Hayward Aqua Plus 16v Скачать руководство пользователя страница 24

21

Select the desired Freeze Protection speed from Spa Filter Lowest to Highest speed 
Move to next menu item

if “Freeze Protect” is enabled
and “Variable Speed” is selected

Spa Filter Pump 

1 Speed

Freeze Protect 

Enabled

Freeze Protect

High Speed

Lowest Speed

10%

Highest Speed

100%

Rotates between 1-speed (default), 2-speed and variable speed options

Toggle between Enabled (default) and Disabled Freeze Protection 

Toggle between high speed (default) and low speed 

Adjust the lowest speed desired for variable speed operation

Adjust the highest speed desired for variable speed operation

Move to next menu item

Move to next menu item or previous/next configuration menu

Move to next menu item

Move to next menu item 

Move to next menu item

if “Freeze Protect” is enabled
and “2-speed Filter” is selected

if “Variable Speed” is selected

if “Variable Speed” is selected

Spa Filter Config.

+ to view/change

Push to access Spa Filter options
Move to previous/next configuration menu item 

if “Pool & Spa Dual” is selected

External Input

Disabled

Toggle between Enabled and Disabled (default)
Move to previous/next configuration menu

Spa Filter Pump

For 2-speed pumps:  When a 2-speed pump is configured, one of  the AUX relays must also be

configured to control the low speed motor winding on the pump.  Refer to the appropriate sections in

the Installation manual for specific information regarding the control logic for 2-speed and variable

speed pump operation.

For the Hayward variable speed pump:  The Spa Filter (Aux1) relay is used to supply input power to

the pump.  The relay will be on when the filter pump output is on.  When the filter pump output is off,

the relay will be off.  On , Off and speed is controlled by commands sent to the pump.

Lowest Speed

This is the lowest speed that the variable speed pump is allowed to run at. It is used as the lower limit

in the Spa Low Speed Settings Menu. Set lowest speed from 10% (default) to 50%.

Highest Speed

This is the highest speed that the variable speed pump is allowed to run at. It is used as the upper limit

in the Spa High Speed Settings Menu.  Also, this is the speed that the pump will run during the first 3

minutes of operation anytime the pump has been off for more than 30 seconds. Set highest speed from

20% to 100% (default).

Freeze Protection

Freeze protection is used to protect the spa and plumbed equipment against freeze damage.  If freeze
protection is enabled and the AIR temperature sensor falls below the freeze threshold (selectable in
Filter Configuration Menu - page 20), the Aqua Plus 16v will turn on the spa filter pump to circulate the
water.

Freeze Protection Speed

This menu only appears if freeze protection is enabled and the pump is configured for 2-speed or

variable speed pump operation. If the pump turns on due to freeze protection only, the pump will run

at this speed.

2-Speed pumps: Select high (default) or low speed operation.

Variable Speed pumps: Select the desired speed (from Filter Lowest to Filter Highest speed).

External Input

When enabled, the filter pump will be forced off when the external input is active.  Note that freeze

protection will have precedence over this feature.

26

When activating Group functions, be aware that the most recent Group function that is initiated will

override any previous Group function.

Lights External Input Interlock

When Lights External Input Interlock is enabled, the lights output will be forced off when the external

input is active.  This will have precedence over freeze protection.  Lights External Input Interlock is not
available for solar, low speed filter pump, dimmer, group, super chlorinate, or pH dispense functions.

Lights Freeze Protection

This function helps protect equipment that is wired to the lights relay against freeze damage.  If Freeze

Protection is enabled and the AIR temperature sensor falls below the selected freeze temperature

threshold, the Aqua Plus 16v will energize the lights relay.  IMPORTANT:  this only enables operation

of the lights relay during freeze--see the “Filter Pump Config.” menu to enable freeze protection for the

main circulation system. Freeze Protection is not available for low speed filter pump, dimmer, group,

super chlorinate or pH dispense functions.

Lights Pump Speed

This is the speed of the filter pump when the Lights output is on.  The default selection is “Settings

Menu”.  This is the speed of the pump that has been selected in the Settings Menu for normal filter

operation. If an alternate speed is desired when the Lights output is on, push “+” or “-” and select

from “Filter Lowest” to “Filter Highest” in 5% increments.

NOTE: The configuration parameters for all Aux outputs are the same as shown below for Aux1.  PS-4: Aux1 and Aux2. PS-8:

Aux1 through Aux6. PS-16: Aux1 through Aux14. Also note that for the PS-16, Valves7, 8, 9 and 10 are turned On/Off with the
control function selected for Aux7, 8, 9, and 10, respectively.

Aux1 Pump Spd

Settings Menu

Select Settings Menu (default) or desired pump speed (Filter Lowest to Highest)
Move to previous/next configuration menu 

if filter pump is set to variable speed

and the relay type is set to standard

Aux1 Config.

+ to view/change

Aux1 Function

Manual On/Off

Aux1 Group

Filter: Unaffected

Aux1 Group

Timer: None(Manual)

Aux1 Name

Cleaner

Aux1 Relay

Standard

Push to access Aux options

Options available depend on the function that is selected

Rotates between Manual On/Off (default),Countdown Timer and Timeclock

Rotates between all available names 

Toggle between Standard (default), Dimmer, ColorLogic and VSP 

Move to previous/next configuration menu 

Move to previous/next menu item or next configuration menu

Move to next configuration menu item

Move to next menu item

Move to next menu item or previous/next configuration menu

Aux1 Interlock

Disable

Aux1 Freeze

Disable

Toggle between Enabled and Disabled (default) Aux1 Interlock

T

oggle between Enabled

and Disabled Aux1 Freeze

(default)

Move to next menu item

Move to previous/next configuration menu

for all functions except solar, dimmer relay,super chlorinate

for all functions except solar, dimmer relay,super chlorinate

low speed, group and pH dispense

low speed, group and pH dispense

for all functions except dimmer relay, super chlorinate
low speed, group and ph dispense

for group function only

for group function only

for manual on/off, countdown

timer and timeclock functions

Move to next menu item

Rotates between 

Manual On/Off (default), Countdown Timer, Low Speed- Filter,

Timeclock, Solar, Low Speed-Spa Filter, Group, Super Chlorinate, and pH Dispense

Aux1 Ext Input

Disabled

Toggle between Enabled and Disabled (default)
Move to previous/next configuration menu

!

 WARNING:  Do not use the Aqua Plus 16v to control an automatic pool cover.  Swim-

mers may become entrapped underneath the cover.

NOTE: If “Pool and Spa-Dual” is selected, Aux1 is dedicated to use as the spa filter. Its Name is set to Spa Filter, the Function
is set to Timeclock and Interlock is set to Disabled. These can’t be changed

.

Содержание Aqua Plus 16v

Страница 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Страница 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Страница 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Страница 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Страница 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Страница 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Страница 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Страница 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Страница 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Страница 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Страница 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Страница 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Страница 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Страница 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Страница 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Страница 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Страница 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Страница 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Страница 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Страница 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Страница 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Страница 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Страница 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Страница 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Страница 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Страница 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...

Отзывы: