Programmable Temperature & Humidity Controller
80
▶ Output specifications
▶ Contact input
▶ Communication specifications
Contact output(DO)
Up to 32 relay
A Contact
30 V DC 3 A max, 250 V AC 3 A
B Contact
NO : 30 V d.c. 5 A max, 250 V AC 5 A
Control output
SSR output
ON : 18 V DC Pulse voltage(800 Ω or more load resistance)
SCR output
4 - 20 mA DC (600 Ω or less load resistance)
Transmission output
Current output
4 - 20 mA DC
Load resistance 600 Ω or less load resistance
Output limit
-5.00 - 105.00 %
Output type
Specific value(PV), Setting value(SV), Output(MV), and random
Refresh interval 250 ms
Max. number of input
32 Contacts
Input type
No-voltage contact input
ON/OFF sensing resistor Minimum 1㏀ and less: On, maximum 10㏀ and more: Off recognition
Min. sensing time
0.25 sec
Operational conditions
During operation/Always
Contact function
Operation and stop/hold/step by DI ; User can define error screen.
Applied standard
RS485
Max. connection number 1:32 (address 1 ~ 99)
Communication type
2-wire
Synchronization
Asynchronous
Communication distance Approx. 1.2 km or less
Communication speed
9600, 19200, 38400, 57600, 115200 bps
Data Length
7/8 bits
Parity Bit
NONE / EVEN / ODD
Stop Bit
1/2 bit(s)
Protocol
PC-Link / PC-Link+SUM / MODBUS ASC / MODBUS RTU
Response Time
0 - 100 ms