CONCENTRATING WATER mode. This information is
available for information only, and no action is required
by the operator related to the counts. The drain mode is
always set to 0, and can not be changed.
To change the display units, move the cursor with the / \
and \ / keys to the units: # line and press enter. Change
the value with the / \ or \ / keys, and press enter again.
Press esc to return to the menu.
The version menu item displays the software revisions
for the purger’s display keypad and for the purger’s plc.
PLC MESSAGES
“Active Purge Point ##” where ## indicates the active
purge point.
For 115VAC models, “Liquid Temp: ### ºF” will appear
during the CONCENTRATING WATER process.
For 220VAC models, “Liquid Temp: ### ºC” will appear
during the CONCENTRATING WATER process.
“READY TO DR AIN. OPEN WATER PURGE SHUT-OFF
VALVE THEN PRESS “OK” BUTTON.” will appear when the
process of CONCENTRATING WATER is complete and it
is ready to be drained.
“DRAINING IS COMPLETE. CLOSE WATER PURGE SHUT-
OFF VALVE THEN PRESS “OK” BUTTON.” will appear when
the APP is done draining and is ready to go back to its
normal mode of COLLECTING AIR/ WATER.
“Releasing Air” will appear when the APP is releasing
air.
“Concentrating Water” will appear during the process of
heating the ammonia /water solution.
CONTROL CONSOLE MENU HIERARCHY
The control console menu is as follows:
+air purge limit
60 minute limit: #
(normal=0, 60 min)
(startup=1,
nolimit)
+purge point enable
01:#
1=enable,0=skip
02:#
1=enable,0=skip
03:#
1=enable,0=skip
04:#
1=enable,0=skip
05:#
1=enable,0=skip
06:#
1=enable,0=skip
07:#
1=enable,0=skip
08:#
1=enable,0=skip
Model APP08 has purge points 01-08 as shown here,
model APP16 has purge points 01-16, model APP24 has
purge points 01-24. Model APPC does not have this
menu item.
+water collection
counts=
#
(600)
drain mode: 0
+display units
units:
#
(1=US)
(0=SI/metric)
+version
keypad FW= ####
plc FW= ####
To change the air purge limit, move the cursor with the / \
and \ / keys to the 60 minute limit: # line and press enter.
Change the value with the / \ or \ / keys, and press enter
again. Press esc to return to the menu.
To enable or disable individual purge points, move the
cursor with the / \ and \ / keys to the desired purge point
and press enter. Change the value with the / \ or \ / keys,
and press enter again. Press esc to return to the menu.
At system start-up, when a purger is initially installed in
a system that has fewer purge points than are available
on the purger (e.g., an APP08 used on system that has 5
purge points), the unused purge points must be set to 0.
The water collection parameters can not be changed and
are for information only. The counts indicate the time
in seconds that the water concentration as measured
by the water concentration sensor exceeds the
concentration set point. The concentration of water in
the purger evaporator must exceed 25% for 10 minutes
(600 seconds) continuously before the purge will enter