CALIBER DESIGNER DIRECT VENT
WARNING!
Always maintain minimum clearances or greater around the vent system. Do NOT pack air spaces with insula-
tion or other material.
Note:
Horizontal runs will require the use of one vent
support (or metal plumbers strap) for every 3 of vent.
CAUTION:
Provisions must be made to provide adequate combustion and ventilation air.
WARNING!
The horizontal run of vent must have a ¼ rise for every 1 of run towards the termination. Never allow the vent
to run downward. This could cause high temperatures and may present a fire hazard.
Note:
To ensure proper operation, verify that the venting
and termination are unobstructed.
1. Horizontal Venting Termination
(See pages 17 and 18 for vertical termination.)
a. Clearances
See Figures 19-20 for clearance information.
Figure 19
Venting Clearances to Combustible Materials
(Rear Venting)
Figure 20
Venting Clearances to Combustible Materials
(Top Venting)
E. VENTING
WARNING!
If you have chosen horizontal termination, be sure
there are no future obstructions from trees, bushes,
snow drifts, etc.