Hansen APP08 Скачать руководство пользователя страница 6

6

APP-001b
APR 2007

the liquid level gradually falls, causing the float ball to 
fall. This changes the SPDT switch position of the liquid 
level float switch and energizes the purge gas solenoid 
valve (C) and the water bubbler fill line solenoid valve (D), 
allowing noncondensible gas to bleed through the orifice 
plate into the water bubbler. As air is released into the 
water bubbler, the liquid refrigerant level in the purger 
float ball chamber rises.

The control software operates each specified remote 

purge point solenoid valve in sequence.

The make -up liquid from the low-pressure pumped 

liquid line typically contains a small percentage of water 

dissolved in the liquid ammonia. This is the water the 

AUTO-PURGER Plus will remove from the refrigeration 

system. Liquid ammonia and water are brought into the 
evaporator chamber of the purger, but only ammonia 
vapor can exit through the suction line.  Gradually 
the concentration of water in the evaporator chamber 

increases with time. When the concentration of water in 
the evaporator chamber reaches about 25% water / 75% 

ammonia, as detected by the water concentration sensor, 
the AUTO-PURGER Plus switches to the CONCENTRATING 
WATER mode.  The purger stops collecting air, isolates 
the mixture of water and ammonia, and energizes the two 
electric heaters.  About half the energy to concentrate 
the water comes from the two electric heaters, and the 
other half comes from the foul gas that continues to flow 
through the purger.  The heaters remain energized until the 
ammonia water solution is heated to 185°F (85°C), except 
for suction pressures in a vacuum.  This corresponds to a 
concentration of about 10% to 20% ammonia and about 
80% to 90% water.  In a vacuum, water boils at lower 
temperatures, so the set point to which the ammonia 
water solution is heated is reduced to an appropriately 

lower temperature depending on the suction pressure as 

detected by the low side pressure transducer.

The AUTO-PURGER Plus will prepare the concentrated 

water for draining, but the computer software will not 
allow draining until an operator presses a button to permit 
draining.  The suction line solenoid valve (E) shuts.  The 
Control Console indicates READY TO DRAIN. OPEN WATER 
PURGE SHUT-OFF VALVE THEN PRESS “OK” BUTTON.  

The system remains in this condition until an operator 

opens the water purge line shut-off valve and presses the 
OK button on the Control Console.  See Figure 5.

SECTION 3   AUTO-PURGER PLUS OPERATION

The AUTO-PURGER Plus is designed to automatically start-

up and operate without the assistance of plant personnel. 
Beginning at star t-up, the following is a description of 
the refrigerant flow through a purger when all connecting 
shut-off valves are open. See Figure 4.

START-UP

Make sure all piping, electrical connections, and settings 
are complete as described in this bulletin.  Open the foul 
gas, low-pressure pumped-liquid, low-pressure liquid 
return, and suction line shut-off valves. Open the purge 
gas valve.  The water purge line shut-off valve should 
remain closed at this time (open only while draining 
water).  On star t-up, the AUTO-PURGER Plus enters a 
COOLING DOWN stage. (The display indicates 3333.) In 
this stage, liquid refrigerant fills and cools the purger. 

The low-pressure pumped-liquid line solenoid valve (B) 

energizes to feed refrigerant to the low-pressure flooded 
evaporator. The liquid make-up level sensor, located in the 
evaporator chamber, senses when the flooded evaporator 

is full and closes the low-pressure pumped-liquid line 

solenoid valve (B).

At the same time the flooded evaporator is cooling, the 

control software energizes the first purge point solenoid 
valve. Foul gas enters the high-pressure air separator 
chamber and condenses to fill the high-pressure air 
separator chamber with liquid. When the float switch 
chamber fills with liquid refrigerant, the float ball rises 
and pulls in the float switch magnet.

At approximately 20°F (–7°C) evaporator temperature, 

the evaporator shell temperature sensor switches the 
purger from the COOLING DOWN stage to STARTUP 
DEL AY MODE for 10 minutes, as indicated by the Control 

Console no longer displaying 3333. The control software 
will not allow any noncondensibles into the water bubbler 
until 10 minutes after the Control Console discontinues 

indicating 3333.

OPERATION

When the purger is in COLLECTING AIR AND WATER mode, 
a mixture of noncondensible gas and refrigerant flows 
into the purger.  The evaporator shell temperature sensor 
also allows solenoid valves (C) and (D) to open when the 
float ball is down (magnet away from tube).

