- 22 -
Service Call 0844 736 9138, Technical Help (Chargeable) Call 0906 802 0253
• Activate the Heating and Domestic Hot Water functions.
• Run the appliance for at least 15 minutes, with a heating
temperature set to greater than or equal to 50°C (not
applicable for an installation with underfl oor heating).
• Vent air from each radiator again until the water fl ows
normally, then close the vents.
• If you have diffi culties in removing the air, launch the air-
removal programs in the heating circuit (see the chapter
("Technical settings for the appliance and list of parameters").
• Make sure that the pressure indicator shows a value of 1.0
bar; if not, top up the water again.
11.5 Initial lighting
Control
The combustion for this appliance has been
checked, adjusted and preset at the factory for
operation on natural gas (G20) as defi ned on the
appliance data label.
No measurement of the combustion is necessary.
Should the appliance require to be converted to LPG
gas ensure you follow the gas conversion section
before lighting the boiler.
• Check that the appliance has been installed in accordance
with the instructions.
• Check the integrity of the fl ue system and fl ue seals.
• Check the integrity of the appliance combustion circuit and
relevant seals.
• Check that all internal/external controls are calling for heat.
• Check that the gas service isolation is open.
• To adapt the appliance to another type of gas, see "LPG
conversion".
Adjusting the temperature
bar
1
2
3
4
0
22
21
20
19
18
17
16
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
24
23
mode
reset
1
2
3
5
4
6
4
3
1
2
3
5
4
6
4
3
Key
1 System pressure gauge
2 ON/OFF and Mode selection button
3 Display
4 Temperature adjustment
5 Anologue clock
6 Reset button
Display
• Light the appliance by following the procedure below.
• Select the "H domestic hot water" function by
pressing the “Mode” button repeatedly to scroll through your
options until
are shown.
The appliance will enter a self checking routine, then the fan
will start and the ignition sequence commence. The boiler, if
necessary, will automatically repeat the ignition sequence a
further 4 times.
If the burner fails to ignite “F28” will be displayed, initially, this
may be due to air in the gas supply line. Press the reset button.
Do not use the reset button to purge the installation - never
press reset more than 3 times.
• Press the
central heating water temperature button and
the factory setting temperature will be displayed.
• Press
or
buttons to adjust.
• Press the hot water temperature
button and the factory
setting temperature will be displayed.
• Press
or
buttons to adjust.
• Open a hot water tap, the display will indicate the domestic
hot water temperature.
• Check that hot water is available at all taps, then close.
11.6 Gas rates
The supply from the governed meter must be of adequate size
to provide a steady inlet working pressure of 20mbar (8in wg) at
the boiler.
• On completion, test the gas installation for tightness using
the pressure drop method and suitable leak detection fl uid,
purge in accordance with the above standard.
Due to the modulating operation of the boiler and the
need to check the gas inlet pressure and measure
the gas rate at maximum rate, it will be necessary to
force it to maximum.
• Activate the test mode "P.01" and set the value to 100 in
order to force the burner at P. max. See chapter "Specifi c
adjustment ► Appliance technical settings and parameter list
► Test modes".