HAUBER-Elektronik GmbH
13
Half Shell
Arrow and Eye
Sign
Fig. 14: Fastened Safety Clip
Fig. 15: Protective Cover
Fig. 16: Fastened Protective Cover
Fig. 13: Safety Clip
Plug in the connection cable socket into the M12-plug completely.
(Pay attention to the code cam!).
15.2
Zone-2-22 - Fastening Safety Clip / Protective Cover
1.
Disconnect mains / electric circuit.
2.
Separate both shell halves of the fuse clip with a screw driver.
3.
Fasten protective cover and skrew it tightly onto the sensor plug.
1.
2.
3.
Tighten firmly the lock-nut of the connection cable socket by hand.
Fasten the safety clip against accidental disconnection of the plug connection:
1.
Put both shell halves of the safety clip around the plug connection.
2.
Press together by hand both shell halves of the safety clip until the
catch lock snaps in.
3.
Put the arrow connected to one shell halve around the cable, then stick
it through the eye on the other end, so that the notice sign is readable
alongside the cable.
Fastening Protective Cover
Fastening Safety Clip
Disassemble the safety clip and mount the protective cover:
The operation of variant Zone-2-22 is not permitted without the safety clip, to avoid
accidently disconnecting the plug-in connection! Otherwise danger of explosion because of
sparkling, when operating in explosion endangered areas!
After disconnecting the plug connection the protective cover has to be mounted!