Setting the Operating Modes

• Whenever the Digi-Span is powered up, it will display the software version number and then the current operating modes.

Each display will remain on the screen approximately 5 seconds.  If the modes are correct, there is no need to make any
adjustments.

• Once the modes have been set for a particular application, they will be retained in memory and will not need to be reset.
• Note that if you do change an operating mode, you will need to reset the set points, differential and offset.
• An operating mode can only be changed when it is being displayed in the start-up sequence.  To restart the sequence it is

necessary to remove power to the Digi-Span and then power it again.

• Set the operating modes as described in sequence below:

30

100

, or 

200

 - Pressure Range

•  If the display shows 

30 

then the range will be from 0 to 30 psi and the display will be in 0.5psi increments.  If the display

shows 

100

 or 

200

, the range will be 0 to 100psi or 0 to 200psi and will display in one pound increments.

• To change the range, hold down the center button while pushing either the 

UP

 or 

DOWN

 button to toggle between ranges

.

• When the range is selected, release the buttons and wait approximately 5 seconds.

or 

C

 - Heating or Cooling (TSC/TSR only)

• If the display shows 

then the Digi-Span will be in a heating mode.  The relays will close when the pressure is below the set

point (see Example on pg.6)

• If the display shows 

C

 then the Digi-Span will be in a cooling mode.  The relays will close when the pressure is above the set

point.

• To change the mode, hold down the center button while pushing either the 

UP

 or 

DOWN

 button to toggle between the

displays of 

H

 and 

C.

• When the correct heating or cooling mode is selected, release the buttons and wait approximately 5 seconds.

TSC 

or 

TSR

 - Fixed or Rotating Lead Stage (TSC/TSR only)

•  If the display shows 

TSC

 the lead stage will not rotate.  Set Point 1 will always control the Black output wires, and Set Point

2 will always control the Red output wires.

• If the display shows 

TSR

, the lead stage will rotate every day to provide more even wear on the units being controlled;  that

is, Set Point 1 will control the Black output wires one day, and the Red output wires the next day.

• If any changes were made to the operating modes, the display will flash.  Then the Digi-Span will display the sensor pres-

sure.

BLACK

BLACK

24 VAC

or wire 120VAC to rear

transformer (blue wires)

SENSOR

TYPICAL WIRING DIAGRAM

HEATER

or CHILLER

OUTPUT 1

OUTPUT 1

POWER

RED

RED

HEATER

or CHILLER

OUTPUT 2

OUTPUT 2

POWER

WARNING

The Digi-Span can accept only
one source of power: 120VAC
or 24VAC.  If more than one
power source is applied, the
unit may be damaged.

Содержание Digi-Span TSC Pressure

Страница 1: ...nstallation or caused by power failures fire flood or lightning are not covered by this warranty The company assumes no liability for indirect or consequential damages of any nature This Heat Timer wa...

Страница 2: ...cer wires can also be connected to the back of the Digi Span using the Rear Wire connector Connect the BLACK sensor wire to yellow Rear Wire and the RED sensor wire to the orange Rear Wire Wiring the...

Страница 3: ...TSC TSR only If the display shows H then the Digi Span will be in a heating mode The relays will close when the pressure is below the set point see Example on pg 6 If the display shows C then the Digi...

Страница 4: ...2 is energized or open as shown in the Example When Output 2 is energized the Red output wires will be continuous When Output 2 is open the Red output wires will be open To adjust Set Point 2 use the...

Страница 5: ...e display will flash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice for the sensor pressure to b...

Страница 6: ...ed and will switch again every 24 hours To adjust Set Point 2 use the following steps 1 Digi Span should be displaying sensor pressure 2 Press the center button twice and release it The display will c...

Страница 7: ...ash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice to display sensor pressure immediately Offset...

Страница 8: ...UTPUT Red Light does not indicate desired stages are active Check the set points and differential values In a heating application the stage will not come on until the pressure drops below the set poin...

Отзывы: