Hearthstone Quality Home Heating Products, Inc
®
Bari Model 8171
29
Figure 5: Chimney Height & Roof Clearance Requirements
I
NSTALLING
I
N
A
M
OBILE
H
OME
Follow these special requirements for installing your
stove in a mobile home.
THIS UNIT IS NOT APPROVED FOR MOBILE
HOME INSTALLATION TO CANADIAN
STANDARDS.
Install the stove in accordance with 24 CFR, Part
3280 (HUD)
•
Permanently attach the stove to your mobile
home’s floor. Use Hearthstone’s Kit #91-99400
- Mobile Home Lock Down Kit.
•
An outside air kit must be used in all mobile
home installations. A 4” fresh air intake is
required for mobile home installation. Kit # 90-
53308. See page 13 for more details.
•
Install one of the following Dura-Vent Mobile
Home Chimney & Connector Kits:
6DP-MH 6” Diameter S/N 9096N
7DP-MH 7” Diameter S/N 9196N
8DP-MH 8” Diameter S/N 9296N
Each kit includes:
Stainless spark arrester cap, storm collar,
Adjustable vented flashing – 0/12 – 6/12,
Two 24” Dura/Plus* chimney pipes, 24”
Support box with built-in starter section
and trim.
* (UL or ULC approved equipment is acceptable)
•
WARNING: DO NOT INSTALL IN A SLEEPING
ROOM IN A MOBILE HOME.
•
CAUTION: MAINTAIN THE STRUCTURAL
INTEGRITY OF THE MOBILE HOME WALLS,
FLOOR, CEILING, AND ROOF WHEN
INSTALLING AND USING YOUR STOVE
.
•
CAUTION: REMOVE THE CHIMNEY WHEN
TRANSPORTING THE MOBILE HOME!
•
FAILURE TO FOLLOW THESE INSTRUCTIONS
AND SPECIFIED COMPONENTS OR USING
MAKE-SHIFT COMPROMISES CAN RESULT IN
FIRE, PROPERTY DAMAGE, BODILY INJURY,
AND EVEN DEATH.
•
BURNING ANY FUEL OTHER THAN WOOD IN
THIS UNIT COULD GENERATE DANGEROUS
LEVELS OF CARBON MONOXIDE WITHIN THE
LIVING SPACE.
•
THE FRONT DOOR MUST REMAIN CLOSED
WHEN IN OPERATION EXCEPT FOR START UP
AND LOADING.
Leaving the door open during
use could cause any smoke or fire detectors in
the home to be set off or a fire could escape the
firebox and start the room on fire
.
•
If this unit is installed in a mobile home, care
must be taken to ensure adequate air is
available. If not enough air is available it
could starve the room of all the oxygen. (See
page 29 for more details)
•
The chimney should be attached directly to
the stove and must extend at least 3 feet (.9
m) above the part of the roof through which
it passes. The top of the chimney is to be at
least 2 feet (.6 m) above the highest elevation
of any part of the mobile home within 10 feet
(3 m) of the chimney.
3'-0"
MINIMUM
10'-0"
2'-0"
MINIMUM
3'-0"
MINIMUM
2'-0"
MINIMUM