Determining the proper location for the Outdoor Sensor is very important.  The HWE-SS will base the heat on 

the outdoor temperature information it receives from this location.  If the sensor is in the sun, or covered with 

ice, its reading will be different from the actual Outdoor temperature (OD).

Wiring the Domestic Hot Water Call DHW (T3+, T3-)

•   DHW can be used to raise system Set Point to the lower of 200°F or Maximum Target temperature.

•   DHW Call terminals are dry contact N.O. terminals.

•   Wire an aquastat or another control to provide contact closure on the DHW Call terminals.

Wiring the Enable/Disable (EXT+, EXT-)

•   The EXT terminals can be used to enable or disable the system by connecting it to a thermostat, external control, 

or a switch.  It accepts dry contact input only.

•   If no thermostat or control is connected to the EXT terminals, leave the jumper supplied as a contact to the 

terminals.

•   No outputs will be active unless the EXT terminals are closed/shorted.

Wiring the Setback/Boost (P+, P-)

•   The Setback feature can be used to provide the HWE-SS with a lower temperature Set Point when less heat is 

required.

•   A typical use for Setback is to provide less system temperature to a building during the night or on the 

weekends when building is not occupied, but heat is still required.

•   The Setback is activated by closing/shorting the P+ and P- terminals using an external timer.

Button and Navigating Menus

The HWE-SS has three buttons.

•   The SET button function varies.  When the Default Screen is displayed, pressing the SET Button views the 

MENU.  When in the Menus and settings, the SET Button accepts the selected entry or setting value.

•   When in the menus, pressing the Up and Down buttons will scroll through the menu options.  They can be used 

to change the setting of a specific function.  i.e., change the Set Point, Differential, or System Trim.  In addition, 

when in the default screen, the Up and Down buttons will display the outdoor 

temperature and Outdoor Cutoff.

•   At the end of every operation menu there is a 

<Back>

 option that allows the 

user to go back one menu level.  If the SET Button was held down for three 

seconds on the 

<Back>

 option, the display will go back to the default screen.

Startup Options

When the control is initiated for the first time or after a manual reset, it will start its operation with the Startup Menu.  Later, the 

Startup menu can be accessed as an option from the operation menu.  An option must be accepted in each screen in the Startup Menu 

to move to the next level.

Display Unit

Options: 

º

F

º

C

 

Default: 

º

F

SET

SET

SET

SET

SET

SET

/<System Startup>/Display Unit

•   The HWE-SS will offer two different temperature displays.  If ºF is selected, all temperatures will 

display in Fahrenheit.  If ºC is selected, all temperatures will display in Celsius.

DISPLAY UNIT:

F
C

Control Mode

Options: 

Outdoor Reset, Set Point

 

Default: Outdoor Reset

SET

SET

SET

SET

SET

SET

/<System Startup>/Display Unit/Control Mode

•   The new HWE-SS have two heating logics.  Outdoor Reset; varies the system set point/target 

CONTROL MODE:

Outdoor Reset
Set Point

   based on outdoor temperature.  This selection will add several menu options, Reset Ratio, Offset, Min Water temp, Max Water temp, 

and Outdoor Cutoff, to allow of adjustment and fine tuning of the Reset Curve.  In addition, a customized curve will be available for 

specialized applications.

•   Set Point; Gives the installer the flexibility of selecting a fixed set point.  The Outdoor Cutoff will be available if an outdoor sensor 

was installed.

SET

SET

SET

SET

SET

SET

N.O.

S.P.S.T. Output Wiring

120VAC Power Wiring

120VAC Power Source

BLACK

BLACK

Boiler

Output Wiring

N.O.

YELLOW

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

24V

AC

Comm

24VAC Power Wiring

Shield

Shield

System T

emp

Outdoor Sensor

Sensor Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Enable/Disable

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Input Terminals

{

{

{

{

{

{

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

150°F - 950°F

Ex

ter

nal Enable/D

isable

Shut

do

wn

Pr

essur

e,

 V

acuum,

 and

4 -20mA

24V

A

C P

o

w

er Supply

N.O.

ORANGE

System Pump

Output Wiring

N.O.

VIOLET

DHW Pump

Output Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

DHW Call

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Setback/Boost

Wiring

N.O.

S.P.S.T. Output Wiring

120VAC Power Wiring

120VAC Power Source

BLACK

BLACK

Boiler

Output Wiring

N.O.

YELLOW

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

24V

AC

Comm

24VAC Power Wiring

Shield

Shield

System T

emp

Outdoor Sensor

Sensor Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Enable/Disable

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Input Terminals

{

{

{

{

{

{

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

150°F - 950°F

Ex

ter

nal Enable/D

isable

Shut

do

wn

Pr

essur

e,

 V

acuum,

 and

4 -20mA

24V

A

C P

o

w

er Supply

N.O.

ORANGE

System Pump

Output Wiring

N.O.

VIOLET

DHW Pump

Output Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

DHW Call

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Setback/Boost

Wiring

N.O.

S.P.S.T. Output Wiring

120VAC Power Wiring

120VAC Power Source

BLACK

BLACK

Boiler

Output Wiring

N.O.

YELLOW

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

24V

AC

Comm

24VAC Power Wiring

Shield

Shield

System T

emp

Outdoor Sensor

Sensor Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Enable/Disable

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Input Terminals

{

{

{

{

{

{

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

30°F - 250°F

Temp

er

atur

e S

ensor

150°F - 950°F

Ex

ter

nal Enable/D

isable

Shut

do

wn

Pr

essur

e,

 V

acuum,

 and

4 -20mA

24V

A

C P

o

w

er Supply

N.O.

ORANGE

System Pump

Output Wiring

N.O.

VIOLET

DHW Pump

Output Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

DHW Call

Wiring

T1

T2

T3+

COM

COM

T3- EXT+ EXT- P+ P- COM 24VAC

Setback/Boost

Wiring

Содержание Digi-Span Elite Series HWE-SS

Страница 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Страница 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Страница 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Страница 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Страница 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Страница 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Страница 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Страница 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Страница 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Страница 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Страница 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Страница 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...

Отзывы: