7.4 The flue should not be sited where the condensate
plume may give rise to a nuisance factor under
certain weather conditions.
NOTE: If you have difficulty siting the flue in an
appropriate location your supplier will be happy to
supply an “anti-plume management kit”, which
discharges the flue products at a higher level.
8.1 The boiler utilises a concentric flue arrangement
which consists of a 60mm-diameter inner flue and
100mm-diameter outer air inlet duct.
8.2. Various types of flues can be purchased with the
boiler but the standard 700+/-5mm flue kit (figure 5) is
supplied with the boiler, which can be routed to the
rear, left or right of the appliance by means of a 90°
bend. The bend is connected to the boiler using the
screws provided and sealed with the gasket.
8.3. The 60/100 mm flue pipes may be extended up to a
maximum of 2.5 m using additional spare components
available from your supplier. This length can be
increased to 7 m using the 80/125 mm flue kit.
8.4. A vertical 60/100 mm flue kit is also available from
your supplier up to a maximum length of 3m. The
terminal is suitable for a flat or pitched roof. This
length can be increased to 7 m using the 80/125mm
flue kit.
8.5. If horizontal and vertical flue lengths are less than
1 m, the restrictor (air diaphragm) – figure 6 must be
fitted on the combination boiler.
Please find the information sheet for the installation
of restrictor given with documentation group.
The diameter of air diaphragm changes according to
the installation types.
C12-C32 C42-C52
60/100
80/125 80/80
24 kW
Ø80 Ø80
Ø80
28 kW
Ø80 Ø82
Ø82
8.6 The air diaphragm should be removed if the length of
the flue pipe installation is below:
C12-C32 C42-C52
60/100
80/125 80/80
24 kW
>1 m
>2 m
28 kW
>1 m
>2 m
8.7. The connection of vertical flue system is similar to
the Horizontal flue connection. The flue is connected to
the boiler via connection screws whilst the sections are
held together with the clamps provided.
8.8. To avoid condensate dripping from the terminal the
flue should be installed with an upward gradient (from
the boiler) of 3
o
. Note that some new flue may have the
3
o
built in.
8.9. The installation types for room sealed versions are
C12-C32-C42-C52
8.10. The boiler can be used with separate ducts such as
80/80 to fit required type of installations.
8. General Flue Info
Note. For each additional 90º elbow used the
maximum flue length must be reduced by 1.5 m,
whilst the use of 2 x 45º bends warrants a
reduction of 2m.
Figure 6
Figure 5
WARNING!
Page 12
ONLY A HEATLINE APPROVED FLUE IS TO BE
USED WITH HIS PRODUCT.FAILURE TO COMPLY
WITH THIS REQUIREMENT WILL INVALIDATE YOUR
GUARANTEE AND COULD LEAD TO A DANGEROUS
SITUATION.
12