4
COC OPERATION
Set Point 1
Set Point 1 controls when Output 1 is energized or open as
shown in the Example.
When Output 1 is energized, the Black output wires will be
continuous.
When Output 1 is open, the Black output wires will be
open.
To adjust Set Point 1, use the following steps:
1. Digi-Span should be displaying sensor pressure.
2. Press the center button and release it. The display will
change to show
SP1
. Wait 2 seconds or press the
UP
or
DOWN
button and the set point will be displayed.
3. Press and hold either the
UP
or
DOWN
button until the
desired set point is displayed.
NOTE: Set Point 1 can not be set below Set Point 2. If
pressing the
DOWN
button does not lower Set Point 1,
it may be necessary to lower Set Point 2 (see below).
4. Wait approximately 10 seconds. If the set point was
changed, the display will flash. Then the Digi-Span will
return to displaying the sensor pressure. (If you dont
want to wait 10 seconds, press the center button once
for Set Point 2, twice for Differential, three times for
Offset or four times to display sensor pressure.)
Set Point 2
Set Point 2 controls when Output 2 is energized or open as
shown in the Example.
When Output 2 is energized, the Red output wires will be
continuous.
When Output 2 is open, the Red output wires will be open.
To adjust Set Point 2, use the following steps:
1. Digi-Span should be displaying sensor pressure.
2. Press the center button twice and release it. The
display will change to show
SP2
. Wait 2 seconds or
press the
UP
or
DOWN
button and the set point will be
displayed.
3. Press and hold either the
UP
or
DOWN
button until the
desired set point is displayed.
NOTE: Set Point 2 can not be set above Set Point 1. If
pressing the
UP
button does not increase Set Point 2, it
may be necessary to raise Set Point 1 (see above).
4. Wait approximately 10 seconds. If the set point was
changed, the display will flash. Then the Digi-Span will
return to displaying the sensor pressure. (If you dont
want to wait 10 seconds, press the center button once
for Differential, twice for Offset, or three times to display
sensor pressure.)
SET POINT and DIFFERENTIAL EXAMPLE
Set Point 1
60psi
Set Point 2
40psi
Differential
2psi
OUTPUT 1 - BLACK
On a rise to
60psi
Stage
1
will Energize
Light will Flash
--------------------------------------------------
On a drop to
58psi
Stage
1
will Open
Light is OFF
OUTPUT 2 - RED
On a drop to
38psi
Stage
2
will Energize
Light is ON
--------------------------------------------------
On a rise to
40psi
Stage
2
will Open
Light is OFF