12 HASCO hot runner
10. Menu items
Menu items
Ex works
Value range
Comment
P00 Offset cold junction temperature
0
-9.9 – 9.9
°C
P02 Re-determine control parameters
1
0 – 1
1= activated
P03 Edit established dead time
X
0 – 100
P04 Manual entry of dead time
0 – 100
P05 Display residual time soft start
X
sec.
P06 Soft start duration
300
120 – 999
sec.
P07 Upper temperature alarm limit
10
0 – 500
0 = deactivated
P08 Lower temperature limit
10
0 – 500
0 = deactivated
P09 Temperature alarm mode
1
0 = Off / 1 = ON
P10 Min. load current
0.2 A
0 – 16 A
0 = deactivated
P11 Max. heating output for soft start
35%
0 – 100%
P12 Max. heating output after soft start
100%
0 – 100%
P13 Max. heating output in manual mode
100%
0 – 100%
P14 Conversion 50 / 60Hz
50Hz
50 – 60Hz
P15 Language
0
0 – 1
0 = German
1 = English
P16 Display brightness
0
0 – 1
P17 Soft start ON = 1 / OFF = 0
1
0 -1
P18 No soft start as of actual temperature
100°C
50 – 100°C
P19 Max. setpoint value
500°C
30 – 500°C
P20 Automatic switch to manual mode
0
0 -1
0 = deactivated