“Draining Water” will appear when removed water is 

draining from the APP. 

“Collecting Air/Water” will appear when the APP is operating 

normally.

“Star tup Delay Mode” will appear for 10 minutes after the 

APP evaporator shell cools to less than 40ºF (4ºC) and 

the foul gas pressure exceeds 80 psig (5.5 barg). 

“System Reset” will appear for 5 seconds after the System 

Reset key has been depressed. 

“2222 foul gas<80 psi” will appear when foul gas pressure 

is lost and the display units are set to US.

“2222 foul gas< 5 bar” will appear when foul gas pressure 

is lost and the diplay units are set to SI/metric.

“3333 evap temp>40 °F” will appear when the evaporator 

temperature is too warm for effective air purging and the 
display units are set to US.

“3333 evap temp> 4 °C” will appear when the evaporator 

temperature is too warm for effective air purging and the 
display units are set to SI/metric.

“4444 air purge>60min, Push RESET 4s to CLR” will appear 

when air has been released for 60 minutes continuously 
and the air purge limit is set to normal.

“7777 loss of lp liq” will appear when the liquid make-

up solenoid valve has been energized for 30 minutes 
continuously.

ERROR HEATER FAULT will be displayed if the heaters are 
on longer than 4 hours. This ERROR can only be cleared 
by depressing the “SYSTEM RESET” key. 

S e e   S e c t i o n   7,   Tr o u b l e s h o o t i n g   f o r   a d d i t i o n a l 

information.

MAINTENANCE ITEM, RTC BACKUP 
BATTERY

Replacement Batter y: 

DURACELL DL2032 or RAYOVAC CR2032

The  coin  cell  batter y,  3.0V  Lithium,  is  used  to  provide 

backup power to the real time clock. The batter y and 
batter y low indicator are located in the lower right corner 

of the PLC, see Figure 6. On certain models, the battery is 

located underneath a control module. The battery should 
be replaced 

ever y 5 years

  or  when  the  LOW  BATTERY 

LED is illuminated.

Batter y Replacement Procedure

The power to the AP Purger must be ON. 

Lift the batter y tab and press the batter y out with your 
finger or non-metallic tool.

To install a new batter y, the batter y polarity “+” must be 

to the top side. Lift the batter y tab and slide the batter y 
into place. Verify the LOW BATTERY LED is not illuminated. 
Procedure is complete.

DL2032

3V

LOW

BATTE

R

Y

CPU

PWR

DS7

DS6

DS5

RAM BACKUP
BATTERY

PLC

LOW BATTERY LED

BATTERY TAB

BATTERY REPLACEMENT

Figure 6

Содержание APP08

Страница 1: ...RGER Plus is a totally automatic electronically controlled refrigerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are...

Страница 2: ...circumstances only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to b...

Страница 3: ...some cases a small high pressure auxiliary receiver is located at the outlet of one or more condensers This receiver should have a purge point at the top Where a high pressure float regulator is used...

Страница 4: ...ected into the purger The low pressure pumped liquid line feeds makeup liquid as required during purging The line contains liquid ammonia that typically is also contaminated with water which is to be...

Страница 5: ...mps electrical supply on a 15 amp circuit breaker are available All models have a 13 mm knockout on the side of the control cabinet to access the power connection terminal strip Any unused knockout ho...

Страница 6: ...connecting shut off valves are open See Figure 4 START UP Make sure all piping electrical connections and settings are complete as described in this bulletin Open the foul gas low pressure pumped liq...

Страница 7: ...there are no releases to atmosphere 1 WATER BUBBLER WATER BUBBLER OVERFLOW TUBE FOUL GAS LINE LOW PRESSURE PUMPED LIQUID LINE SUCTION LINE FILL LINE D B C FLOW REGULATOR GAUGE VALVE GAUGE VALVE LIQUI...

Страница 8: ...system parameters The operator can switch between the two message types by pressing the esc key Control Console Specifications Display Type Character LCD 4 lines by 20 characters w LED backlight Encl...

Страница 9: ...and the temperature of the plate heaters see figure 4 Another press of this key displays the pressures in the low side and the high side of the purger A final press of this key returns the display to...

Страница 10: ...follows air purge limit 60 minute limit normal 0 60 min startup 1 nolimit purge point enable 01 1 enable 0 skip 02 1 enable 0 skip 03 1 enable 0 skip 04 1 enable 0 skip 05 1 enable 0 skip 06 1 enable...

Страница 11: ...normal 7777 loss of lp liq will appear when the liquid make up solenoid valve has been energized for 30 minutes continuously ERROR HEATER FAULT will be displayed if the heaters are on longer than 4 ho...

Страница 12: ...1 psid 07 bar check valve in the water purge line to prevent reverse flow of water into the purger from the customer supplied container The water bubbler fill line has a check valve OPERATION OF PURG...

Страница 13: ...URGE GAS GAUGE VALVE WIDE OPEN DURING OPERATION CLOSED FOR SERVICING PURGER PURGE GAS 1 32 0 8 MM DIA METERING ORIFICE 0 07 BAR PURGE GAS TO WATER BUBBLER OR TO CUSTOMER SUPPLIED WATER BOTTLE CHECK VA...

Страница 14: ...r fill line valve The purger will pump down in several hours To accelerate the process attach ammonia hoses to the oil drain valves and pump out into a suction line Close the low pressure liquid retur...

Страница 15: ...por Trap H5600R Relief Valve 300 psi ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50 60 Hz 750 Watt 20 12...

Страница 16: ...ctional pushbutton several times until the pressures are displayed Verify that the high side pressure is greater than 80 psig 5 5 barg Action If the high side pressure displayed is less than 80 psig 5...

Страница 17: ...id line plugged strainers or the plastic shipping cap still in the liquid line flange Action Inspect piping for a closed shut off valve Open the shut off valves clean the strainer or remove the shippi...

Страница 18: ...18 APP 001b APR 2007 THIS PAGE INTENTIONALLY BLANK...

Страница 19: ...ce schedule and the Safety Precautions Sheet supplied with this product Escaping refrigerant can cause injury especially to the eyes and lungs WARRANTY All Hansen products except electronics are guara...

Страница 20: ...poration 6827 High Grove Boulevard Burr Ridge Illinois 60527 USA Tel 630 325 1565 Fax 630 325 1572 Toll 800 426 7368 Email info hantech com Web www hantech com USA Asia Europe India Latin America Midd...

Отзывы: