4

Two Speed Filter Pump:

  If the pump is currently off, simply press the “FILTER” button to turn on high speed

operation of the filter pump.  The “Filter” LED will illuminate continuously.  Pressing the “FILTER” button again will

switch to low speed operation and the “FILTER” LED will flash. Note that if the pump has been off for more than

30 seconds, it will run at high speed for 3 minutes regardless of selection.  This high speed operation helps allow the

pump to prime and establish normal water flow.

Variable Speed Filter Pump: 

If the pump is currently off, press the “FILTER” button to turn the filter pump on to

the last speed (1, 2, 3, or 4) that was used. A temporary display is generated indicating the current speed selection

(Filter On:Spd 1). Pushing the “+” or “-” button changes the speed selection. If the pump has been off for more

than 30 seconds, it will run at the highest speed for 3 minutes regardless of selection. This high speed operation

helps allow the pump to prime and establish normal water flow.

Freeze Protection:

  This function protects the pool, plumbing, and equipment against freeze damage.  If Freeze

Protection is enabled and the AIR temperature sensor falls below the preset freeze protection temperature (see

Filter Configuration), the Aqua Plus 16v will turn on the filter pump to circulate the water.

Spa Filter Pump (when using Dual Equipment)

Single Speed Filter Pump:

  If the pump is currently off, press the “AUX1” button to turn on the pump.  Pressing

the “AUX1” button again will turn off the pump.  However, if there is a heater in the system, and it is operating, and

the “Heater Cooldown” feature is enabled (Configuration Menu) then:  when you press the “AUX1” button to turn

off the filter, only the heater will turn off, the Filter LED will flash and the display will indicate “Heater Cooldown”.

At this point the filter pump will automatically turn off after 5 minutes of heater cooldown operation.  If you want to

override the heater cooldown, simply press the “AUX1” button again to turn off the filter pump.

Two Speed Spa Filter Pump:

  If the pump is currently off, simply press the “AUX1” button to turn on high speed

operation of the filter pump.  The “AUX1” LED will illuminate continuously.  Pressing the “AUX1” button again will

switch to low speed operation and the “AUX1” LED will flash.  Note that if the pump has been off for more than

30 seconds, it will run at high speed for 3 minutes regardless of selection.  This high speed operation helps allow the

pump to prime and establish normal water flow.

Variable Speed Filter Pump: 

If the pump is currently off, press the “AUX1” button to turn the filter pump on to

the last speed (1 or 2) that was used. A temporary display is generated indicating the current speed selection (Filter

On:Spd 1). Pushing the “+” or “-” button changes the speed selection.  If the pump has been off for more than 30

seconds, it will run at the highest speed for 3 minutes regardless of selection. This high speed operation helps allow

the pump to prime and establish normal water flow.

Freeze Protection:

  This function protects the pool, plumbing, and equipment against freeze damage.  If Freeze

Protection is enabled and the AIR temperature sensor falls below the preset freeze protection temperature, the

Aqua Plus 16v will turn on the spa filter pump to circulate the water.

Lights and Aux Outputs

Standard Relay:

 Manual operation of all relays (LIGHTS,  AUX1 - AUX6) is identical.  Assuming that the relay

is currently off, simply press the appropriate button to turn on the relay.  If the relay does not turn on, it probably is

due to the “interlock” feature (which was set up in the Configuration Menu) being activated that requires the filter

pump to be running and the valves to be in the pool-only position.  This protects pumps and other equipment from

possible damage.  If the controlled output is on, pressing the appropriate button again will turn off the relay.

Manual turn off is disabled if the “Freeze Protection” feature is enabled and the air temperature is less than the

selected freeze temperature threshold.

Dimmer Relay

: If Lights or an Aux output is configured as a dimmer, pressing the corresponding button will

generate a temporary display which shows the dimmer output level (Off - On 100%).  Pushing the “+” or “-”

button changes the level in increments of 20%.  When the desired output level is displayed, press the correspond-

ing button again to turn off the display and return to normal operation.  When the Lights or Aux output comes on

again (either manually or automatically), the dimmer output level will be the same as the last time that it was set.

ColorLogic Relay

:  This selection will only appear if an optional ColorLogic Network Module (AQL-COLOR-

MODHV) is detected at startup.  The Network Module allows the Aqua Plus 16v to control custom colors and

light shows in Hayward Generation 4 or later ColorLogic pool and spa lights.  Refer to the AQL-COLOR-

MODHV manual for details on how to configure an Aux output for use with these lights. If a ColorLogic Module

is detected at power up, the Lights relay is under automatic control and is used to power the ColorLogic lights.

43

Instant Salt

3200 PPM (+=save)

Move to previous/next menu item

Press to load the “Instant Salt” into the averaged salt display

This display will be shown only if the chlorinator is enabled.

  This display shows “Instant Salt” or

“Instant Minerals” (if Chlor. Config. is set for “Display Minerals”).  The “Instant Salt” is calculated

based on the voltage, current (amps), and water temperature at the cell.  This is different than the

“average salt” value which is displayed as part of the default menu.  There are a number of reasons

why instant and average salt readings may differ.  Some of these include salt having just been added

to the pool and not yet thoroughly mixed, calcium buildup on the cell, and the cell aging.

pH 7.5            (On)
ORP 700 mV   (On)

No function
Move to previous/next menu item

if AQL-CHEM is used

This display will be shown only if sensing is enabled.

 This display shows both pH and ORP levels/

status when chemistry sensing is enabled via the Chemistry Configuration Wizard (requires the use of

AQL-CHEM Sensing  Kit).  The Aqua Plus 16v will refer to these levels to determine how much

chlorine to generate (ORP) and, if using an AQL-CHEM2 dispense kit, how much CO

2

 or acid to

dispense (pH).  Refer to the AQL-CHEM manual for specific information about these levels as well as

the recommended ranges.

Flow Switch

Flow

No function
Move to previous/next menu item

This display will be shown only if the chlorinator is enabled.

 The current status of the flow switch is

displayed.  There is a short delay when transitioning from flow to no-flow and a longer delay on the

transition from no-flow to flow.  The delay time is displayed.

Содержание Aqua Plus 16v

Страница 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Страница 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Страница 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Страница 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Страница 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Страница 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Страница 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Страница 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Страница 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Страница 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Страница 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Страница 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Страница 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Страница 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Страница 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Страница 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Страница 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Страница 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Страница 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Страница 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Страница 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Страница 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Страница 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Страница 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Страница 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Страница 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...

Отзывы: