CASTILE PELLET STOVE

INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS

250-6422 

March 19, 2003

Please read this entire manual before installation and use of this pellet fuel and shelled field corn room heater.

Failure to follow these instructions could result in property damage, bodily injury or even death.

O-T L

Tested and 

Listed by

Beaverton

Oregon USA

OMNI-Test Laboratories, Inc.

C

IMPORTANT! Record serial number of your stove on the warranty card and mail immediately.  The 

serial number is located inside the hopper on the left side.

IMPORTANT SAFETY NOTES

1.     When installing your stove, particular attention should be paid to fire protection.  If this unit is not properly installed, a house 

fire may result.  For your safety, follow the installation instructions.  

CONTACT LOCAL BUILDING OR FIRE OFFICIALS 

ABOUT RESTRICTIONS AND INSTALLATION INSPECTION REQUIRED IN YOUR AREA.

2.     Read power supply section of component information (page 14) before you plug in the stove.
3.     Always unplug the stove before cleaning or servicing.
4.     During operation, if any part of the stove starts to glow, the stove is in an overfired condition.  Reduce the feed rate and 

increase the amount of air going into the stove.  

OVERFIRING VOIDS WARRANTY.

5.     DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT.  DO NOT CONNECT TO ANY 

AIR DISTRIBUTION DUCT OR SYSTEM.  DO NOT INSTALL A FLUE DAMPER IN THE EXHAUSE VENTING SYSTEM 
OF THIS UNIT.

6.     Do not connect the stove to a chimney flue already serving another appliance.
7.     DO NOT BURN GARBAGE OR FLAMMABLE FLUIDS SUCH AS GASOLINE, NAPTHA OR ENGINE OIL.  Never use 

gasoline, gasoline-type lantern fuel, kerosene, charcoal lighter fluid, or similar liquids to start or freshen up a fire in this heater.  
Keep all such liquids well away from the heater while it is in use.

8.     The stove operates with a negative pressure firebox and a positive pressure exhaust.  It is imperative that the chimney 

system be airtight and installed correctly.

9.     Dispose of all ashes in a metal container.
10.   Comply with all minimum clearances to combustibles as shown on page 5.
11.   HOT WHILE IN OPERATION.  Keep children, clothing and furniture away.  Contact may cause skin burns. 
11.   The Quadra-Fire Castile is tested and approved for pelleted biomass and shelled field corn fuel only.  Burning of any other 

type of fuel voids your warranty!

12.   Hearth & Home Technologies, manufacturer of the Castile pellet stove, reserves the right to alter its products, their 

specifications and/or price without notice.

13.   

HEARTH & HOME TECHNOLOGIES GRANTS NO WARRANTY, IMPLIED OR STATED, FOR THE INSTALLATION OR 
MAINTENANCE OF THIS UNIT AND ASSUMES NO RESPONSIBILITY FOR ANY CONSEQUENTIAL DAMAGE(S).

Содержание QUADRA-FIRE

Страница 1: ...OVERFIRING VOIDS WARRANTY 5 DO NOT INSTALL A FLUE DAMPER IN THE EXHAUST VENTING SYSTEM OF THIS UNIT DO NOT CONNECT TO ANY AIR DISTRIBUTION DUCT OR SYSTEM DO NOT INSTALL A FLUE DAMPER IN THE EXHAUSE VE...

Страница 2: ...inserts and fireplaces And yet we are old fashioned when it comes to craftsmanship Each unit is meticulously fabricated and gold surfaces are hand finished for lasting beauty and enjoyment Our pledge...

Страница 3: ...Chimney and Exhaust Connections 5 Venting Termination Requirements 5 Vent Graph and Table 5 Venting Systems A Alcove 6 B Through the wall 6 C Vertical 7 D Through the wall and vertical 7 E Masonry 7 F...

Страница 4: ...and to the sides front and back of unit as shown in Floor Protection Diagram Measure front distance I from the surface of the glass door Exceptions US INSTALLATIONS Recommend a non combustible floor...

Страница 5: ...shielding or guards may be required 3 Termination must exhaust above air inlet elevation It is recommended that at least 60 1524mm of vertical pipe be installed when appliance is vented directly thro...

Страница 6: ...5 Degree VENTING SYSTEMS Straight Out A ALCOVE The Quadra Fire Castile is approved for minimum alcove height of 43 1092mm a maximum alcove depth of 36 914mm and a minimum alcove side wall of 6 152mm A...

Страница 7: ...Cap Flashing 2 51mm minimum 6 152mm minimum VENTING SYSTEMS CONT C VERTICAL D THROUGH THE WALL VERTICAL E MASONRY F ALTERNATE MASONRY Non combustible Hearth Pad Airtight Cleanout Door Cleanout cover S...

Страница 8: ...nt Adapter remove clean out cover NOTES 1 The Feed Adjustment Rod is factory set and should be adequate for most fuels However if the flame height is too high or too low follow the instructions below...

Страница 9: ...ZE AND MATERIAL Wood Pellets Fuel pellets are made from sawdust or wood by products If the source material is hardwood they will have a higher mineral content creating a heavier ash Minerals and other...

Страница 10: ...es in that when the thermostat calls for heat your stove will automatically light and deliver heat in the most efficient and economical way When the room is up to temperature and the thermostat is sat...

Страница 11: ...ppermost portion of the Heat Exchanger Tubes This area is only accessible when the baffle is removed from the stove Reinstall panels and baffle and latch when finished cleaning NOTE Unplug the stove b...

Страница 12: ...this removed the blower and housing may now be removed There are four screws that attach the blower housing Two on each side Loosen all four screws but do not remove them Now lift the blower housing...

Страница 13: ...s to indicate that the stove has reached operating temperature If the red light does not come on in the first nine minutes of start up the stove will shut 1 POWER SUPPLY a Check the wall receptacle fo...

Страница 14: ...surges can also trip this Snap Disc To reset unplug the stove from outlet and push in the Red Reset Button in the center of the Snap Disc then plug the stove back in and try to relight it 13 BLOWER 1...

Страница 15: ...sure that the floor of the firepot is closing completely 18 DOOR GASKET ROPE a To inspect the door gasket rope open the door and see that the door rope extends approximately 1 8 3mm to 3 16 9 5mm fro...

Страница 16: ...ews 5 Measure distance from floor to air vent opening in stove and mark location on wall Use saw to cut opening in wall Cut a 2 1 2 to 3 64mm to 76mm opening on inside wall and a 3 to 3 1 2 76mm to 89...

Страница 17: ...he top baffle and the inside of the firebox cen tered from side to side The latch pivots up and down 2 Push the latch up with your finger while sliding the top baffle forward and down See Figure 17A 3...

Страница 18: ...he Thermocouple and the Thermocouple Cover should extend approximately 1 25mm into the firepot for accurate temperature reading 3 Push the Reset Button When the Thermocouple reaches 200 F 93 C the TRO...

Страница 19: ...jumper wire in order to create a manual bypass to determine if the stove or the thermostat is faulty NOTE Unplug the stove while hooking up the jumper wire Plug the stove back in and the unit should...

Страница 20: ...AUGER MOTOR BLUE COMB BLOWER WHITE NEUTRAL IN NEUTRAL AUGER NEUTRAL CONV NEUTRAL COMB NEUTRAL IGN HT M RED WHT SNAP DISC 1 M IGNITER HT M BURN RATE LIGHT P B FUSE AUG CAP ORANGE BLUE GRAY BLACK YELLOW...

Страница 21: ...ot scraper paint fasteners power cord wire harness thermostat igniter owner s manual video and warranty card 812 4940 Control Box 812 4890 Door Assembly with Glass 812 4421 Feed Motor 812 4430 Firepot...

Страница 22: ...llet Stove R 3 4 5 6 2 1 7 8 9 10 11 12 1 Control Box 2 Convection Blower 3 Exhaust Blower 4 Feed Motor 5 Firepot 6 Glass Door Assembly EXPLODED VIEW 7 Igniter 8 Junction Box 9 Snap Disc 1 10 Snap Dis...

Страница 23: ...essories Adjustments regular maintenance cleaning and temporary repairs do not qualify for a service call fee and will not be covered The replacement of consumer replaceable items and installation of...

Страница 24: ...March 19 2003 250 6422 24 PLEASE RETURN THESE INSTRUCTIONS TO THE HOME OWNER WHEN INSTALLATION IS COMPLETE ATTENTION INSTALLER R...

Отзывы: