All roof-chimney terminations should be able
to be readily removed / re-installed at or
below an elevation of 13-1/2 feet (4.1 m)
above ground level without the use of special
tools or instructions. The chimney assembly
shall be provided with a mechanical
securement means to secure the chimney to
the ceiling support box.
•
When a chimney exits the mobile home at a
location other than through the roof, and
exits at a point 7 feet (2.1 m) or less above the
ground level on which the mobile home is
positioned, a guard or method of enclosing
the chimney shall be provided at the point of
exit for a height up to 7 feet.
•
The chimney guard shall not allow the
passage of a ¾ inch (19.1 mm) diameter rod,
and a ½” (12.7 mm) diameter rod shall not be
able to touch the chimney when inserted
through any part of the guard a distance of 4
inches (102 mm).
•
The chimney shall be provided with a spark
arrester secured to the chimney. The net free
area of the arrester above the chimney outlet
shall not be less than 4 times the net area of
the chimney outlet, and the vertical height of
the arrester above the chimney outlet shall
not be less than ½ the diameter of the
chimney flue. Openings shall not permit the
passage of a sphere having a diameter of ½
inch (12.7 mm), and shall allow the passage
of a sphere of 3/8” (9.6 mm).
•
Be sure to follow the manufacturer’s
instructions to maintain an effective vapor
barrier at the location where the chimney of
other component penetrates the exterior of
the structure.
•
CAUTION: REMOVE THE CHIMNEY
WHEN TRANSPORTING THE MOBILE
HOME!