Differential

• The differential controls how many pounds the system can fluctuate around the set points.  It is used to prevent short

cycling of the units being controlled.

• In the heating mode, a stage will energize when the sensor pressure falls to the set point minus the differential.  The stage will

open when the pressure rises to the set point (see Example on opposite page).

• In the cooling mode, a stage will energize when the sensor pressure rises to the set point.  The relay will open when the

pressure falls to the set point minus the differential.

• To set the differential, use the following steps:

1.  Digi-Span should be displaying sensor pressure.
2.   Press and release the center button three times.  The display will change to show 

dIF

.  Wait 2 seconds or press the 

UP

 or

DOWN

 button and the differential will be displayed.

3.   Press and hold either the 

UP

 or 

DOWN

 button until the desired differential is displayed.

4.   Wait approximately 10 seconds.  If the differential was changed, the display will flash.  Then the Digi-Span will return to

displaying the sensor pressure.  (If you don’t want to wait 10 seconds, press the center button once for Offset or twice to
display sensor pressure immediately.)

Offset

• The offset value calibrates the sensor pressure reading by the number of pounds selected.
• To adjust the offset, use the following steps:

1.   The Digi-Span should be displaying sensor pressure.
2.   Press the center button four times and release it.  The display will change to show 

OFF

.  Wait 2 seconds or press the 

UP

or 

DOWN 

button and the offset will be displayed.

3.   Press and hold either the 

UP

 or 

DOWN

 button until the desired offset is displayed.

4.   Wait approximately 10 seconds.  If the offset was changed, the display will flash and then show the corrected sensor

pressure.  (If you don’t want to wait, press the center button once.)

OUTPUT

 Light Indication

• The red 

OUTPUT

 light indicates how many stages are active at any given time.  When the red light is:

• OFF - Neither output stage is active.  Both the Black and Red wires are open.
• FLASHING - One output stage is active.  Either the Black or the Red wires are continuous, but not both.
• ON - Both output stages are active.  Both the Black and Red wire are continuous.

Содержание Digi-Span TSC Pressure

Страница 1: ...nstallation or caused by power failures fire flood or lightning are not covered by this warranty The company assumes no liability for indirect or consequential damages of any nature This Heat Timer wa...

Страница 2: ...cer wires can also be connected to the back of the Digi Span using the Rear Wire connector Connect the BLACK sensor wire to yellow Rear Wire and the RED sensor wire to the orange Rear Wire Wiring the...

Страница 3: ...TSC TSR only If the display shows H then the Digi Span will be in a heating mode The relays will close when the pressure is below the set point see Example on pg 6 If the display shows C then the Digi...

Страница 4: ...2 is energized or open as shown in the Example When Output 2 is energized the Red output wires will be continuous When Output 2 is open the Red output wires will be open To adjust Set Point 2 use the...

Страница 5: ...e display will flash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice for the sensor pressure to b...

Страница 6: ...ed and will switch again every 24 hours To adjust Set Point 2 use the following steps 1 Digi Span should be displaying sensor pressure 2 Press the center button twice and release it The display will c...

Страница 7: ...ash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice to display sensor pressure immediately Offset...

Страница 8: ...UTPUT Red Light does not indicate desired stages are active Check the set points and differential values In a heating application the stage will not come on until the pressure drops below the set poin...

Отзывы: