17

Super Chlorinate

The Aqua Plus 16v can be programmed to Super Chlorinate the pool or spa while running a group command.

When the Group starts, the Super Chlorinate cycle will begin.  Super Chlorinate will continue until the preset time

expires (see Timers Menu/Super Chlorinate Hours) or until the Group turns off.  Changing the Super Chlorinate

state using the Settings Menu, the Aqua Pod Super Chlorinate button, or a Super Chlorinate assigned Aux/Lights/

Valve button will temporarily cancel the Group’s control of Super Chlorinate until the next time the Group is

activated.

Variable Speed in Groups

The Aqua Plus 16v can be programmed to use alternate pump speeds while running group commands. This allows

the pump(s) to be set to a higher or lower speed than normal, while the group is activated. When the group stops,

the speed will return to its normal setting.

Changing the speed setting while the group is running will make the group release the alternate speed setting and

revert back to the normal speed setting. Any changes that are made at that point will affect the normal speed

setting.  The next time the group is activated, the speed will return to the group speed setting that was originally

programmed in the Configuration Menu. To change the speed setting while the group is running, go to the Settings

menu and press the +/- button while “Group Control” is displayed.  The speed setting will change to the normal

speed setting.

Virtual Buttons

The Aqua Plus 16v offers 8 auxiliary outputs with limited functionality.  These aux outputs (7-14) can only be

assigned to the Super Chlorinate function (if the Chlorinator is enabled), ColorLogic Lights control or to a Group

function.  Refer to the following programming information when assigning functions to the virtual auxiliary outputs.

Configuration Menus

Each item needs to be programmed and may contain additional sub-menu items.  Refer to the following pages for

information on programming.

Cell Type

T-CELL-15

Rotates between available Cell types
Move to next menu item

Move to next menu item

Chlorinator

Enabled

Display

Salt

Chlor. Config.

+ to view/change

Toggle between Display Salt (default) and Minerals 

Toggle between Chlorinator Enabled and Disabled (default) 

Move to previous/next configuration menu

Move to next configuration menu

Push to access Chlorinator option

Cell Type

T-CELL-15

Chlorinator

Enabled

Display

Salt

Chlor. Config.

+ to view/change

Chlorinator

The Aqua Plus 16v is shipped with the chlorinator enabled. The cell and flow switch must be installed

and the Aqua Plus 16v will automatically chlorinate both the pool and spa according to the desired

output setting (see Settings Menu in the Operation manual).  If disabled, all displays relating to the

chlorinator will be suppressed.

When the chlorinator is enabled, the Aqua Plus 16v will automatically detect and control any Aqua

Rite(s) that is installed in the system.

Display

Allows for the display of salt (default) or mineral values.

Cell Type Selection

The Cell Type Menu appears after “Display Salt/Minerals” in the Chlorinator Configuration Menu.

The options are T-CELL-15 (default), T-CELL-9, T-CELL-5 or T-CELL-3.  Make the proper selection

based on the chlorinator cell that is used in your system. Refer to the information below.

"T-CELL-3" = T-CELL-3, GLX-CELL-3-W

"T-CELL-5" = GLX-CELL-5, GLX-CELL-5-W

"T-CELL-9" = T-CELL-9, GLX-CELL-9-W

"T-CELL-15" = T-CELL-15, GLX-CELL-15-W

30

Group 

 – the valve operates when the Group function is initiated and shuts off when the Group

function is terminated.  See valve3 Group section for operation information for the Group function.

Super Chlorinate 

 – The Super Chlorinate function can be assigned to any Aux, Lights or Valve

button.  This allows the user to simply hit a button to start a Super Chlorinate cycle, rather than using

the Settings Menu.  Note that only one button can me assigned to this function.

Valve3 Interlock

If “Enabled”, this feature will override the function (timeclock, manual on/off, countdown timer or in-

floor cleaner) selected above and turn the valve off whenever the filter pump is off or the pool/spa

suction/return valves are set to “spa only” or “spillover” operation.   Interlock is not available with

solar, group or super chlorinate.

Valve3 Group

The valve3 Group function allows the user to perform multiple tasks with a single push of the VALVE3

button. When setting up a Group function, refer to page 15 for specific programming information.

There are two Group menus; the first menu determines how the group command will be initiated

(Manual On/Off, Countdown Timer, or Timeclock) and the second menu selects the desired functions

and their respective control parameters.

When activating Group functions, be aware that the most recent Group function that is initiated will

override any previous Group function.

Valve3 External Input Interlock

When Valve3 External Input Interlock is enabled, the Valve3 output will be forced off when the external

input is active.  This will have precedence over freeze protection. Valve3 External Input Interlock is not
available for solar, group, and super chlorinate.

Valve3 Freeze Protection

This function protects the pool and plumbed equipment against freeze damage.  If Freeze Protection

is enabled and the AIR temperature falls sensor falls below the selected freeze protection temperature,

the Aqua Plus 16v will turn on the valve to allow circulation of the water.  IMPORTANT:  this only

enables operation of the valve3 output during freeze--see the “Filter Pump Config.” menu to enable

freeze protection for the main circulation system. Freeze protection is not available for group or super

chlorinate functions.

Valve3 Pump Speed

This is the speed of the pump when the Valve3 output is on.  The default selection is “Settings Menu”.

This is the speed of the pump that has been selected in the Settings Menu for normal filter operation.

If an alternate speed is desired when the Valve3 output is on, push “+” or “-” and select from “Filter

Lowest” to “Filter Highest” in 5% increments.

6B Spa Config.

+ to view/change

6B A,  Button 1

Pool/Spa

Select 6B Spa

A

Push to access the 6 Button Spa Side Remote options

Rotates between System Off, Pool/Spa, Filter, Lights, Heater1, Valve3,

Valve4, and all available Aux outputs

Rotates between all available remotes

Move to previous/next configuration menu 

Move to previous/next menu item or next configuration menu

Move to next menu item

if AQL-SS-6B is connected

Select 6B Spa

This menu only appears if more than one AQL-SS-6B is detected at power up.  Select which of the

available remote controls (A, B or C) is to be configured.

6B A,  Button 1

This menu allows the user to map each button of the AQL-SS-6B to one of the standard Aqua Plus 16v

functions.  The default selections are:  Button 1 - Pool/Spa, Button 2 - Filter, Button 3 - Lights, Button

4 - Heater1, Button 5 - Aux1 and Button 6 - Aux2.

Содержание Aqua Plus 16v

Страница 1: ...required to increase Add baking soda to increase Stabilizer 60 80 ppm Add cyanuric acid to increase Calcium 200 400 ppm Add calcium to increase Electrolytic Cell inspect clean Refer to section in manu...

Страница 2: ...totheoriginalowner Proofofpurchaseisrequiredforwarrantyservice Ifwrittenproofofpurchaseisnotprovided themanufacturing date code will be the sole determinant of the date of installation of the product...

Страница 3: ...enu 32 Quick How To Operate the Spa Manually 33 Guide Operate the Spa Automatically 33 Set the Heater Temperature 33 Set the Chlorinator Output 33 Start Stop Superchlorination 34 Program a Timeclock 3...

Страница 4: ...solarheater Bothmanualandautomatic programmed operationare available All of the control functions can be programmed at a display keypad which is part of the main unit typically located near the pool e...

Страница 5: ...installing this product as part of a saline water purification system in a pool or spa using natural stone for coping or for immediately adjacent patios decking a qualified stone installation special...

Страница 6: ...Valve4 or Heater2 See Configuration Menu System Off remote displays or Service main unit display Air Sensor 94 F Cell Temp Sensor 77 F Solar Sensor Short circuit Water Sensor Open circuit Spa Sensor O...

Страница 7: ...tandard Relay Manual operation of all relays LIGHTS AUX1 AUX6 is identical Assuming that the relay iscurrentlyoff simplypresstheappropriatebuttontoturnontherelay Iftherelaydoesnotturnon itprobablyis d...

Страница 8: ...the time remaining will be displayed on the remote display keypad s Pressingthe SERVICE buttonagain willreturntheAquaPlus16vtonormal automatic operation SeeTrouble shooting DiagnosticInformationformor...

Страница 9: ...is invalid Cell Power Error If a chlorinator cell power error is detected on the printed circuit board No Flow Filter Pump If the filter pump is on and the flow switch indicates no flow for 15 minutes...

Страница 10: ...sary before adding salt High Salt Amps Minerals TheAqua Plus 16v will stop generating chlorine under certain high salt condi tionsinordertoprotecttheinternalelectronicsfromdamage Theonlywaytolowerthes...

Страница 11: ...er FILTER 39 System Maintenance Tomaintainmaximumperformance itisrecommendedthatyouopenandvisuallyinspectthecellevery3months oraftercleaningyourfilter TheAquaPlus16vwillremindyoutodothisbydisplayingth...

Страница 12: ...peed Set the desired Filter Speed 1 from the Filter Lowest to the Filter Highest Set the desired Spa Filter Speed 1 from the Spa Filter Lowest to Spa Filter Highest Move to next menu item Aux2 Speed 9...

Страница 13: ...s enabled This setting determines the speed of the pump during low speed pool or spillover operation This value can be set from Lowest Speed to 50 in 5 increments 50 is default For PS models using dua...

Страница 14: ...to the distance between the Base Receiver and the remote device being too great or may be due to interference caused by other RF equipment operating in the neighborhood Try using the Change Channel c...

Страница 15: ...and filter operation set to pool only the valves will switch to the pool only position Refer to page 12 for general notes regarding timeclock programming For two speed or variable speed pumps this set...

Страница 16: ...d stop times to previous next menu item or or Lights CountDn 0 20 Adjust time setting Manual On Off 0 05 0 10 0 015 Move to previous next menu item Note Separate chlorinator output levels for the pool...

Страница 17: ...the Lights relay it should be marked on the label inside the door Then press the appro priate button to turn on the jets blower Operate the Spa Automatically 1 Pressthe MENU buttonrepeatedlyuntil Time...

Страница 18: ...7P Adjust time setting Adjust time setting Manual On Off 0 05 0 10 0 15 Move between start and stop times to previous next menu item Move to previous next menu item Valve3 all 8 30A to 4 00P Valve3 0...

Страница 19: ...of the standardAqua Plus 16v functions The default selections are Button 1 Pool Spa Button 2 Filter Button 3 Lights Button 4 Heater1 Button 5 Valve3 Button 6 Valve4 Button 7 Aux1 and Button 8 Aux2 Di...

Страница 20: ...L 15 T CELL 15 GLX CELL 15 W 30 Group the valve operates when the Group function is initiated and shuts off when the Group function is terminated See valve3 Group section for operation information for...

Страница 21: ...ool Only and Spillover are available 29 NOTE The configuration for Valve3 and Valve4 are identical However if Heater2 was enabled then the Valve4 configuration will not appear a single relay is used t...

Страница 22: ...en they want to control the filter equipment Asheet of small name labels is included with theAqua Plus 16v main unit and each remote display keypad so that appropriate pushbuttons can be labeled the s...

Страница 23: ...name as a help to technicians who may service this system at a later date Aux1 Function Manual On Off default the aux relay will alternate between turning on and off when the aux button is pressed The...

Страница 24: ...d the lights output will be forced off when the external input is active This will have precedence over freeze protection Lights External Input Interlock is not available for solar low speed filter pu...

Страница 25: ...can be used to control other pool devices that may require these options The function of each option is shown below Manual On Off the lights relay will alternate between turning on and off when the LI...

Страница 26: ...lter is configured for 2 speed operation During default operation high speed mode is used whenever the solar heater is on If Allow Low Speed is enabled low speed pump operation will be allowed during...

Отзывы: