 01 www hedson com HEDSON TECHNOLOGIES AB Box 1530 SE 462 28 V nersborg Tel 46 0 40 53 42 00 Telefax 46 0 521 669 09 www hedson com Hedson Technologies 2017 The manufact...

Отзывы: