6. Troubleshooting
8. Troubleshooting flowchart
Trouble
The compressor does not
start even though pressing
[START] button of Micom.
Is the red lamp on [TRIP]
of Micom on?
Is the [STOP] lamp of
Micom controller on?
Is the start standby message
displayed on the LCD of
Micom controller?
Is the rated power supplied
to the compressor?
Is the schedule operation
lamp on or is the schedule
operation mode selelcted?
The compressor needs
inspecting in detail. Please
contact your dealer or out
A/S service center.
Defect power supply
burnt fuse within Micom PCB
For fuse location, refer to page 34
For control circuit, refer to page 64
High P1 internal pressure or
63A switch fault
High P2 pressure
Abnormal power or
control circuit
Schedule mode selection
Schedule operation
Main motor overload trip
Fan motor overload trip
Pressure sensor fault
Temp. sensor fault
Main motor reverse phaes
Checklist
Potential trouble causes
Y
N
N
Y
N
Y
N
Y
N
Y
Содержание GRH 3 series
Страница 1: ...User s Manual of Compressor...
Страница 60: ...60 Hanshin 8 Control System 8 1 Compressor Configuration Layout 8 Control System...
Страница 62: ...62 Hanshin 8 Control System 2 Micom Controller GRH3 50A 100A...
Страница 63: ...63 GRH3 25A 30A 35A 50A Star delta GRH3 star delta User s Manual...
Страница 64: ...64 Hanshin 8 Control System GRH3 75A 100A Star delta...
Страница 74: ...74 Hanshin 12 Quality Warranty 13 Outside Drawing by Models 1 GRH3 20A 25A 30A 35A 13 Outside Drawing by Models...
Страница 75: ...75 2 GRH3 50A GRH3 star delta User s Manual...
Страница 76: ...76 Hanshin 13 Outside Drawing by Models 3 GRH3 75A 100A...
Страница 77: ...4 GRH3 75W 100W GRH3 star delta User s Manual 77 Appearance...
Страница 79: ......