background image

2

 Dry Seasoned Wood Only!                                                              3-90-798                                                                 Save These Instructions

Oakleaf Woodburning stove

Hearth & Home Technologies welcomes you to our tradition of excellence! By choosing a Harman appliance, 
you have become part of our commitment to meeting the heating needs of consumers with the most distinctive, 
powerful and responsible home heating products available. 
The Oakleaf has huge features in an elegantly small package. With a heating capacity of 1400 to 1600 ft²,  The 
Oakleaf takes advantage of Harman’s 30+ years of stove design, technology and manufacturing. The Firedome 
secondary combustion system provides for super-clean burning and minimal maintenance. The top-loading feature 
makes for more convenient loading, with enough fuel for an all day burn.

We wish you and your family many years of enjoyment in the warmth and comfort of your hearth appliance.
Thank you for choosing Harman.

Harman Home Heating

A division of

 

Hearth & Home Technologies, Inc.

352 Mountain House Road

Halifax, PA 17032

www.harmanstoves.com

When This Room Heater Is Not properly Installed, 

a House fire May Result.  To Reduce The Risk Of 

fire, follow The Installation Instructions. Contact 

Local Building Or fire Officials about Restrictions 

and Installation Inspection Requirements In your 

area.

This Label is located on the rear of the appliance. It contains important safety test information as well as the 

clearances to combustible materials. The label also contains the appliance serial number. For your records, 

copy your serial number and purchase date here.

Serial #: ________________________  

 

Date of Purchase: ________________________

Report #/ Raport # 135-S-26-6.2

Tested to / Testé à: UL1482-10, and ULC S627-00 

Test Date: August 2010
Approved For Use in Mobile/Manufactured Homes- 

USA ONLY

This appliance is also approved for installation into a shop.

“PREVENT HOUSE FIRES”

Install and use only in accordance with manufacturer’s installation and operation instructions 

and local codes. In absence of local codes, installation must meet minimum requirements of 

NFPA 211 in USA. Refer to manufacturer’s instructions and local codes for precautions required 

for passing chimney through a combustible wall or ceiling. 

WARNING FOR MANUFACTURED HOMES:

 (US Only) Do not install appliance in a sleeping 

room. An outside air inlet must be provided. The structural integrity of the manufactured home’s 

floor, walls, and ceiling must be maintained.

Flue connector pipe must be 6” diameter, minimum 24 MSG blue steel. Chimney must be factory   

                built 103HT or masonry construction.

                Contact Local Building or Fire Officials About Restrictions and Installation       

                Inspection In Your Area.

DO NOT CONNECT THIS APPLIANCE TO A CHIMNEY SERVING ANOTHER APPLIANCE.

FOR USE WITH SOLID WOOD FUEL ONLY

 Do not burn coal.

DO NOT Overfire - If Heater or chimney connector glows, you are overfiring.

Optional Blower

 

Harman #1-00-797032:

 Electrical Rating 115 VAC, 60Hz, 1AMP Maximum 

Route power cord away from unit. 

Replace glass only with 5mm ceramic, available from your dealer.

Combustible flooring must be protected with an approved 0.45R hearth board.

Appliance must be installed with the legs attached. Do not obstruct airflow under the appliance.

DANGER: Risk of Fire or Explosion - Do not burn garbage,  gasoline, drain oil or other 

flammable liquids.

WARNING: Risk of Fire 

Do not operate with fuel loading or ash removal doors open. 

Do not store fuel or combustibles within marked clearances.

Inspect and clean chimney and connector regularly- Under certain conditions of use, 

creosote buildup may occur rapidly.

The Bypass Damper must be opened prior to opening any load or ash door.

Do not install a grate or otherwise elevate the fire.

OAKLEAF Woodburning Stove

Poêle Du Bois OAKLEAF

Serial No.

№ de série

008

Rapport no 135-S-26-6.2

Conforme à UL 1482-10 et ULC S627-00

Date d’essai: Aug. 2010

Homologué pour les maisons mobiles et préfabriquées - É.-U. SEULEMENT

Cet appareil est également homologué pour être installé dans un atelier.

«ÉVITEZ LES INCENDIES DE MAISON»

N’installez et n’utilisez cet appareil que selon le mode d’installation et le mode 

d’emploi  du  fabricant  et  les  codes  locaux.  En  l’absence  de  codes  locaux, 

l’installation doit au minimum être conforme aux exigences de la norme NFPA 

211 aux É.-U. Voir dans les recommandations du fabricant et dans les codes 

locaux les précautions quant au passage d’une cheminée à travers un mur ou 

un plafond combustible.

MISE EN GARDE POUR LES MAISONS PRÉFABRIQUÉES : (É.-U. seulement) 

N’installez pas cet appareil dans une chambre à coucher. Une arrivée d’air de 

combustion extérieur doit être prévue. L’intégrité structurelle du plancher, des 

murs et du plafond de la maison préfabriquée doit être maintenue.

Le tuyau de raccord à la cheminée doit être d’un diamètre de 15,25 cm (6 po), 

au  minimum  en  acier  bleu  24  MSG.  La  cheminée  doit  être  en  métal  103HT 

d’usine ou construite en maçonnerie.

NE RELIEZ PAS CE POÊLE À UNE CHEMINÉE QUI SERT POUR UN AUTRE 

APPAREIL.

IL NE FAUT UTILISER QUE DU BOIS EN BUCHES.

  Ne chauffez pas TROP. Si 

l’appareil ou le raccord de cheminée rougit, c’est que le feu est trop puissant.

Éloignez le cordon électrique de l’appareil.

DANGER: 

Risque  de  décharge  électrique.  Débranchez  la  prise  avant  tout 

entretien.  Pour plus de détails, consultez le mode d’emploi.

Ne remplacez le verre que par du verre céramique de 5 mm à obtenir de votre 

détaillant.

L’appareil doit être installé avec ses pieds fixés. N’obstruez pas le passage d’air 

sous l’appareil.

DANGER: 

Risque  d’incendie  ou  d’explosion.  Ne  brûlez  pas  d’ordures, 

d’essence, d’huile de vidange ni aucun autre liquide inflammable.

MISE EN GARDE:

 Risque d’incendie.

N’utilisez pas le poêle lorsque les portes du foyer et du cendrier sont ouvertes.

Gardez le carburant et les matériaux combustibles 

en dehors des dégagements prescrits.

Inspectez et nettoyez fréquemment les conduits et la cheminée.

J

H

G

Floor Protection 

Requirements

Inches Millimeters

Sides / Côtés
Front- from glass/Devant, par rapport au verre
Rear / Arrière

8             203

 8             203

18            457

CLEARANCE TO COMbUSTIbLES /

 

DISTANCES MINIMALES DE SECURITE:

Date of Manufacture / Date de fabrication:

2010  2011  2012  JAN   FEB   MAR   APR   MAY   JUN   JUL   AUG   SEP   OCT   NOV   DEC

Fabriqué par: Harman Home Heating 352 Mountain House Road, Halifax PA 17032 (É.-U.)

P.N. 3-90-797

IGN

CAUTION:

 

HOT  WHILE  IN  OPERATION.  DO  NOT  TOUCH.  KEEP 

CHILDREN AND CLOTHING AWAY. CONTACT MAY CAUSE SKIN BURNS. 

SEE  NAMEPLATE  AND  INSTRUCTIONS.  KEEP  FURNISHINGS  AND 

OTHER COMbUSTIbLE MATERIALS A CONSIDERAbLE DISTANCE AWAY 

FROM THIS APPLIANCE.

ATTENTION:

 

CHAUD LORS DU FONCTIONNEMENT. NE TOUCHEZ 

PAS L’APPAREIL.GARDEZ LES ENFANTS ET LES VÊTEMENTS ÉLOIGNÉS. TOUT 

CONTACT PEUT ENTRAÎNER DES BRÛLURES DE LA PEAU.  RÉFÉREZ-VOUS À 

LA PLAQUE SIGNALÉTIQUE ET AU MODE D’EMPLOI. GARDEZ LE MOBILIER ET 

LES AUTRES MATÉRIAUX COMBUSTIBLES BIEN À L’ÉCART DE L’APPAREIL.

A C

D

b

E

F

F

C
D

b

A

Parallel 

Installation

Inches Millimeters

Back Wall / Entre mur arriereet l’appareil
Side Wall To Unit / Entre mur lateral et l’appareil
Back Wall To Flue Pipe / Entre  tuyau et le mur arriere
Side Wall To Flue Pipe / Entre tuyau et le mur lateral

14            330

17.5          444

17            432

26.75         679

F

E

Corner 

Installation

Inches Millimeters

Walls to Unit Body / Entre mur adjacent et l’appareil
Walls to Flue Pipe / Entre tuyau et le mur adjacent

14           330

21.75        552

Floor  protection  must  be  a  minimum  3/8” 

(9.5mm) of 0.84k material, or 0.45R. Must also 

be  placed  under  any  horizontal  sections  of 

flue connector, extending 2” (51mm) beyond 

the measurement of the pipe. Use of bottom 

heat shield required on protected floor.
Pour  protéger  le  plancher,  il  faut  sous  le 

poêle  un  matériau  (9.5mm  /  0.84k),  o  0.45R. 

Qui  doit  aussi  être  placé  sous  les  parties 

horizontales  du  tuyau  de  raccord  à  la 

cheminée et s’étendre à 51 mm (2 po) au-delà 

de la mesure du tuyau.

G

G

H

J

15.5”

5.875”

Made in U.S.A. of US and imported parts. / Fabriqué aux États-Unis-

d’Amérique par des pièces d’origine américaine et pièces importées.

E

REFER TO MANUFACTURER’S INSTRUCTIONS 

FOR CLEARANCES WITH ADDITIONAL VENT 

CONFIGURATIONS.

Содержание OAKLEAF 1-90-797000

Страница 1: ... children and adults to hazards of high temperatures High temperatures may ignite clothing or other flammable materials Keep clothing furniture draperies and other flammable materials away HOT SURFACES Glass and other surfaces are hot during operation AND cool down CAUTION Tested and approved for use with dry seasoned cordwood only Do Not Burn Wet or Green Wood Burning any other type of fuel will ...

Страница 2: ...Cet appareil est également homologué pour être installé dans un atelier ÉVITEZ LES INCENDIES DE MAISON N installez et n utilisez cet appareil que selon le mode d installation et le mode d emploi du fabricant et les codes locaux En l absence de codes locaux l installation doit au minimum être conforme aux exigences de la norme NFPA 211 aux É U Voir dans les recommandations du fabricant et dans les ...

Страница 3: ...Mobile Home US only A Mobile Home Installation 21 Section 7 Appliance Set Up A Outside Air Attachment 22 B Leveling The Appliance 22 C Optional Cooking Grill 22 D Optional Blower Kit 23 E Optional Rear Vent Rear Shield 23 F Optional Bottom Heat Shield 23 Section 8 Operating Instructions A Fuel Specifications 24 B General Operating Information 24 C Combustion Process 25 D User Controls 26 E Before ...

Страница 4: ... must be properly grounded to the frame of the mobile home and must never be installed in a room designated for sleeping The unit must have provisions for an outside air source when installed in a mobile home C Glass Specifications D Electrical Rating This appliance is equipped with 5mm ceramic glass Replace glass only with 5mm ceramic glass Please contact your dealer for replacement glass if need...

Страница 5: ... is designed to be as safe as possible it is important that you install a CO detector This is true for oil gas or coal burning products as well CO is not specifically heavier or lighter than air Therefore it is best to install the detector at table top level rather than on the ceiling like a smoke detector CO detectors are very sensitive and may sound an alarm for fumes other than CO or CO from so...

Страница 6: ... is needed to replace what the chimney draws away through the appliance B Fire Safety Maintain the designated clearances to combustibles Insulation must not touch the chimney You must maintain the designated air space around the chimney This space around a chimney is necessary to allow natural heat removal from the area Insulation in this space will cause a heat buildup which may ignite wood frami...

Страница 7: ... through the firebox and the open bypass damper loosen the retainer bolts on each of the flue collar and the cast iron plate With the bolts loosened turn the retainer to allow the piece to come free of the stove body Reposition the flue collar and the cast iron plate and secure them with the retainers by tightening the bolts You will now need to install a different upper rear heat shield See page ...

Страница 8: ...ements have been read and followed 6 The flue connector has been installed in accordance with the instructions herein 7 The proper clearances from the appliance and chimney connector to combustibles have been met 8 The masonry chimney has been cleaned and inspected by a professional or the factory built metal chimney is installed according to the manufacturers instructions 9 The chimney meets the ...

Страница 9: ...y 1 1990 25 635mm 26 2 665 5mm 27 2 691mm 29 2 742mm When configured for rear flue Floor to center of flue measures 23 5 597mm Air Intake 10 2 259mm 18 9 480mm 25 6 650mm Centered 27 6 701mm NOTICE When using rear flue configuration a new upper rear heat shield 1 00 797066 must be installed in place of the existing shield Weight 430 lbs Flue Size 6 inch Log Length Recommended 18 Average Emissions ...

Страница 10: ...t Pipe to Ceiling 16 407 mm F Minimum Vertical 0 0 mm For clearance reduction methods refer to NFPA 211 or Local Codes Pipe clearance may be reduced using double wall or insulated connector pipe provided that you adhere to the specified clearances from the stove itself Follow pipe manufacturer s guidelines Pipe clearance may be reduced using double wall or insulated connector pipe provided that yo...

Страница 11: ... Side Wall 17 432 mm B Unit to Back Wall 13 330 mm C Vent Pipe to Side Wall 26 5 673 mm Corner Installation D Shield Corner to Wall 14 356 mm E NFPA 211 specifies clearance of 18 457 mm Although vent clearance may be reduced using double wall pipe D must be followed B A C E D For clearance reduction methods refer to NFPA 211 or Local Codes NOTICE When using rear flue configuration a new upper rear...

Страница 12: ...value the better the protection Example 1 inch of Durock 0 52R In all installations the area under and around the stove must be protected from falling ash and live coals The area under a horizontal run of chimney connector must also be protected extending two 2 inches beyond the measurement of the horizontal connector Further guidelines for floor protection are as follows In the U S the floor prot...

Страница 13: ...oof space closet or other concealed space or through a floor or ceiling Whenever possible avoid passing the connector through a combustible wall if you must use an approved wall pass through described later in this section C Wall Pass thrus Depending on your local building codes and the pertinent provincial or national codes there are several choices for passing the chimney connector safely throug...

Страница 14: ...ys extend 3 ft 0 9 m above the highest point at which they exit from the roof Then the chimney must extend 2 ft 0 6 m above the highest point within a 10 ft 3 m radius Thus the 3 foot 2 foot 10 foot rule 3ft Above roof exit point 2ft Higher than anything within 10ft of the chimney NOTE The restriction of not venting more than one appliance to the same flue applies to the U S specifically While it ...

Страница 15: ...eferred method a breech pipe is a piece of steel pipe used the same way In Canada a breech pipe has ridges or protrusions to lock it firmly into the refractory cement In either case the chimney connector vents to the chimney through the thimble or breech pipe Using a thimble the connector slides completely inside the masonry to the inner edge of the flue liner and may be easily removed for chimney...

Страница 16: ...ng Installation with Factory Built Chimney Chimney Cap Factory Built Metal Chimney Sealed Storm Collar Finishing Collar Chimney Connector Cathedral Ceiling Installation with Factory Built Chimney Roof Flashing Roof Radiation Shield Roof Radiation Shield Cathedral Style Chimney Support Attic Radiation Shield The Chimney Connector Shall Not Pass Through an Attic or Roof Space Closet or Similar Conce...

Страница 17: ...le Flue Liner with Required Air Space Three Sheet Metal Screws per Joint of Chimney Connector Mantel and Trim Protection Floor Protection in Accordance with Solid Fuel Appliance Listing Airtight insulated Clean out Damper Closed and Sealed with Non Combustible Material Combustible Floor Floor Protection The Chimney Connector Shall Not Pass Through an Attic or Roof Space Closet or Similar Concealed...

Страница 18: ...upper rear heat shield 1 00 797066 must be installed in place of the existing shield Flue Liner with Required Air Space Stainless Steel Chimney Connector Must Extend to Flue Liner Minimum 8 Masonry Thickness in Front of Smoke Chamber Use Damper Adapter or Seal with Non Combustible Material Airtight insulated Clean Out Damper Plate is Removed or Fastened in Open Position Listed Fireplace Trim Prote...

Страница 19: ...lining system Follow liner manufacturer s instructions on insulation and support Floor Protection in Accordance with Solid Fuel Appliance Listing Damper Plate Removed or Fastened in Open Position Floor Protection Combustible Floor Use Damper Adapter or Seal with Non Combustible Material The Chimney Connector Shall Not Pass Through an Attic or Roof Space Closet or Similar Concealed Space a Floor or...

Страница 20: ...tected Ceiling Flue Liner with Required Air Space Listed or Approved Thimble Assembly 1 Clearance for Complexity Exterior Chimney or 2 Clearance for Interior Chimney and 2 Clearance for NFPA 211 Type Approved Thimbles Combustible Wall Sheetrock Airtight insulated Clean out Combustible Floor Damper Closed and Sealed with Non Combustible Material Mantel Trim Protection Floor Protection 16 The Chimne...

Страница 21: ...e vent manufacturer s instructions when installing in a mobile home 7 Installation shall be in accordance with the Manufactured Home and Safety Standard HUD CFR 3280 Part 24 8 The appliance must never be installed in a room designated for sleeping WARNING Installation must comply with Manufactured Home and Safety Standard HUD CFR 3280 Part 24 CAUTION Maintain structural integrity of mobile home Fl...

Страница 22: ...ake flex pipe into the stub on the rear of the Oakleaf and secure it with aluminum tape This air intake will supply outside air for the secondary combustion within the FireDome 7 Secure the trim ring in place for finishing the inside wall area 8 Seal around the rodent screen on the exterior wall using silicone caulking Outside Air Attachment B Leveling the Appliance To adjust the leveling bolts yo...

Страница 23: ... from the top vent shield and install the rear vent shield in it s place Height adjustment for blower use is done the same as with the top vent shield in place See D Optional Blower Installation above for detailed instructions F Optional Bottom Heat Shield Part 1 00 797058 must be purchased and installed whenever the Oakleaf is installed on a protected combustible floor The shield installs on four...

Страница 24: ...KEEP ALL SUCH LIQUIDS WELL AWAY FROM THE HEATER WHILE IN USE B General Operating Information 1 Draft Before you install and operate your Oakleaf wood stove please read the entire contents of this manual Pay particular attention to the explanation of draft and its effect on stove performance in the Installation section By following the installation and operating guidelines you will ensure proper dr...

Страница 25: ...s where the volatile gases contained in the wood are released and burned This represents most of the wood s heating capacity The final stage is the charcoal stage where the charcoal burns the remaining heat content in the wood fuel Ash remains after the burning is complete Within the primary firebox two or more of these stages of combustion are occurring at once Always be sure to provide adequate ...

Страница 26: ...llow this start up fire to burn for a few minutes keeping the bypass damper open Add about five more pieces of wood in the 2 to 3 inch 50 80mm size range making sure that the fuel bed is all the way across the firebox and staggered to allow airflow Close the door and allow this loading to burn a few minutes Add increasingly larger pieces of wood to the fire until you have a thick bed of hot embers...

Страница 27: ...rough the stove too quickly 2 You may have positioned the primary air control lever too far to the right 3 Inadvertently leaving the damper open or 4 Not keeping up with routine maintenance such as checking door gaskets for wear Overfiring results in excessive fuel consumption and may cause parts of the stove or chimney connector to glow red If you notice signs of overfiring reduce the air supply ...

Страница 28: ...ling During future burns be careful not to overload the stove with fuel so you will not be tempted to constantly operate at a low air control setting Other causes of poor ventilation or draft are icing exhaust fans a blocked outside air inlet and room air starvation If your stove is sluggish and you get occasional odor check these possibilities and increase the air flow in your home Seasonal clean...

Страница 29: ...is or yard waste 2 Door Glass Frequency As needed Weekly By User Whenever the view of the fire is obstructed or weekly clean the glass using a soft cloth dampened with standard household glass cleaner Never spray glass cleaner directly onto hot glass Apply the cleaner to the cloth then wipe the glass Fly ash allowed to accumulate on the glass may lead to permanent fogging or crazing of the glass I...

Страница 30: ... is very important to clean all ashes at the end of the heating season When cleaning the chimney connector above the appliance keep the bypass damper in the open position This will keep any loosened material from falling into the Firedome combustion chamber 6 Chimney Frequency As necessary Yearly By Qualified Service Technician Chimney Sweep The entire chimney should be professionally cleaned at l...

Страница 31: ... Dry Seasoned Wood Only Oakleaf Woodburning Stove 10Reference Materials Variable Speed Switch Power Cord Blower Thermostat Rocker Grounded to housing Switch Black Wire White Wire 2 1 Oakleaf Optional Blower Kit 1 00 797032 WIRING DIAGRAM ...

Страница 32: ...e Cast Iron Wood stove 1 90 797000 1 Black sept 2010 thru june 2011 1 90 797000 2 Charcoal 1 90 797000 3 goldenfire Beginning Manufacturing date sept 2010 Ending Manufacturing date active 1 2 7 6 8 23 22 3 4 5 28 27 26 24 25 21 20 19 18 15 16 17 12 11 10 9 13 14 ...

Страница 33: ...0 797022 y Gasket 1 4 Round PSA 15 FT 1 00 2312 y 8 Ramp Assembly w Gsket 1 10 797109 y Gasket 1 4 Round PSA 15 FT 1 00 2312 y 9 Brick Clip Set 1 00 249153 y 10 Damper Frame Assembly 1 10 797103A y Damper Adjustment Kit 1 00 249142 y Damper Handle 3 50 00500S y Damper Plate 4 00 797113 y Damper Rod 1 10 797036W y Gasket 1 4 Round PSA Damper Plate 15 FT 1 00 2312 y Gasket 3 8 Round LD Damper Frame ...

Страница 34: ...X 1 Z Pkg of 50 3 30 1134 50 y Bolt CB 5 16 18 X 2 Z Pkg of 25 3 30 4001 25 y Nut FHN 5 16 18 Z 5 Pkg of 100 3 30 8005 100 y 21 Center Brick 3 40 797020 y Gasket 1 4 Round PSA 15 FT 1 00 2312 y 22 Brick 12 X 6 X 1 1 4 3 40 86125 y Brick Clip 1 Set 1 00 249172 y 23 Center Seal Plate w Gasket 1 10 797034 Gasket 1 1 2X3 8 BULBPSA Center Plate 5 Ft 1 00 10050 y Gasket 1 4 Round PSA 15 FT 1 00 2312 y 2...

Страница 35: ...r after July 1 1990 0 8 5 Grams Per Hour SMOke 50 60 70 80 90 100 Wood heaters with higher efficiencies cost less to operate effIcIency Heat OutPut 9 600 to 24 700 btu use this to choose the right size appliance for your needs aSk dealer fOr HelP This wood heater will achieve low smoke output and high efficiency only if properly operated and maintained See owner s manual 3 90 799 ...

Страница 36: ...struction warranty coverage begins on the date of first occupancy of the dwelling or six months after the sale of the product by an independent authorized HHT dealer distributor whichever occurs earlier The warranty shall commence no later than 24 months following the date of product shipment from HHT regardless of the installation or occupancy date The warranty period for parts and labor for cove...

Страница 37: ...lt of normal use As a heating appliance some changes in color of interior and exterior surface finishes may occur This is not a flaw and is not covered under warranty Damage to printed plated or enameled surfaces caused by fingerprints accidents misuse scratches melted items or other external sources and residues left on the plated surfaces from the use of abrasive cleaners or polishes Repair or r...

Страница 38: ...38 Dry Seasoned Wood Only 3 90 798 Save These Instructions Oakleaf Woodburning Stove Service Maintenance Log Date Of Service Performed By Description Of Service ...

Страница 39: ......

Страница 40: ...Proudly Printed On 100 Recycled Paper ...

Отзывы: