5
HWE-SS Elite Installation and Operation Manual
HEAT-TIMER CORP.
V1.00 c 2006
DIGI-SPAN ELITE
HWE-SS
Loading Default
Values...
DISPLAY UNIT:
F
C
SENSOR FAULT:
Output On
Output Off
SETUP COMPLETE!
PRESS SET
Startup Menu
SYSTEM=
68 F
TARGET=
150 F
------MAIN------
Set Point 150 F
<Out. Reset>
<Settings>
<Maintenance>
<Sys. Startup>
<Info>
<Back>
Set Point:
70 F
----SETTINGS----
Diff.
5 F
Run-On
2m
DHW Prior
60m
Setback
20 F
<Back>
Differential:
5 F
System Trim:
+0 F
SYSTEM STARTUP
No
Yes
HWE-SS V1.00
Setpoint F
FAULT: Output On
Operating Menu
Default Screen
Menus
SET
SET
SET
SET
SET
SET
Sensor Fault
Options:
Output On, Output Off
Default: Output On
SET
SET
SET
SET
SET
SET
/<System Startup>/..../Sensor Fault
• The Sensor Fault will determine the operating status of the output relays when a sensor reads Short
or Open. On sensor fault the Set Point will indicate
FAULT TGT=ON
or
OFF
to indicate the
condition of the output and the faulty sensor will read
OPEN
or
SHORT
to indicate the condition of
the sensor.
SENSOR FAULT:
Output On
Output Off
Set SYS Temp 1:
100 F
CONTROL MODE:
Outdoor Reset
Set Point
-OUTDOOR RESET--
Reset Ratio
7
Offset
+0 F
Cutoff
60 F
Min Tgt. 120 F
Max Tgt. 200 F
<Back>
Cutoff:
60 F
Reset Ratio O/S:
Custom
1(8.00 : 1.00)
2(4.00 : 1.00)
3(3.00 : 1.00)
4(2.00 : 1.00)
5(1.50 : 1.00)
6(1.25 : 1.00)
7(1.00 : 1.00)
8(1.00 : 1.25)
9(1.00 : 1.50)
10(1.00 : 2.00)
11(1.00 : 3.00)
12(1.00 : 4.00)
At OD Temp 1:
70 F
Set SYS Temp 2:
170 F
At OD Temp 2:
0 F
---MAINTENANCE---
Sys. Trim
+0 F
Out. Trim
+0 F
<Back>
Offset:
+0 F
Min Target:
120 F
Max Target:
200 F
Outdoor Trim:
+0 F
Pump Run-On:
2m
DHW Priority:
60m
Setback:
20 F
Boost:
No
Yes
Set Point
Reset