E. Installing Wall Shield Firestops and Horizontal Termination Cap
NOTE:
Where required, an exterior wall fl ashing is
available.
When penetrating a brick wall, a brick extension kit
is available for framing the brick.
Installing the Horizontal Termination Cap
Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.
Flash and seal as appropriate for siding material at outside
edges of cap.
When installing a horizontal termination cap, follow the cap
location guidelines as prescribed by current
ANSI Z223.1
and
CAN/CGA-B149
installation codes.
Figure 8.14 Hole and Vent Pipe
WALL SHIELD
FIRESTOP
(EXTERIOR)
WALLSHIELD
FIRESTOP
(INTERIOR)
HEAT SHIELD
TRIM HEAT SHIELD IF
TOO LONG.
USE EXTENDED HEAT
SHIELD (DVP-HSM-B) IF
TOO SHORT.
Figure 8.15 Heat Shield, Interior & Exterior Wall Shield Firestops
Fire Risk
Exhaust Fumes Risk
Impaired Performance of Appliance
WARNING
• Ensure vent components are locked together correctly.
• Pipe may separate if not properly joined.
• Position the wall shield fi restops on both sides of the
hole previously cut and secure the wall shield fi restops
with nails or screws.
• The heat shields of the wall shield fi restops
MUST BE
placed towards the top of the hole.
• Continue the vent run through the wall shield fi restops.
Fire Risk.
Explosion Risk.
Do NOT pack insulation or other
combustibles between fi restops.
WARNING
• ALWAYS maintain specifi ed clearances around venting
and fi restop systems.
• Install
fi restops as specifi ed.
Failure to keep insulation or other material away from vent
pipe may cause fi re.
VENT PIPE
1 in. (25.4 mm)
10 in.
(254mm)
10 in.
(254mm)
For Horizontal Runs
- Wall shield fi restops are
REQUIRED
on
both sides of a combustible wall through which the vent passes.
NOTE: Model SLK-01TRD does not need an exterior
wall shield
fi restop on an exterior combustible wall.
To install wall shield fi restops for horizontal runs that pass
through either interior or exterior walls:
Cut a 10 in. x 10 in. (254mm x 254mm) hole for SL-D-
series pipe. The center of the framing hole is one (1) inch
(25.4mm) above the center of the horizontal vent pipe.
WARNING
Fire Hazard
Impaired performance of appliance
• Telescoping
fl ue section of termination
cap MUST be used when connecting pipe
section to termination cap.
• Maintain a 1-1/2 inch minimum overlap on
telescoping fl ue section of termination cap.
Burn Risk
• Termination caps may be hot. Consider their
proximity to doors or other traffi c areas.
• Local codes may require installation of a cap
shield to prevent anything or anyone from
touching the hot cap.
WARNING