background image

March 19, 2003                                                                        8                        

 

 

 

    250-6422

                                                                                           

Castile Pellet Stove

R

Part 811-0890, 3"-3" Top Vent Adapter    or    Part 812-3570, 3"-6" Top Vent Offset Adapter      

1)     Put  a  layer  of  silicone  on  the  3"  (76mcm)  exhaust 

outlet.

2)     Slide  the Top Vent  Adapter  onto  the  rear  exhaust 

outlet.

3)     Adjust the assembly to a vertical position.

4)     Drill four holes with #26 drill bit (provided) into the back 

of the stove using the outer shield as a pattern (make 

sure the assembly is vertical).

5)     Install the four mounting screws.

6)     Drill  two  holes  with  #26  drill  bit  through  the  Rear 

Exhaust Outlet using the two holes already in the short 

horizontal  pipe  in  the Top Vent  Adapter  as  a  guide.  

Install the two screws.

7)     Install the stove pipe into the Top Vent Adapter (be sure 

to silicone all joints).

8)     To clean Top Vent Adapter, remove clean out cover.

NOTES:

 

1.  The Feed Adjustment Rod is factory set, and should be 

adequate for most fuels.  However, if the flame height is 

too high or too low, follow the instructions below.

2.   Loosen  the  set  screw  (Fig  8A)  1/4  to  1/2  turn  during 

set-up  of  stove.   This  will  allow  movement  of  the  Fuel 

Adjustment Rod.  Do not re-tighten set screw.

3.   Adjust  Fuel  Adjustment  Rod  after  the  stove  has  been 

burning  for  10-15  minutes. The  flames  should  be 

TOP VENT FLUE ADAPTER INSTALLATION

FEED ADJUSTMENT

Set Screw

Wing Nut

Fuel Adjustment 

Rod

FIGURE  8A

FIGURE 8B

approximately  4"  (102mm)  above  the  firepot  at  high 

heat output setting.

a.

Loosen the wing nut

b. Adjust  the  Fuel  Adjustment  Rod  upward  towards 

the    "+"    symbol  to  increase  the  feed  rate  and 

flame height or down towards the  "-"  symbol, to 

decrease the feed rate and flame height.

c. Re-tighten the wing nut.

Rear Exhaust Outlet

Top Vent Adapter

Mount with four screws

Use hole on each side as 

drilling guide

Содержание QUADRA-FIRE

Страница 1: ...OVERFIRING VOIDS WARRANTY 5 DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM DO NOT INSTALL A FLUE DAMPER IN THE EXHAUSE VE...

Страница 2: ...inserts and fireplaces And yet we are old fashioned when it comes to craftsmanship Each unit is meticulously fabricated and gold surfaces are hand finished for lasting beauty and enjoyment Our pledge...

Страница 3: ...Chimney and Exhaust Connections 5 Venting Termination Requirements 5 Vent Graph and Table 5 Venting Systems A Alcove 6 B Through the wall 6 C Vertical 7 D Through the wall and vertical 7 E Masonry 7 F...

Страница 4: ...and to the sides front and back of unit as shown in Floor Protection Diagram Measure front distance I from the surface of the glass door Exceptions US INSTALLATIONS Recommend a non combustible floor...

Страница 5: ...shielding or guards may be required 3 Termination must exhaust above air inlet elevation It is recommended that at least 60 1524mm of vertical pipe be installed when appliance is vented directly thro...

Страница 6: ...5 Degree VENTING SYSTEMS Straight Out A ALCOVE The Quadra Fire Castile is approved for minimum alcove height of 43 1092mm a maximum alcove depth of 36 914mm and a minimum alcove side wall of 6 152mm A...

Страница 7: ...Cap Flashing 2 51mm minimum 6 152mm minimum VENTING SYSTEMS CONT C VERTICAL D THROUGH THE WALL VERTICAL E MASONRY F ALTERNATE MASONRY Non combustible Hearth Pad Airtight Cleanout Door Cleanout cover S...

Страница 8: ...nt Adapter remove clean out cover NOTES 1 The Feed Adjustment Rod is factory set and should be adequate for most fuels However if the flame height is too high or too low follow the instructions below...

Страница 9: ...ZE AND MATERIAL Wood Pellets Fuel pellets are made from sawdust or wood by products If the source material is hardwood they will have a higher mineral content creating a heavier ash Minerals and other...

Страница 10: ...es in that when the thermostat calls for heat your stove will automatically light and deliver heat in the most efficient and economical way When the room is up to temperature and the thermostat is sat...

Страница 11: ...ppermost portion of the Heat Exchanger Tubes This area is only accessible when the baffle is removed from the stove Reinstall panels and baffle and latch when finished cleaning NOTE Unplug the stove b...

Страница 12: ...this removed the blower and housing may now be removed There are four screws that attach the blower housing Two on each side Loosen all four screws but do not remove them Now lift the blower housing...

Страница 13: ...s to indicate that the stove has reached operating temperature If the red light does not come on in the first nine minutes of start up the stove will shut 1 POWER SUPPLY a Check the wall receptacle fo...

Страница 14: ...surges can also trip this Snap Disc To reset unplug the stove from outlet and push in the Red Reset Button in the center of the Snap Disc then plug the stove back in and try to relight it 13 BLOWER 1...

Страница 15: ...sure that the floor of the firepot is closing completely 18 DOOR GASKET ROPE a To inspect the door gasket rope open the door and see that the door rope extends approximately 1 8 3mm to 3 16 9 5mm fro...

Страница 16: ...ews 5 Measure distance from floor to air vent opening in stove and mark location on wall Use saw to cut opening in wall Cut a 2 1 2 to 3 64mm to 76mm opening on inside wall and a 3 to 3 1 2 76mm to 89...

Страница 17: ...he top baffle and the inside of the firebox cen tered from side to side The latch pivots up and down 2 Push the latch up with your finger while sliding the top baffle forward and down See Figure 17A 3...

Страница 18: ...he Thermocouple and the Thermocouple Cover should extend approximately 1 25mm into the firepot for accurate temperature reading 3 Push the Reset Button When the Thermocouple reaches 200 F 93 C the TRO...

Страница 19: ...jumper wire in order to create a manual bypass to determine if the stove or the thermostat is faulty NOTE Unplug the stove while hooking up the jumper wire Plug the stove back in and the unit should...

Страница 20: ...AUGER MOTOR BLUE COMB BLOWER WHITE NEUTRAL IN NEUTRAL AUGER NEUTRAL CONV NEUTRAL COMB NEUTRAL IGN HT M RED WHT SNAP DISC 1 M IGNITER HT M BURN RATE LIGHT P B FUSE AUG CAP ORANGE BLUE GRAY BLACK YELLOW...

Страница 21: ...ot scraper paint fasteners power cord wire harness thermostat igniter owner s manual video and warranty card 812 4940 Control Box 812 4890 Door Assembly with Glass 812 4421 Feed Motor 812 4430 Firepot...

Страница 22: ...llet Stove R 3 4 5 6 2 1 7 8 9 10 11 12 1 Control Box 2 Convection Blower 3 Exhaust Blower 4 Feed Motor 5 Firepot 6 Glass Door Assembly EXPLODED VIEW 7 Igniter 8 Junction Box 9 Snap Disc 1 10 Snap Dis...

Страница 23: ...essories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of...

Страница 24: ...March 19 2003 250 6422 24 PLEASE RETURN THESE INSTRUCTIONS TO THE HOME OWNER WHEN INSTALLATION IS COMPLETE ATTENTION INSTALLER R...

Отзывы: