7056-138L • August 23, 2019
32
Heatilator EcoChoice WS18
www.heatilatorecochoice.com
NOTE:
Clearances may only be reduced by means
approved by the regulatory authority having
jurisdiction
BACKWALL / SIDEWALL
A
B
C
D
E
F
E
F
CORNER INSTALLATION
G
H*
90° OFF TOP
UP & OUT CEILING
CLEARANCE
STOVE TO CEILING
CLEARANCE
C
D
ALCOVE TOP VIEW
G
A
B
ALCOVE SIDE VIEW
C. Clearances to Combustibles (UL and ULC)
MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS: INCHES & (MILLIMETERS)
NOTE: ALL “A”, “C” AND “F” DIMENSIONS ARE TO INSIDE DIAMETER OF FLUE COLLAR.
A
B
C
D
E
F
G
H
INSTALLATION: Full Vertical OR Horizontal with 2 foot (609mm) minimum vertical Off Appliance Top
Single Wall Pipe
12 (305)
8.25 (210) 21 (533.4) 11.5 (292) 3.5 (89)
13 (330)
54.25 (1378)
*
Double Wall Pipe
10.75 (273)
7 (178)
19 (482.6)
9.5 (241)
3 (76)
12.5 (317.5) 54.25 (1378) 10 (254)
INSTALLATION: 90
°
Elbow Off Top of Appliance Through Back wall
Single Wall Pipe
11.75 (298)
8 (203)
18.25 (464) 8.5 (216) 3.5 (89)
13 (330)
54.25 (1378)
*
Double Wall Pipe
11.75 (298)
8 (203)
18.25 (464) 8.5 (216)
3 (76)
12.5 (318) 54.25 (1378) 10 (254)
For alcove only:
Six inch diameter listed Double wall air insulated connector pipe with
UL103 HT listed factory built
Class A chimney or masonry chimney
. Maximum depth of Alcove shall be no more than 48 inches (1219mm) and the
referenced alcove clearances. Canada must comply with
CAN/ULC-S269 M87 for the 650° factory built chimney
.
* SEE PIPE MANUFACTURERS CLEARANCES - NOT TESTED
Fire Risk.
• Comply with all minimum clearances to
combustibles as specified.
•
Failure to comply may cause house fire.
WARNING
NOTE: Service Space
•
In order to replace the tube channel assembly a
clearance of 19 inches (483mm) is required on the
right side of appliance in order to remove the tubes
with the appliance in place.
•
If space is not available, the appliance will have to be
disconnected from the chimney to proceed with the
tube replacement.