background image

8

196349 rev 1

EN

7.2  Run

7.2.1  Start check

Use the cassette selection button on the 
keyboard to alter between one, two or three 
active cassettes. Use the temperature control 
button to turn on/off the temp. control (only 
possible 

on

 when temp. control is included 

in the unit), see 8.1. 

Optional:

 The distance is indicated on the 

display as numbers or by the texts ”Too 
Close”, ”Too Far” or ”Correct” (only ap-
pears when start on Keypads). If measuring 
fails "Check distance manually" appears.

7.2.2  Start drying

Press 

start

 to begin the drying sequence. 

Power control

, continues mode on:

 

the 

time will start counting. 

Temperature control

, continues mode 

off: the remaining time of the flash off 
will start counting down. When the flash 
off is finished, the program automatically 
changes to full bake mode.

7.2.3  Program values

Press

 

view

 and the screen shows the 

values for power (0–100 % of machine 
capacity) and energy consumption of 
current drying process. When the unit 
is temperature controlled: both a target 
and an actual value is given. 

Note!

 An inactive temperature control 

does not show temperature values. 
Press 

view

 again and total energy consumption 

per drying process is shown for the last 10 runs.

7.2.4  Drying complete

When flash off and full bake times have 
expired the software returns to 7.1. 

Note! 

To extend the lifetime of the lamps, the 

ventilators will continue to run for cooling. Af-
ter three minutes they turn off automatically. 

Note!

 When the drying program is complet-

ed, the temperature control will automatically 
reactivate (if included in the unit).

7.2.5  Alarm functions

There are five possible types of alarm: 

1. Cassette Temperature Alarm

 

If a temperature switch is triggered in a cas-
sette the drying operation will be terminat-
ed and there will be an alarm. In the display 
there will be a warning message stating 
that the temperature in the cassette is too 
high. A value of 500 is also showing beside 
the cassette where the switch is triggered. If 
this happens; Check fans, filters, hoses and 

ambient temperature. Reset by pressing on 
the indicated reset button on the display. 

2. Box Temperature Alarm

 

When the temperature exceeds 70ºC at the 
circuit board this alarm will show in the display 
after the drying operation is finished. If this 
happens check the cooling system of the con-
trol unit (fan, filter or ambient temperature). 

3. Paint Temperature Alarm

 

Also called Process alarm, see 8.2. Option if
pyrometer is used. 

4. Filter Alarm

 

When the maximum operation time for the
filter is reached, there will be a warning 
message stating this. The default time is 400
hours, to change this see 9.4.11. To reset the
alarm, see 9.4.18. 

5. Phase Alarm

 

There are two possible sources: 

1. Disturbance in main electrical supply:

 

Check incoming electrical supply all phases. 

2. Internal fuse tripped:

 Check fuses and

reset if tripped, see 11. 
To reset the alarm press 

reset

 indicated on

the display or restart the dryer.

7.3  Edit

7.3.1  Properties 

The values of the chosen program will show 
on the display. Press 

Temperature control

 to 

switch between properties with and without 
temperature control. A change in either prop-
erty is independent of the other one. See 8.1.

7.3.2  PIN Code

Use the arrow keys to set the correct digit. Press 

enter

 to confirm and to edit the second, third and 

fourth digit of the advanced PIN code. 

Note! 

An entered PIN code is valid for all 

entries until the main switch is turned off. See 
8.2 for advanced PIN code.

7.3.3  Edit program parameters 

When marked, change the value of the 
parameters with the arrow keys. Press 

enter

 to 

change the next value and so on. Pressing 

en-

ter

 for the last value directs the user to editing 

of program position and name. Press

 cancel 

to exit without saving any parameters. It is 
also possible to change final temperature and 
power level when the unit has been started. 
Press 

edit

 and change value, then 

save

.

7.3.4  Edit program position/name

When marked, change the program number 
with the arrow keys. Press 

enter

 to confirm 

and to edit the next symbol.  

Note! 

Changing the number will also change 

the program position in the program list.

7. Program Mode – General rules for navigation in the software

The display shows software defined options in the bottom corner fields. 

To adjust the values, use the 

arrow keys.

To move to previous display without saving, press 

cancel

.

