NOVUS SERIES INSTALLATION INSTRUCTIONS
6. FIRESTOP SPACER/VENT INSTALLATION
Frame an opening and install a firestop spacer
whenever the vent penetrates a ceiling/floor area, as
shown in Figure 30. Frame the opening with the same
sized lumber as used in the ceiling/floor joists. Unless
the flue is offset, the hole should be directly above the
appliance. DO NOT pack insulation around the vent.
Figure 30
Installing the Firestop Spacer
b. Rear Vent Vertical Termination
1) Rear Vent Clearances
See Figure 28 for clearance information.
2) Vent Lengths
Various venting configurations are shown in
Figure 29 from which maximum vent runs can
be determined.
Figure 28 - Vertical Termination Clearances
Figure 29 - Vertical Termination Vent Lengths
WARNING - RISK OF FIRE!
Always maintain minimum clearances or greater
around the vent system. Do not pack air spaces with
insulation or other material.
WARNING!
The horizontal run of vent must have a 1/4 rise for
every 1 ft. of run towards the termination. Never allow
the vent to run downward. This could cause high
temperatures and may create a fire hazard.
Starter elbow
cannot
be used
in any rear vent
configuration