The foul gas may carr y a cer tain amount of condensed 

refrigerant, which is captured by the liquid drainer before 
it enters the purger’s condenser coil. From the liquid 
drainer, the liquid is fed directly into the low-pressure 
liquid return line. If this separation does not occur, liquid 
refrigerant will fill the purger’s condenser and limit the 
condensing capacity of the purger.

The liquid-free foul gas enters the purger condensing 

coil, which is submerged in the flooded evaporator. The 
refrigerant condenses inside the coil. The condensed 
refrigerant and noncondensible gas then flow through a 
check valve and back into the air separator chamber. The 
condensed liquid refrigerant is removed from the high-
pressure air separator chamber through the liquid metering 
valve and to the low-pressure liquid return line.

Meanwhile, the noncondensible gas travels along the top of 
the air separator chamber and into the float ball chamber 
where it collects. As more noncondensible gases collect, 

Содержание APP08

Страница 1: ...RGER Plus is a totally automatic electronically controlled refrigerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are...

Страница 2: ...circumstances only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to b...

Страница 3: ...some cases a small high pressure auxiliary receiver is located at the outlet of one or more condensers This receiver should have a purge point at the top Where a high pressure float regulator is used...

Страница 4: ...ected into the purger The low pressure pumped liquid line feeds makeup liquid as required during purging The line contains liquid ammonia that typically is also contaminated with water which is to be...

Страница 5: ...mps electrical supply on a 15 amp circuit breaker are available All models have a 13 mm knockout on the side of the control cabinet to access the power connection terminal strip Any unused knockout ho...

Страница 6: ...connecting shut off valves are open See Figure 4 START UP Make sure all piping electrical connections and settings are complete as described in this bulletin Open the foul gas low pressure pumped liq...

Страница 7: ...there are no releases to atmosphere 1 WATER BUBBLER WATER BUBBLER OVERFLOW TUBE FOUL GAS LINE LOW PRESSURE PUMPED LIQUID LINE SUCTION LINE FILL LINE D B C FLOW REGULATOR GAUGE VALVE GAUGE VALVE LIQUI...

Страница 8: ...system parameters The operator can switch between the two message types by pressing the esc key Control Console Specifications Display Type Character LCD 4 lines by 20 characters w LED backlight Encl...

Страница 9: ...and the temperature of the plate heaters see figure 4 Another press of this key displays the pressures in the low side and the high side of the purger A final press of this key returns the display to...

Страница 10: ...follows air purge limit 60 minute limit normal 0 60 min startup 1 nolimit purge point enable 01 1 enable 0 skip 02 1 enable 0 skip 03 1 enable 0 skip 04 1 enable 0 skip 05 1 enable 0 skip 06 1 enable...

Страница 11: ...normal 7777 loss of lp liq will appear when the liquid make up solenoid valve has been energized for 30 minutes continuously ERROR HEATER FAULT will be displayed if the heaters are on longer than 4 ho...

Страница 12: ...1 psid 07 bar check valve in the water purge line to prevent reverse flow of water into the purger from the customer supplied container The water bubbler fill line has a check valve OPERATION OF PURG...

Страница 13: ...URGE GAS GAUGE VALVE WIDE OPEN DURING OPERATION CLOSED FOR SERVICING PURGER PURGE GAS 1 32 0 8 MM DIA METERING ORIFICE 0 07 BAR PURGE GAS TO WATER BUBBLER OR TO CUSTOMER SUPPLIED WATER BOTTLE CHECK VA...

Страница 14: ...r fill line valve The purger will pump down in several hours To accelerate the process attach ammonia hoses to the oil drain valves and pump out into a suction line Close the low pressure liquid retur...

Страница 15: ...por Trap H5600R Relief Valve 300 psi ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50 60 Hz 750 Watt 20 12...

Страница 16: ...ctional pushbutton several times until the pressures are displayed Verify that the high side pressure is greater than 80 psig 5 5 barg Action If the high side pressure displayed is less than 80 psig 5...

Страница 17: ...id line plugged strainers or the plastic shipping cap still in the liquid line flange Action Inspect piping for a closed shut off valve Open the shut off valves clean the strainer or remove the shippi...

Страница 18: ...18 APP 001b APR 2007 THIS PAGE INTENTIONALLY BLANK...