7.1  Basic navigation

Power control

Temperature control

There are 15 predefined programs. All 15 programs have editable positions, names and 
drying parameters. 
Scroll up or down using the 

arrow keys

, press 

select

 to run the program or 

view

 to edit.

Stop

 or 

cancel

 

returns to 7.1.

Power control

Temperature control

Power control

Temperature control

Содержание IRT System Series

Страница 1: ...196349 rev 1 Hedson Technologies AB 2018 IRT Dryer Siemens Leading Edge Protection EN Operation Manual original language...

Страница 2: ...wner 5 5 Assembly instruction 5 6 Basic instruction for operation 5 7 Program mode 8 8 Extended usage information 9 9 Settings mode 9 10 Maintenance and Service 12 11 Spare parts 14 12 Safety inspecti...

Страница 3: ...ounted on the lifting platform 1 Safety instructions 1 1 Operator s duty of care The IRT Siemens Leading Edge Protection Dryer is designed and built after a hazard assessment was con sidered and follo...

Страница 4: ...king under the raised working platform and during its lifting and lowering movements is not permitted 3 Product description The IRT Siemens Leading Edge Protection Dryer is a maneuverable infrared dry...

Страница 5: ...ir only A filter regulator must only be installed in the air supply line air filter and water separator 6 Basic instruction for operation Move the dryer to the site where you want to use it This can o...

Страница 6: ...amps Control panel 1 The lights turn green when the correct distance obtained between IR lamps and object This distance must be checked before the IR lights turned on During operation with IR lamps th...

Страница 7: ...ered This is normally not a part of the everyday usage To enter the settings mode press both arrow keys when you turn the main switch to position 1 Read chapter 9 for more information 6 8 Program inte...

Страница 8: ...is finished If this happens check the cooling system of the con trol unit fan filter or ambient temperature 3 Paint Temperature Alarm Also called Process alarm see 8 2 Option if pyrometer is used 4 Fi...

Страница 9: ...ram is terminated In case of process alarm check if the temperature measuring device pyrometer is aligned correctly on the surface to be dried and that it is not registering unwanted material temperat...

Страница 10: ...o select no yes Press select to confirm 9 4 6 7 Basic PIN Code You can change the PIN code to prevent unauthor ized access to the basic setting as described in table in chapter 9 4 To do this use the...

Страница 11: ...t 4 Cassette IR Test The IR cassette lamps output I light up Check that all the IR lamps are lit For safety reasons this test is limited to 10 seconds Press enter or next to continue Test 5 Ventilator...

Страница 12: ...uitably trained personnel Do not use running water or flammable liquids for clean ing Abide by the following points to ensure a long service life and continuous operation of the dryer Only original sp...

Страница 13: ...round the lamp until the fit ting is completed 1 Loosen the mounting screws on both end cov ers 2 Loosen both lamp end protections 3 Pull the protection out of the slide The screws for the lamp holder...

Страница 14: ...st environmental pro tection facility for recycling 11 Spare parts The following spare parts are the most common ones for the SingleHeater IR units Part Part nr 1 Fan 202024 2 Filter 103055 3 IR lamp...

Страница 15: ...s to the zero position when released Fall arrester function Emergency release status Air bellows status Supporting structure status Function test Lifting lowering Function test Lifting lowering with l...

Страница 16: ...lowing standard s or other normative document s EN 61000 6 4 Electromagnetic Compatibility Generic Emission Standard EN 61000 6 3 Electromagnetic Compatibility Generic Immunity Standard EN 60204 1 Saf...

Страница 17: ...appendix 1 761 054_PNTS 77 Electrical diagram for IRT Siemens Leading Edge Protection Dryer equipment is found in the appendix 2 15 Weights and Dimensions The overall weight is 665 kg Dimensions as b...

Страница 18: ...sette tripped Check fans filters hoses and ambient tempera ture Reset by pressing the temp switch button Lifting malfunction Maintenance unit manometer without mains pressure Ensure the mains pressure...

Страница 19: ...70 196349 rev 1...

Страница 20: ...53 42 00 Telefax 46 0 40 43 29 01 www hedson com HEDSON TECHNOLOGIES AB Box 1530 SE 462 28 V nersborg Tel 46 0 40 53 42 00 Telefax 46 0 521 669 09 www hedson com Hedson Technologies 2017 The manufact...

Отзывы: