background image

8

Minimum Target 

(Available when Startup Control Mode = Outdoor Reset)

Options: 

 From 70

º

F/21

ºC

 to 180

º

F/77

ºC

  

Default: 70

º

F/27

ºC

SET

SET

SET

SET

SET

SET

/Set Point/<Out. Reset>/Min. Tgt

Min Target:

120 F

•   The Minimum Target Temperature must be set to the boiler manufacturer’s specification.  The HWE-SS will calculate the Target 

based on the Outdoor temperature (OD), the Reset Ratio, and the Offset value.  The HWE-SS will control the boiler to hold either 

the calculated temperature or the Minimum Target Temperature whichever is higher.

•   The Minimum Target Temperature must be at least 20°F lower than the Maximum Temperature (See next setting).

Maximum Target

(Available when Startup Control Mode = Outdoor Reset)

Options: 

 From 90

º

F/38

ºC

 to 240

º

F/116

ºC

  

Default: 240

º

F/116

ºC

SET

SET

SET

SET

SET

SET

/Set Point/<Out. Reset>/Max. Tgt

Max Target:

200 F

•   This is the highest temperature heating water the HWE-SS will circulate through the heating system.  It 

must be at least 20°F higher 

than the Minimum Temperature.

•   When using a radiation system, it should be set according to the tubing or floor manufacturer’s specification.

Differential

Options: 

 From 1

º

F/1

ºC

 to 20

º

F/11

ºC

  

Default: 5

º

F/3

ºC

SET

SET

SET

SET

SET

SET

/Settings>/Diff.

Differential:

 5 F

•   The Differential controls boiler cycling. When there is a call for heat, the boiler will be activated until the Calculated temperature is 

reached. The boiler will then turn off and stay off until the system water temperature falls to the Set Point less the Differential.

•   A smaller Differential setting will normally result in tighter control of the set point but will tend to increase the frequency of boiler 

cycling.  Larger Differential values will reduce boiler short cycling, but the system will be allowed to vary further from the target 

value.

Run-On

Options: 

 From 0 min to 60 min  

Default: 2 min

SET

SET

SET

SET

SET

SET

/Settings>/Run On

•   The SYS relay will energize whenever the Outdoor temperature is below the Outdoor Cutoff.  

When the Outdoor temperature increases 2°F above the Outdoor Cutoff and after the boiler relay 

has de-energized, the SYS relay will stay on for a period set by the System Run-On.  This allows 

the Pump to dissipate the residual heat within the boilers back into the system.

•   A common use for the System Run-On is to provide extra time for the for the Pump to help transfer 

the heat from the boilers to the heating system.

Pump Run-On:
2m

•   The System Run-On time should be set based on the size and type of the boilers and pumps.  In general, a boiler with large water 

content and high horsepower will need a longer System Run-On than a boiler with the same horsepower and less water content.  

(Refer to boiler manufacturer recommendation).

•   When DHW Priority is active while the TSTAT is open or the outdoor temperature is above the Outdoor Cutoff, a DHW call will 

energize only the DHW relay.  When the DHW call expires, the DHW will run for the Run-On period then de-energize.

Domestic Hot Water (DHW) Priority

Options: 

 NO and From 1 min to 120 min  

Default: NO

SET

SET

SET

SET

SET

SET

/Settings>/DHW Prior.

DHW Priority:
60m

•   If the DHW Priority value was set to other than NO, it will provide the user with an adjustable DHW priority timer.  That is, when 

a DHW call starts, by closing/shorting the 

T3±

 terminals, the system relay will de-energize for the period set by the DHW Priority.  

However, the DHW relay will remain energized for as long as the DHW call is active.  The System relay will resume its operation 

when the DHW timer expires or if the DHW call ends.  This will take place whenever the outdoor temperature is below Outdoor 

Cutoff and the TSTAT terminals are closed/shorted.

•   If NO was selected as the option for the DHW Priority, a DHW call will energize both relays, System and DHW even when TSTAT 

is de-activated.

Setback

Options: 

 From 0

º

F/0

ºC

 to 80

º

F/44

ºC

  

Default: 11

º

F/6

ºC

SET

SET

SET

SET

SET

SET

/Settings>/Setback.

•   The Setback feature can be used to provide the HWE-SS with a lower temperature Set Point when 

less load is required.

•   The lower Set Point will appear on the main display indicating  

SBC TGT=

 .

Setback:

20 F

SYSTEM= 

68 F

SBC TGT= 

140 F

Содержание Digi-Span Elite Series HWE-SS

Страница 1: ...ydronic Heating Applications The HWE Single Stage HWE SS DIGI SPAN Elite establishes ambient comfort by varying the temperature of the heating system s circulating hot water in response to changes in...

Страница 2: ...HW tank to be satisfied quickly Mounting the Controller The HWE SS DIGI Elite is designed to mount on a 1900 4 x4 deep electrical box If additional room is needed for wiring use the extension skirt pr...

Страница 3: ...M The Outdoor Sensor must be used when Outdoor Reset is selected as the Control Mode from the Startup menu However in Set Point mode the Outdoor Sensor is optional When connected in that mode it will...

Страница 4: ...to the next level Display Unit Options F C Default F SET System Startup Display Unit The HWE SS will offer two different temperature displays If F is selected all temperatures will display in Fahrenh...

Страница 5: ...etermine the operating status of the output relays when a sensor reads Short or Open On sensor fault the Set Point will indicate FAULT TGT ON or OFF to indicate the condition of the output and the fau...

Страница 6: ...nu Options Click SET Button SYSTEM 148 F TARGET 150 F SET SET SET SET SET S SET SET SET SET SET S Outdoor 48 F Cutoff 65 F Set Point Available when Startup Control Mode Set Point Options From 10 F 23...

Страница 7: ...Reset Ratio Max Target Min Target Reset Ratio 10F Offset Min Target 120 F Max Target 170 F Offset Available when Startup Control Mode Outdoor Reset Options From 40 F 22 C to 40 F 22 C Default 0 F 0 C...

Страница 8: ...or temperature increases 2 F above the Outdoor Cutoff and after the boiler relay has de energized the SYS relay will stay on for a period set by the System Run On This allows the Pump to dissipate the...

Страница 9: ...existing system The System and Outdoor Trim values adjust the System Sensor and Outdoor Sensor readings using positive or negative values System Trim 0 F Outdoor Trim 0 F Enable Disable Input The HWE...

Страница 10: ...temperature is below the Target water temperature minus the Differential If not wait until the System temperature falls and then the stage LED should come on and the boiler should fire Otherwise remov...

Страница 11: ...ED WITH 24VAC T1 T2 COM COM T3 T3 EXT EXT P P COM 24VAC System Sensor Outdoor Sensor DHW Call Enable Dry Contact Setback Timer Boiler SYS Pump DHW Pump SET C O R P O R A T I O N R SYSTEM 147F TARGET 1...

Страница 12: ...P 6Amp resistive at 120 VAC 60 Hz Control Modes Outdoor Reset Set Point Reset Ratios 12 Standard ranging from 8 1 to 1 4 Outdoor System and one Custom Offset from 40 F 22 C to 40 F 22 C Minimum Water...

Отзывы: