background image

8

TROUBLESHOOTING

No Display

:  Check the power to the Digi-Span.  The Digi-Span can run off any of the power sources described on page 2.

Turn the power off and back on.

OPN

 Display

:  The Digi-Span does not see a sensor connected.  Check the wires are continuous from the sensor to the Digi-

Span controller.  Then follow the procedure for Incorrect Pressure Display.

SHT

 Display

:

  The Digi-Span sees a short across the input terminals.  If you remove the sensor wires from the Digi-Span

terminals, the display should change to read 

OPN

.  If the display does not change to 

OPN

, the Digi-Span may be dam-

aged.

Incorrect Pressure Display:

  Remove the wires from the 

SENSOR

 screws.  The display should change to read 

OPN

. If it

doesn’t, the Digi-Span may be damaged.  Use a voltmeter to measure across the 

SENSOR

 screws.  There should be at

least 24VDC across the two terminals.  If there isn’t, the Digi-Span may be damaged.  Finally, reconnect the sensor with a
mA meter in series with one sensor wire.  The mA reading should correspond to the chart below.  You can use the Offset
value (see pg. 5 or 7) to make small adjustments to the pressure reading.

OUTPUT

 Red Light does not indicate desired stages are active:

  Check the set points and differential values.  In a

heating application, the stage will not come on until the pressure drops below the set point minus the differential.  In a
cooling application, the stage will come on when the pressure rises to the set point. (see Examples on pgs. 4 and 6).

Digi-Span does not activate the output: 

 First check the 

OUTPUT

 light to see which stages should be active.  If the

OUTPUT

 light is OFF, no stages should be running.  If the 

OUTPUT

 light is flashing or on, check page 4 for a COC or

page 6 for a TSC/TSR to see which output wires should be continuous.  Remove all connections to the Black and Red
output wires.  Check the appropriate wires for continuity.  If the wires are continuous, the Digi-Span is working properly.
Check the unit the Digi-Span is controlling to determine why it is not running.

For Technical Help or Additional Product Information contact:

Heat-Timer Corporation

20 New Dutch Lane

Fairfield, NJ 07004

Phone (973) 575-4004  Fax (973) 575 -4052

http://www.heat-timer.com

HT 059218-00

mA

30 PSI

100 PSI

200 PSI

4

0

0

0

4 . 0 8

1

4 . 1 6

1

2

4 . 4

5

4 . 5 6

1

4 . 8

5

1 0

5 . 0 6

2

5 . 6

3

1 0

2 0

6 . 1 3

4

6 . 4

1 5

3 0

6 . 6

5

7 . 2

6

2 0

4 0

8 . 8

9

3 0

6 0

1 0 . 4

1 2

4 0

8 0

1 2

1 5

5 0

1 0 0

1 3 . 6

1 8

6 0

1 2 0

1 5 . 2

2 1

7 0

1 4 0

1 6 . 8

2 4

8 0

1 6 0

1 8 . 4

2 7

9 0

1 8 0

2 0

3 0

1 0 0

2 0 0

Содержание Digi-Span TSC Pressure

Страница 1: ...nstallation or caused by power failures fire flood or lightning are not covered by this warranty The company assumes no liability for indirect or consequential damages of any nature This Heat Timer wa...

Страница 2: ...cer wires can also be connected to the back of the Digi Span using the Rear Wire connector Connect the BLACK sensor wire to yellow Rear Wire and the RED sensor wire to the orange Rear Wire Wiring the...

Страница 3: ...TSC TSR only If the display shows H then the Digi Span will be in a heating mode The relays will close when the pressure is below the set point see Example on pg 6 If the display shows C then the Digi...

Страница 4: ...2 is energized or open as shown in the Example When Output 2 is energized the Red output wires will be continuous When Output 2 is open the Red output wires will be open To adjust Set Point 2 use the...

Страница 5: ...e display will flash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice for the sensor pressure to b...

Страница 6: ...ed and will switch again every 24 hours To adjust Set Point 2 use the following steps 1 Digi Span should be displaying sensor pressure 2 Press the center button twice and release it The display will c...

Страница 7: ...ash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice to display sensor pressure immediately Offset...

Страница 8: ...UTPUT Red Light does not indicate desired stages are active Check the set points and differential values In a heating application the stage will not come on until the pressure drops below the set poin...

Отзывы: