background image

6

TSC/TSR OPERATION

Set Point 1

• Set Point 1 controls when Stage 1 is energized or open as

shown in the Example.

• TSC mode -  Stage 1 controls the Black output wires (see

pg. 3).

• TSR mode - For the first 12 hours of operation, Stage 1

controls the Black output wires.  For the next 24 hours,
Stage 1 controls the Red output wires.  Then the control
will switch back to Black and will switch again every 24
hours.

• To adjust Set Point 1, use the following steps:

1.  Digi-Span should be displaying sensor pressure.
2.   Press the center button and release it.  The display will

change to show 

SP1

.  Wait 2 seconds or press the 

UP

or 

DOWN 

button and the set point will be displayed.

3.   Press and hold either the 

UP

 or 

DOWN

 button until the

desired set point is displayed.

4.   Wait approximately 10 seconds.  If the set point was

changed, the display will flash.  Then the Digi-Span will
return to displaying the sensor pressure.  (If you don’t
want to wait 10 seconds, press the center button once
for Set Point 2, twice for Differential, three times for
Offset or four times to display sensor pressure.)

Set Point 2

• Set Point 2 controls when Stage 2 is energized or open as

shown in the Example.

• TSC mode -  Stage 2 controls the Red output wires (see pg.

3).

• TSR mode - For the first 12 hours of operation, Stage 2

controls the Red output wires.  For the next 24 hours, Stage
2 controls the Black output wires.  Then the control will
switch back to Red and will switch again every 24 hours.

• To adjust Set Point 2, use the following steps:

1.  Digi-Span should be displaying sensor pressure.
2.   Press the center button twice and release it.  The

display will change to show 

SP2

.  Wait 2 seconds or

press the 

UP

 or 

DOWN 

button and the set point will be

displayed.

3.   Press and hold either the 

UP

 or 

DOWN

 button until the

desired set point is displayed.

4.   Wait approximately 10 seconds.  If the set point was

changed, the display will flash.  Then the Digi-Span will
return to displaying the sensor pressure.  (If you don’t
want to wait 10 seconds, press the center button once
for Differential, twice for Offset or three times to display
sensor pressure.)

NOTE:  Set Point 1 does not need to be set above Set Point 2.

Either set point can be any value in the operational
range.  See page 3 to set either the Heating or the
Cooling mode.

SET POINT and DIFFERENTIAL EXAMPLE

Set Point 1

60psi

Set Point 2

50psi

Differential

 2psi

HEATING MODE

On a drop to 

58psi 

Stage

 1 

will Energize

Light will Flash

On a further drop to 

48psi

 Stage 

will Energize

Light is ON

--------------------------------------------------

On a rise to 

50psi

 Stage 

will Open

Light will flash

On a further rise to 

60psi

 Stage 

1

 will Open

Light is OFF

COOLING MODE

On a rise to 

50psi 

Stage

 2

 will Energize

Light will Flash

On a further rise to 

60psi 

Stage 

will Energize

Light is ON

--------------------------------------------------

On a drop to 

58psi

 Stage 

will Open

Light will flash

On a further drop to 

48psi 

Stage

 2 

will Open

Light is OFF

TSC

Stage 1 controls Black output wires
Stage 2 controls Red output wire

TSR

Outputs rotate 12 hours after initial powerup and
every 24 hours thereafter

Содержание Digi-Span TSC Pressure

Страница 1: ...nstallation or caused by power failures fire flood or lightning are not covered by this warranty The company assumes no liability for indirect or consequential damages of any nature This Heat Timer wa...

Страница 2: ...cer wires can also be connected to the back of the Digi Span using the Rear Wire connector Connect the BLACK sensor wire to yellow Rear Wire and the RED sensor wire to the orange Rear Wire Wiring the...

Страница 3: ...TSC TSR only If the display shows H then the Digi Span will be in a heating mode The relays will close when the pressure is below the set point see Example on pg 6 If the display shows C then the Digi...

Страница 4: ...2 is energized or open as shown in the Example When Output 2 is energized the Red output wires will be continuous When Output 2 is open the Red output wires will be open To adjust Set Point 2 use the...

Страница 5: ...e display will flash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice for the sensor pressure to b...

Страница 6: ...ed and will switch again every 24 hours To adjust Set Point 2 use the following steps 1 Digi Span should be displaying sensor pressure 2 Press the center button twice and release it The display will c...

Страница 7: ...ash Then the Digi Span will return to displaying the sensor pressure If you don t want to wait 10 seconds press the center button once for Offset or twice to display sensor pressure immediately Offset...

Страница 8: ...UTPUT Red Light does not indicate desired stages are active Check the set points and differential values In a heating application the stage will not come on until the pressure drops below the set poin...

Отзывы: