Hansen APP08 Скачать руководство пользователя страница 2

2

APP-001b
APR 2007

MOUNTING INSTRUCTIONS

Mount the AUTO-PURGER Plus securely on a wall or 
sturdy steel channels capable of supporting 450 lbs (205 
Kg). Eight mounting holes in the frame are provided to 
support the unit. See Figure 1. The unit should be located 
in an accessible area, but away from moving equipment 
that could accidentally come in contact with the purger. 
Elevation with respect to condensers or high-pressure 
receivers is not critical. Do not punch access holes in the 
top of the control cabinet. Unused electrical entrances 
to the enclosure must be sealed to protect the controls 
from moisture.

The AUTO-PURGER Plus is normally installed in the 

compressor room where it can be monitored, but also may 

be installed outdoors where temperatures below freezing 

are not anticipated. Outdoor use in areas near falling or 
spraying water, or in constant high humidity areas is not 
recommended.

Install the float switch assembly on the purger by removing 
the packaging material and metal shipping tube.  Slip the 
float switch assembly over the enclosing tube being sure 
the float switch assembly bottoms on the neck on the 
enclosing tube.  Warning: Tighten the retaining screw such 
that the screw tip is in the groove of the neck assembly.  
If the float switch assembly is not properly positioned 
and retained, the switch may not function.

FOUL GAS PIPING

It is nearly impossible to predict where noncondensible 
gases (air) will accumulate. Therefore, purging at several 
points on the high-pressure side of the system is the best 
method for removing air from the system.

For multipoint purgers, the solenoid valves may be 
manifolded into one line to the purger. However, only one 
purge point should be purged at a time. Connecting two 
purge points together may result in gas flowing from one 
condenser to another due to unequal pressure drop, even 
though the difference in pressure drops is ver y small, 
for example ¼ psi (0.02 bar). The result is that even in 
the best of circumstances, only one point is effectively 
purged. The best practice is to purge each condenser 
and receiver circuit separately.

It is extremely important to install purge points at locations 
sure to be liquid free. Also, no liquid traps are desirable 
either before or after purge point solenoid valves. See 
Figure 2. The line from the purge point on the condenser 
to the AUTO-PURGER Plus should not pass through cold 
areas where fur ther condensing of the saturated gas can 
occur. If this cannot be avoided, the purge line must be 
insulated because flooded purge point lines will flood the 

AUTO-PURGER Plus with liquid, resulting in a temporar y 

halt of noncondensibles being removed.

AUTO-PURGER PLUS APP INSTALLATION DIMENSIONS

Figure 1

SECTION 2   INSTALLATION

LOW PRESSURE SEPARATOR
OIL DRAIN CONNECTION (1/4" FPT)

21.50"

[546 MM]

5.75"

[146 MM]

HIGH PRESSURE SEPARATOR
OIL DRAIN CONNECTION (1/4" FPT)

1" PVC OR 1" FPT WATER BUBBLER

DRAIN CONNECTION.

DO NOT INSTALL SHUT-OFF VALVE

IN WATER BUBBLER DRAIN LINE.

DO NOT RUN LINE MORE

THAN 10' (3 M) ABOVE BUBBLER.

WALL OR
COLUMN

.63"

[16 MM]

OUTLET

.75" [19 MM] CONDUIT KNOCKOUT
FOR REMOTE PURGE
POINT SOLENOID VALVE
CONNECTIONS

.50" [12 MM] CONDUIT KNOCKOUT
FOR POWER CONNECTION

.53" [14 MM] MOUNTING
HOLE (TYPICAL)

4.50"

[114 MM]

31.50"

[800 MM]

7.50"

[191 MM]

16.50"

[419 MM]

1/2" WATER LINE

12.00"

[305 MM]

3.62"

[92 MM]

8.94"

[227 MM]

1/4" FPT GAUGE VALVE

FLANGE UNION

1/2" FPT WATER
BUBBLER FILL LINE

CONNECTION

25.00"

[635 MM]

21.25"

[540 MM]

16.25"

[413 MM]

ACCESS HOLES IN THE TOP

DO NOT PUNCH ELECTRICAL

1" FPT SUCTION LINE CONNECTION

TO PROTECTED SUCTION ACCUMULATOR

SHUT-OFF VALVE

1/2" FPT FOUL GAS LINE CONNECTION FROM PURGE POINTS

ON HIGH PRESSURE CONDENSERS AND RECEIVERS

1/2" FPT LOW-PRESSURE PUMPED-LIQUID LINE CONNECTION

1/4" FPT GAUGE VALVE

1/2" STRAINER

FLOW REGULATOR

1/2" STRAINER

SHUT-OFF VALVE

1/4" FPT GAUGE VALVE

BUBBLER

2.50" [64 MM]

1.00"

[25 MM]

TYPICAL

1.50"

[38 MM]

4.19"

[106 MM]

12.00"

[305 MM]

8.62"

[219 MM]

1/2" FPT LOW-PRESSURE LIQUID-RETURN LINE CONNECTION

10.00"

[254 MM]

1/4" MPT CONNECTION
FOR WATER  PURGE LINE

35.00"

[889 MM]

RELIEF VALVE

3/4" FPT

11.00"

[279 MM]

TO CUSTOMER SUPPLIED CONTAINER

CONTROL CABINET

SHUT-OFF VALVE

WATER PURGE LINE
SHUT-OFF VALVE

1/2" STRAINER

Содержание APP08

Страница 1: ...RGER Plus is a totally automatic electronically controlled refrigerant noncondensible gas air and water purger for reducing the energy costs of operating an ammonia refrigeration system All models are...

Страница 2: ...circumstances only one point is effectively purged The best practice is to purge each condenser and receiver circuit separately It is extremely important to install purge points at locations sure to b...

Страница 3: ...some cases a small high pressure auxiliary receiver is located at the outlet of one or more condensers This receiver should have a purge point at the top Where a high pressure float regulator is used...

Страница 4: ...ected into the purger The low pressure pumped liquid line feeds makeup liquid as required during purging The line contains liquid ammonia that typically is also contaminated with water which is to be...

Страница 5: ...mps electrical supply on a 15 amp circuit breaker are available All models have a 13 mm knockout on the side of the control cabinet to access the power connection terminal strip Any unused knockout ho...

Страница 6: ...connecting shut off valves are open See Figure 4 START UP Make sure all piping electrical connections and settings are complete as described in this bulletin Open the foul gas low pressure pumped liq...

Страница 7: ...there are no releases to atmosphere 1 WATER BUBBLER WATER BUBBLER OVERFLOW TUBE FOUL GAS LINE LOW PRESSURE PUMPED LIQUID LINE SUCTION LINE FILL LINE D B C FLOW REGULATOR GAUGE VALVE GAUGE VALVE LIQUI...

Страница 8: ...system parameters The operator can switch between the two message types by pressing the esc key Control Console Specifications Display Type Character LCD 4 lines by 20 characters w LED backlight Encl...

Страница 9: ...and the temperature of the plate heaters see figure 4 Another press of this key displays the pressures in the low side and the high side of the purger A final press of this key returns the display to...

Страница 10: ...follows air purge limit 60 minute limit normal 0 60 min startup 1 nolimit purge point enable 01 1 enable 0 skip 02 1 enable 0 skip 03 1 enable 0 skip 04 1 enable 0 skip 05 1 enable 0 skip 06 1 enable...

Страница 11: ...normal 7777 loss of lp liq will appear when the liquid make up solenoid valve has been energized for 30 minutes continuously ERROR HEATER FAULT will be displayed if the heaters are on longer than 4 ho...

Страница 12: ...1 psid 07 bar check valve in the water purge line to prevent reverse flow of water into the purger from the customer supplied container The water bubbler fill line has a check valve OPERATION OF PURG...

Страница 13: ...URGE GAS GAUGE VALVE WIDE OPEN DURING OPERATION CLOSED FOR SERVICING PURGER PURGE GAS 1 32 0 8 MM DIA METERING ORIFICE 0 07 BAR PURGE GAS TO WATER BUBBLER OR TO CUSTOMER SUPPLIED WATER BOTTLE CHECK VA...

Страница 14: ...r fill line valve The purger will pump down in several hours To accelerate the process attach ammonia hoses to the oil drain valves and pump out into a suction line Close the low pressure liquid retur...

Страница 15: ...por Trap H5600R Relief Valve 300 psi ELECTRICAL 70 1088 Solenoid Coil DIN plug 115V 50 60 Hz 16 Watt 20 2428 Electric Heater 115V 50 60 Hz 750 Watt 20 2477 Electric Heater 230V 50 60 Hz 750 Watt 20 12...

Страница 16: ...ctional pushbutton several times until the pressures are displayed Verify that the high side pressure is greater than 80 psig 5 5 barg Action If the high side pressure displayed is less than 80 psig 5...

Страница 17: ...id line plugged strainers or the plastic shipping cap still in the liquid line flange Action Inspect piping for a closed shut off valve Open the shut off valves clean the strainer or remove the shippi...

Страница 18: ...18 APP 001b APR 2007 THIS PAGE INTENTIONALLY BLANK...

Страница 19: ...ce schedule and the Safety Precautions Sheet supplied with this product Escaping refrigerant can cause injury especially to the eyes and lungs WARRANTY All Hansen products except electronics are guara...

Страница 20: ...poration 6827 High Grove Boulevard Burr Ridge Illinois 60527 USA Tel 630 325 1565 Fax 630 325 1572 Toll 800 426 7368 Email info hantech com Web www hantech com USA Asia Europe India Latin America Midd...

Отзывы: