Programmable Temperature & Humidity Controller
42
▶ Pattern information
2. Pattern management
① Select a pattern. Parameters can be set for individual patterns in this screen.
② Set the number of pattern cycles.
③ Displays name of selected pattern.
④ When current pattern operation is finished, set a pattern No. to continue operation.
If End mode is selected as a connected pattern, the connected operation is conducted.
⑤ Set end mode.
⑥ If a measurement is out of wait operation range of setting value, it waits for a segment to continue
during set wait operation time and then moves to next segment. Wait operation may be set by
segment of the pattern.
⑦ Set wait operation time. Set “0” to wait operation time in order to skip wait operation.
⑧ Set Start mode.
⑨ If SSV is set to Start mode, start SV can be set by channel.
Parameter
Description
Stop operation
Stop operation when current pattern is finished.
Holding seg
Continue operation with setting values of last segment.
Connect
Continue operation with the pattern set to the connected pattern No.
Parameter
Description
SSV
Start operation with start setting value.
SPV
Start operation with current specific value.
Parameter
Setting range
Default
Number of pattern cycles
1 ~ 999
1
Connected pattern No.
0 ~ 100
0
End mode
Stop operation, Holding seg, and Connect pattern
Stop operation
Temperature Wait
Temperature EU(0 ~ 100) [℃]
0.0
Humidity Wait
Humidity EU(0 ~ 100) [%]
0.0
Wait operation (M)
0 ~ 9999 [M]
0
Start mode
SSV, SPV
SPV
Temperature Start SV
Temperature EU(0 ~ 100) [℃]
0.0
Humidity Start SV
Humidity EU(0 ~ 100) [%]
0.0
[Pattern information parameter]
Fig. 50) Pattern information
①
③
⑧
②
④
⑤
⑦
⑥
⑨