background image

7

 

HWE-SS Elite Installation and Operation Manual

•   If required:

 Adjust the RESET RATiO in cold weather.

  If the ambient building temperatures are too cold in cold weather, move 

the ratio to a higher selection.  That is, if 1.00 (OD):1.00 (SYS) was initially selected, change the selection to 1.00 (OD):1.25 (SYS).  

If the building temperatures are too warm in cold weather, move the ratio to a lower selection.  That is, if 1.00 (OD):1.00 (SYS) was 

initially selected, change the selection to 1.25 (OD):1.00 (SYS).

•   The Custom option gives the user the capability of creating a specialized Reset Ratio curve.  Setting two points on the Reset Ratio 

chart generates the customized curve.  Each point requires a System Water Temperature and an Outdoor Temperature.  The line 

connecting the two points will be the customized reset ratio.

•   Reset Ratios are adjustable based on the building and application. See suggested ratios on page 2.

Custom Outdoor Reset Curve

Options: 

Sys Temp 1, 2 (-10ºF/21ºC) to (210ºF/99ºC) Default: 1(100ºF/38ºC), 2(171ºF/77ºC)

Options: 

Outdoor Temp 1, 2 (-10ºF/-23ºC) to (100ºF/38ºC) Default: 1(70ºF/21ºC), 2(0ºF/-18ºC)

SET

SET

SET

SET

SET

SET

/<Out. Reset>/Reset Ratio/Custom

•   For situations where the provided reset ratios do not provide the perfect building heat-loss 

equilibrium, the customized option can be used.

•   The Custom Reset Ratio is only available when 

Custom

 is selected from the Reset Ratio menu 

option.  It provides the user with the capability of assigning two points on the reset ratio diagram 

and use the line that connects those two points as the customized reset ratio curve.  Each of the two 

points will need a specific System and Outdoor Temperature to identify it on the diagram.

•   To Set the first point, specify Sys Temp 1, and OD Temp 1.  Then, specify Sys Temp 2, and OD 

Temp 2, to set the second point on the curve.  The two points can be any where on the line, not 

necessarily at the ends.

•   The chart shows an example of a customized curve 6(OD):5(SYS) that do not exist in the standard 

curve options.  If the outdoor temperature reaches 30ºF, the system target will be 145ºF.

•   Remember that the Min Target and Max Target apply to all reset ratios including the customized 

reset ratio ones.

Set SYS Temp 1:

100 F

At OD Temp 1:

70 F

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater 

Temperature (in °F)

Custom Reset Ratio

Point1: System=120°F

Oudoor=60°F

Point2: System=170°F

Oudoor=0°F

Point1

Point2

Customized Reset Ratio

Max Target

Min Target

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater 

Temperature (in °F)

Target Offset

Offset=10°F

Reset Ratio=1.5 : 1.0

Reset Ratio

Max Target

Min Target

Reset Ratio + 10F Offset

Min Target=120°F

Max Target=170°F

Offset (Available when Startup Control Mode = Outdoor Reset)

Options: 

From -40ºF/-22

º

C to +40ºF/+22

º

 

Default: 0

º

F/0

º

C

SET

SET

SET

SET

SET

SET

/<Out. Reset>/Offset

Offset:

+0 F

•   The Offset setting lets you adjust the starting points of the Reset Ratio curves.  This means that, 

regardless of the Outdoor temperature (OD), or the Reset Ratio that has been selected, when 

the Offset setting is changed, that change is directly added to or subtracted from the calculated 

temperature/Target.  For example, if the Set Point temperature was 130°F and the Offset was 

changed from 0° to +10°, then the Set Point temperature would increase to 140°F

•   If required: 

Adjust the Water Offset in mild weather

.  If the ambient building temperatures 

are too warm in the mild weather, decrease the Offset.  If the ambient building temperatures are 

too cold in the mild weather, increase the Offset.  The rule of thumb for baseboard radiation is 

to change the Offset 4°F for every 1°F you wish to change the building temperatures.  In radiant 

heat applications, change the Offset 1°F or 2°F for every 1°F you wish to change the building 

temperature. 

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater 

Temperature (in °F)

Custom Reset Ratio

Point1: System=120°F

Oudoor=60°F

Point2: System=170°F

Oudoor=0°F

Point1

Point2

Customized Reset Ratio

Max Target

Min Target

Outdoor Temperature (in °F)

70 60 50 40

20

30

0

-10

10

-20

120

140

130

150

160

170

180

100

110

W

ater 

Temperature (in °F)

Target Offset

Offset=10°F

Reset Ratio=1.5 : 1.0

Reset Ratio

Max Target

Min Target

Reset Ratio + 10F Offset

Min Target=120°F

Max Target=170°F

Outdoor Cutoff

Options: 

 Off, 20ºF/-6ºC to 100

º

F/38

º

C, On 

Default: 65ºF/18ºF

SET

SET

SET

SET

SET

SET

/Set Point/Cutoff

 

in Set Point

SET

SET

SET

SET

SET

SET

/Set Point/<Out. Reset>/Cutoff

 

in Reset

•   In Set Point, if the outdoor sensor is installed, the Outdoor Cutoff setting screen will automatically 

appear after the temperature Set Point has been selected.

Cutoff:

 60 F

•   The Outdoor and Cutoff temperatures can be viewed from the default screen by clicking the Up or Down buttons.

•   When the outdoor temperature falls to the adjustable Outdoor Cutoff temperature, the HWE-SS will control the System Pump and 

Boiler relays to provide heat.

•   When the outdoor temperature rises to the Outdoor Cutoff plus a 2°F differential, the HWE-SS will turn the boiler off.  The System 

relay will remain energized for the Run-On delay then de-energize.  

•   The Outdoor Cutoff can be set from 20°F to 100°F.  In addition, the Setting can be set to ON or OFF.  If ON is selected, the System 

Relay will run regardless of the Outdoor temperature (OD) and the boiler will be active to hold the calculated water temperature.  If 

OFF is selected, the System and Boiler relays will always be off.

Содержание Digi-Span Elite Series HWE-SS

Страница 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Страница 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Страница 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Страница 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Страница 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Страница 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Страница 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Страница 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Страница 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Страница 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Страница 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Страница 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...

Отзывы: